background image

9

FILTERING OUT TROUBLE

UNIT PERFORMANCE HAZARD

Failure to follow this caution may result in unit component

damage.
Never operate your furnace without a filter in place. Doing

so may damage the furnace blower motor.

An

accumulation of dust and lint on internal parts of your

furnace can cause a loss of efficiency.

CAUTION

!

A dirty filter will cause excessive stress on the furnace, heat

exchanger, and blower motor and can cause it to overheat and
automatically shut down. The furnace filter should be checked

every 4 weeks and cleaned or replaced if necessary.
If installed with factory--specified disposable media filter, check or
replace filter before each heating and cooling season. Replace

disposable media filter at least once a year.
If your furnace filter needs replacing, be sure to use the same size

and type of filter that was originally specified.
The air filter for the furnace may be located in the blower
compartment or in the factory--supplied filter cabinet attached to

the side or bottom of the furnace casing. If air filter has been
installed in another location, contact your dealer for instructions.

To inspect, clean and/or replace the air filter(s), follow these steps:

1. Turn off electrical supply to the furnace. See Fig. 20.
2. Remove air filter from furnace.

S

AIR FILTER(S) LOCATED IN BLOWER COMPARTMENT:

a. Remove main furnace door. See Fig. 21.

b. Remove blower access panel. See Fig. 22.

NOTE

: It will be necessary to remove two screws.

S

AIR FILTER(S) LOCATED IN BLOWER COMPARTMENT
BOTTOM:

c. Slide filter retainer sideways until it is free of latch (See

Fig. 25).

d. Slide air filter out of furnace. See Fig. 26.

S

AIR FILTER(S) LOCATED IN BLOWER COMPARTMENT
SIDE:

a. Remove filter retainer from latch. See Fig. 27.

b. Gently remove air filter and carefully turn the dirty side

up (if dirty) to avoid spilling dirt from the filter (See
Fig. 28).

S

AIR FILTER(S) LOCATED IN FILTER CABINET:

a. Remove filter cabinet door. (See Fig. 23 and 24.)

NOTE

: It will be necessary to remove one thumbscrew.
b. Slide air filter out of furnace. Keep dirty side up (if

dirty) to avoid spilling dirt. See Fig. 29 and 30.

3. Inspect the filter. If torn replace it.

NOTE

: If a washable filter was shipped with the furnace and has

been replaced by:

S

Factory specified disposable media filter----Do not clean.

If dirty, replace only with media filter having the same
part number and size. Install with airflow direction ar-

row pointing towards blower.

S

Electronic Air Cleaner (EAC), refer to the EAC Owner’s
Manual for maintenance information.

4. If washable filter, wash filter (if dirty) in a sink, bathtub, or

outside with a garden hose. Always use cold tap water. A

mild liquid detergent may be used if necessary. Spray water
through filter in the opposite direction of airflow. Allow fil-
ter to dry.

5. Reinstall clean air filter.
6. Reinstall filter retainer (for blower compartment locations

only.)

7. Replace blower access panel and main furnace door (See

Fig. 33 and 34) or filter cabinet door (Fig. 29 and 30).

8. Turn on electrical supply to the furnace.

If your furnace air filter needs to be replaced, be sure to use a

factory--authorized filter of the same size that was originally
specified. Use the filter tables and compare your furnace size with

the proper filter size.

A92185

Fig. 20 -- Turn Off Electrical Supply

A05087

Fig. 21 -- Main Furnace Door

A93204

Fig. 22 -- Blower Access Panel

Summary of Contents for Condencing Gas Furnace

Page 1: ...ified installer service agency or the gas supplier WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury and or death Carbon Monoxide is invisible odorless and toxic Install a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living area of your home and away from gas appliances and do...

Page 2: ...your new furnace is so efficient over 90 of the heat generated during combustion is captured and delivered inside your home That is more than a 30 increase in heating efficiency over conventional furnaces This furnace is among the safest most dependable energy efficient furnaces you can buy today We are proud of the technological advances incorporated into the design of this furnace With only mini...

Page 3: ...vary 9 Condensate drain connection collects moisture condensed from burned gases for disposal into home drain system location in furnace varies 10 Heavy duty blower circulates air across the heat ex changers to transfer heat into the home 11 Secondary condensing heat exchanger inside Wrings out more heat through condensation Constructed with polypro pylene laminated steel to ensure durability 12 P...

Page 4: ...nt 2 pipe Fig 1 application or as a non direct vent 1 pipe Fig 2 application S In a direct vent 2 pipe application your furnace uses air from outside the home for combustion and vents flue gas to the outdoors This type of application will have 2 pipes running from the furnace to the outdoors See Fig 1 In this application the vent and air intake pipes must terminate outside the structure and must n...

Page 5: ...e area in which the furnace is installed and the space around the furnace CAUTION BEFORE STARTING YOUR FURNACE Examine the furnace installation to determine that 1 All flue gas carrying areas external to the furnace i e chim ney vent connector are clear and free of obstructions 2 The vent connector is in place slopes upward and is physic ally sound without holes or excessive corrosion 3 The return...

Page 6: ...Fig 8 A92185 Fig 8 Turn Off Electrical Supply 4 Remove the main furnace door See Fig 9 A05087 Fig 9 Remove Furnace Door 5 Turn the control switch on the gas control to the OFF position and wait 5 minutes See Fig 10 Then smellfor gas including near the floor If you smell gas STOP Follow B on furnace label If you don t smell gas go to next step GAS CONTROL SWITCH SHOWN IN OFF POSITION TWO STAGE GAS ...

Page 7: ...ely cold days The few de grees at the top of your thermostat comfort level are the most costly degrees to obtain When the room temperature drops below the temperature selected on the thermostat the furnace will switch on automatically When the room temperature reaches the setting selected on the thermostat the furnace will be automatically switched off Continuous Fan Operation Some thermostats hav...

Page 8: ...e hazardous due to gas and electrical components Only trained and qualified personnel should install repair or service heating equipment Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel Observe safety precautions in this manual on tags and on labels attached to the furnace and ...

Page 9: ...See Fig 25 d Slide air filter out of furnace See Fig 26 S AIR FILTER S LOCATED IN BLOWER COMPARTMENT SIDE a Remove filter retainer from latch See Fig 27 b Gently remove air filter and carefully turn the dirty side up if dirty to avoid spilling dirt from the filter See Fig 28 S AIR FILTER S LOCATED IN FILTER CABINET a Remove filter cabinet door See Fig 23 and 24 NOTE It will be necessary to remove ...

Page 10: ...wer Cabinet A93010 Fig 25 Release Filter Retaining Rod Bottom Inlet A93011 Fig 26 Slide Filter Out Bottom Inlet A93012 Fig 27 Release Filter Retaining Rod Side Inlet A93013 Fig 28 Slide Filter Out of Furnace Side Inlet A00227 Fig 29 Removal of Filter from Side Blower Cabinet A00228 Fig 30 Removal of Filter from Bottom Blower Cabinet ...

Page 11: ... 21 533 1 16 x 25 x 3 4 406 x 635 x 19 1 20 x 25 x 3 4 508 x 635 x 19 3 4 19 mm thick washable 24 1 2 610 1 16 x 25 x 3 4 406 x 635 x 19 1 24 x 25 x 3 4 610 x 635 x 19 3 4 19 mm thick washable Table 2 Air Filter Located in Filter Cabinet FILTER CABINET HEIGHT IN MM FILTER SIZE IN MM FILTER TYPE 16 406 1 16 x 25 x 3 4 406 x 635 x 19 or 1 16 x 25 x 4 5 16 406 x 635 x 110 washable 20 508 1 20 x 25 x ...

Page 12: ...he combustion air intake adjacent to the furnace or outside your home for blockage Also check the vent pipe on the outside of your home for blockage NOTE If your furnace makes a loud noise when the main burners are ignited shut down the furnace and call your servicing dealer Use your flashlight and follow these steps for inspecting the combustion area and vent system of your furnace CARBON MONOXID...

Page 13: ...or equivalent UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glycol Prestone II antifreeze coolant or equivalent Failure of plastic components may occur CAUTION 2 Turn off electrical supply to your furnace 3 Remove main furnace door 4 Remove upper inducer housing drain connection cap See Fig 38 5 Connect...

Page 14: ...mostat for proper temperature Is thermostat set above room temperature S Is thermostat set to HEAT mode S Check fuses and circuit breakers Is the electrical power supply switch on S Is the manual shut off valve in the gas supply pipe leading to the furnace open NOTE Turn off electrical supply before continuing with checklist S Is control switch on gas valve in ON position Follow start up procedure...

Page 15: ...ial _____________________________________ INDOOR COIL Furnace Coil or Fan Coil Model _____________________________________ Serial _____________________________________ INSTALLATION INFORMATION Date Installed ________________________________ DEALERSHIP CONTACT INFORMATION Company Name_______________________________ Address______________________________________ ______________________________________...

Page 16: ...e or change at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 09 09 Replaces OM05 56 Catalog No OM05 58 ...

Reviews: