44
Inlet Pressure 14.0 in wc (3.4 kPa)or less; 0.3 in wc (0.07 kPa) Pressure Drop
Nominal
Pipe Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
131
90
72
62
55
50
46
42
40
38
¾
0.824
273
188
151
129
114
104
95
89
83
79
1
1.049
514
353
284
243
215
195
179
167
157
148
1¼
1.380
1060
726
583
499
442
400
368
343
322
304
1½
1.610
1580
1090
873
747
662
600
552
514
482
455
2
2.067
3050
2090
1680
1440
1280
1160
1060
989
928
877
2½
2.469
4860
3340
2680
2290
2030
1840
1690
1580
1480
1400
3
3.068
8580
5900
4740
4050
3590
3260
3000
2790
2610
2470
Table 18: Maximum Capacity of Schedule 40 Black Pipe in CFH* (Natural Gas) For Gas Pressures
of 1/2 psi (3.4 kPa) or Less
X. Gas Piping
(continued)
Inlet Pressure 14.0 in wc (3.4 kPa)or less; 0.5 in wc (0.12 kPa) Pressure Drop
Nominal
Pipe Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
172
118
95
81
72
65
60
56
52
50
¾
0.824
360
247
199
170
151
137
126
117
110
104
1
1.049
678
466
374
320
284
257
237
220
207
195
1¼
1.380
1390
957
768
657
583
528
486
452
424
400
1½
1.610
2090
1430
1150
985
873
791
728
677
635
600
2
2.067
4020
2760
2220
1900 1680
1520
1400
1300
1220
1160
2½
2.469
6400
4400
3530
3020 2680
2430
2230
2080
1950
1840
3
3.068
11300
7780
6250
5350 4740
4290
3950
3674
3450
3260
Nominal
Pipe Size,
Inc.
Inside
Valves (Screwed) - Fully Open
Screwed Fittings
Gate
Globe Angle Swing
Check
45°
Elbow
90°
Elbow
180 Close
Return
Bend
90 Tee
Flow
Through
Run
90 Tee, Flow
Through
Branch
½
0.622
0.4
17.3
8.7
4.3
0.7
1.6
3.5
1.6
3.1
¾
0.824
0.5
22.9
11.4
5.7
1.0
2.1
4.6
2.1
4.1
1
1.049
0.6
29.1
14.6
7.3
1.2
2.6
5.8
2.6
5.2
1¼
1.38
0.8
38.3
19.1
9.6
1.6
3.5
7.7
3.5
6.9
1½
1.61
0.9
44.7
22.4
11.2
1.9
4.0
9.0
4.0
8.0
2
2.067
1.2
57.4
28.7
14.4
2.4
5.2
11.5
5.2
10.3
2½
2.469
1.4
68.5
34.3
17.1
2.9
6.2
13.7
6.2
12.3
3
3.068
1.8
85.2
42.6
21.3
3.6
7.7
17.1
7.7
15.3
Table 19: Equivalent Lengths of Standard Pipe Fittings & Valves (ft)
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heaging valve of your gas.
Summary of Contents for BFIT 1000
Page 9: ...9 Figure 1 BFIT MODEL 1000 2000 ...
Page 12: ...12 IV BFIT Component Identification continued Figure 2 Component Identification ...
Page 13: ...13 IV BFIT Component Identification continued Figure 3 Component Identification ...
Page 52: ...52 Figure 24 Operating Instructions XII System Start up continued ...
Page 66: ...66 APPENDIX D INLET OUTLET WATER AND FLUE OUTLET TEMPERATURE SENSOR RESISTANCE VOLTAGE CHART ...
Page 68: ...68 ...