—5—

The BW9, unlike normal residential atmospheric and induced draft
boilers, takes its combustion air directly from the outdoors (sealed
combustion) and does not compete with building occupants for
fresh air. Sealed combustion (also known as “direct vent”) is the
safest and best way to obtain plenty of clean combustion air. The
induced draft fan draws in the outside combustion air, then takes the
cooler flue gases from the heat exchanger and provides a positive
removal of the flue gases from the building through inexpensive and
readily available PVC and CPVC pipes.

 

FEATURES

 

RANGE OF CAPACITIES

 

—Three sizes ranging from 50,000

through 100,000 Btuh input.

 

COMPLETELY PACKAGED

 

—Each boiler is completely

assembled, including all controls (except room thermostat). All
necessary wiring is factory installed. The boiler is ready for gas
piping, room thermostat, and electrical power connections as
shipped. Circulator is shipped pre-wired with 6 ft bx conduit for
easy installation for supply side pumping.

 

VENTING

 

—This boiler is direct vented with PVC and CPVC pipe.

See the Installation Instructions for common venting requirements.

 

ALUMINUM SECTIONS

 

—These sections speed heat transfer to

the boiler water. With faster thermal response, greater comfort and
economy are achieved.

 

PRE-MIX BURNER

 

—Provides quiet operation and improved

combustion efficiency.

 

CONTROLS

 

—Integrated Boiler Control provides safe,

dependable operation of burners. Factory-installed safety
components provide maximum safety against overheating,
pressure buildup, and low-water operation.

 

SECTIONS TESTED

 

—Each section is hydrostatically tested to

50 psig.  Individual sections are tested to 125 psig at factory.
Assembled sections are tested to 75 psig at the factory. The
maximum allowable pressure is 50 psig for hot water boilers.

 

PROPANE CONVERTIBLE

 

—With factory approved conversion

kit accessory.

 

WARRANTY

 

—The aluminum sections are covered by a limited

15-year warranty on the entire assembly. Circulator pump is
covered by a limited 3-year warranty. All other parts are covered
by a 1-year limited warranty.

 

 

SPECIFICATIONS

 

UNIT SIZE

050

075

100

 

Sections

1

 

GAS CONTROLS

 

Gas Valve

Honeywell

 

Inlet Size

In.

1/2

 

Ignition

Hot Surface Ignition

Burner—Stainless/Titanium Alloy

1

 

Burner Orifice

No.

0.0615

 

#48

#44

 

CONTROLS

 

Limit Control Range

°F

100-200

Pressure Relief Valve Setting

Psig

30

Integrated Boiler Control

UTEC factory installed

 

CIRCULATOR

 

Taco

Model

007

Full Load Amps

2.0 AMPS/330 WATTS

Flange Size FPT

In.

1-1/4

 

The BW9 is a gas fired direct vent condensing hot water
boiler with cast aluminum heat exchanger sections. A
revolutionary cast aluminum heat exchanger means better
heat transfer and thermal storage than similarly sized cast
iron boiler, which results in higher efficiency. The heating
system water absorbs large amounts of heat from the cast
aluminum heat exchanger, cooling the flue gases and
causing condensation. Sealed combustion, premix gas
burner, and low flame temperature means drastically
reduced CO and NOx emissions, which contribute to a
cleaner and healthier environment.

 

MODELS BW9

Summary of Contents for BS1

Page 1: ...Form No PDS BS1A 75 3 Gas and Oil Fired Water and Gas Fired Steam Boilers BS BW MODEL BW4B BW5B Series B MODEL BW1 BW2 Series B MODEL BW9 Series A MODEL BW3 Series B MODEL BS1 BS2 Series B ...

Page 2: ... KBAHL0101DNK Combustible Floor Base 2 thru 6 section models KBASB0301DNK Combustible Floor Base 6 thru 7 section models KBASB0401DNK Zoning Valve 3 4 in KBAZV0101DNK Zoning Valve 1 in KBAZV0201DNK Gas Conversion Kit Natural to Propane After 1799V KBANP0201DNK Gas Conversion Kit Propane to Natural KBAPN0201DNK NOTE There was never a Natural to Propane conversion kit for BW BS boiler prior to 1799V...

Page 3: ...to 1799V BW4 BW5 DESCRIPTION PART NO Filtrol Package Includes Air Purge Extrol Tank and Fill Valve KBAFP0201DNK KBAFP0301DNK Zone Valve 3 4 in KBAZV0101DNK Zone Valve 1 in KBAZV0201DNK High Limit Control Manual Reset KBAHL0101DNK Tankless Water Heater Kit KBATH0101IDNK Combustible Floor Base KBASB0301DNK Low Fire Rate Kit 3 Section BW4 BW5 KBALF0101DNK Low Fire Rate Kit 4 Section BW4 BW5 KBALF0201...

Page 4: ... Control Circuit Power Available 40va 24v MODEL BW1 BW2 BW3 BW4 BW5 BW9 BS1 BS2 Circulator Pump 3 3 3 3 3 3 Vent Damper 5 5 5 5 Heat Exchanger Section Assembly Non prorated 20 20 20 20 20 15 12 12 Oil Burner 3 3 WATER BOILER CIRCULATOR CURVE WATER FLOW M3 H WATER FLOW GPM TOTAL HEAD METERS TOTAL HEAD FEET 1 4 0 2 4 6 8 10 12 8 12 16 20 24 2 3 4 5 3 2 1 ama CERTIFIED ASME ...

Page 5: ...installed safety components provide maximum safety against overheating pressure buildup and low water operation SECTIONS TESTED Each section is hydrostatically tested to 50 psig Individual sections are tested to 125 psig at factory Assembled sections are tested to 75 psig at the factory The maximum allowable pressure is 50 psig for hot water boilers PROPANE CONVERTIBLE With factory approved conver...

Page 6: ...BUSTION AIR INTAKE FITTING 2 PVC 50 8mm STANDARD BOILER WATER SUPPLY RETURN OPENINGS 1 1 4 NPT 31 75mm CONNECTIONS PROVIDED INSIDE BOILER CABINET A99156 RATINGS AND CAPACITIES Gas input ratings are for elevations up to 2000 ft In the USA for elevations above 2000 ft reduce input per the charts supplied in the high altitude derate kits In Canada boilers may be used at high altitude by using a certi...

Page 7: ... The boiler is ready for gas water room thermostat and electrical connections as shipped THERMAL PIN CAST IRON SECTIONS These sections speed heat transfer from the flue gases to the boiler water with faster ther mostat response providing greater comfort and economy Max imum heat is produced at a lower level on the thermal pin sections leading to peak efficiency TITANIUM COMPOSITE BURNERS Provide q...

Page 8: ...00 184 000 767 80 9 800 BS2AAN075 Natural 3 75 000 62 000 47 000 196 82 7 256 BS2AAN112 Natural 4 112 500 91 000 68 000 283 80 4 404 BS2AAN150 Natural 5 150 000 122 000 92 000 383 80 6 483 BS2AAN187 Natural 6 187 500 153 000 115 000 479 80 9 564 BS2AAN225 Natural 7 225 000 183 000 137 000 575 81 1 649 BS2AAN262 Natural 8 262 500 214 000 161 000 671 81 3 719 BS2AAN299 Natural 9 299 000 245 000 184 ...

Page 9: ...ponents assure protection against overheating pressure buildup and low water operation INSULATED CASING The casing is fully insulated with fiberglass for maximum operating efficiency and economy AUTOMATIC VENT DAMPER The Model BS1 and BS2 is designed with automatic vent damper to recover chimney loss during off cycle SECTIONS TESTED Each section is hydrostatically tested to 50 psig Individual sect...

Page 10: ... 6 9 Section TOP 6 BACK 6 FRONT 6 RATINGS AND CAPACITIES Ratings are for altitudes to 2000 ft Unit ratings for altitudes over 2000 ft are 4 less for each 1000 ft above sea level BW1 BW2 GAS TYPE NUMBER OF SECTIONS MAX INPUT BTUH HEATING CAPACITY BTUH NET RATING BTUH AFUE APPROX SHIP WT Lb BW1 BW2 AAN037 Natural 2 37 500 30 000 26 000 80 0 81 4 227 AAN070 Natural 3 70 000 57 000 50 000 80 4 81 6 28...

Page 11: ...er room thermostat and electrical power connections as shipped VENTING This boiler can be vented into any approved chimney or Type B 1 vent Common venting with an existing water heater is acceptable in vertical vent systems See the Installation Instructions for common venting requirements The induced combustion design also eliminates the need for a vent damper THERMAL PIN CAST IRON SECTIONS These ...

Page 12: ...s are for elevations up to 2000 ft For elevations above 2000 ft reduce input 4 for each 1000 ft above sea level Selection factors providing for piping loss and starting load are those recommended by the Institute of Boiler and Radiator Manufacturers Net water boiler ratings are based on an allowance of 1 15 In accordance with U S Government test procedures UNIT GAS TYPE MAX INPUT BTUH RATINGS HEAT...

Page 13: ...talled drain is provided should the boiler ever need to be drained Oil primary control prevents boiler in operation in the event of flame loss SECTIONS TESTED Each section is hydrostatically tested to 50 psig Individual sections are tested to 125 psig at factory Assembled sections are tested to 75 psig at the factory The maximum allowable pressure is 50 psig for hot water boilers EASE OF INSTALLAT...

Page 14: ...he manufacturer has determined that this product meets Energy Star guidelines for Energy Efficiency BOILER MODEL NO NO SEC INPUT MBH HEAT ING CA PACITY MBH NET I B R RATING MBH FIRING RATE GPH A F U E MINIMUM CHIMNEY SIZE HEIGHT DIMENSIONS IN WITH TANKLESS COIL WITHOUT TANKLESS COIL A B C BW5BAH091 BW4BAH091 3 91 80 70 0 65 86 3 8 in x 8 in x 15 ft 14 1 2 6 8 BW5BAH105 BW4BAH105 3 105 92 80 0 75 8...

Page 15: ... 15 ...

Page 16: ...TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels PDS BSIA 75 2 2001 Bryant Heating Cooling Systems 7310 W Morris St Indpls IN 46231 PRINTED IN U S A Catalog No 12BS 1A1 3 01 ...

Reviews: