background image

7

FIRE, EXPLOSION, UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal

injury, death, or property damage.
Gas valve switch MUST be facing forward or tilted

slightly.

!

WARNING

19. Replace burner box cover.
20. Turn on gas and electrical supplies to furnace.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury, death or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically

for the detection of leaks to check all connections.

!

WARNING

21. Check for gas leaks.
22. Replace main furnace door.

Step 4 — Cleaning Heat Exchangers

The following items should be performed by a qualified service

technician.

Primary Heat Exchangers

If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:

NOTE

: If the heat exchangers get a heavy accumulation of soot

and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build--up of soot and carbon indicates
that a problem exists which needs to be corrected, such as improper
adjustment of manifold pressure, insufficient or poor quality
combustion air, improper vent termination, incorrect size or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.

1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in furnace

component damage.
Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and hazardous

operation.

CAUTION

!

3. Disconnect wires or connectors to flame rollout switch, gas

valve, igniter, and flame sensor.

4. Disconnect combustion--air intake pipe from intake hous-

ing.

5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and

rotate intake housing away from burner box for removal.

7. Using backup wrench, disconnect gas supply pipe from fur-

nace gas control valve.

8. Disconnect pressure tubing from gas valve.

9. Remove two screws attaching top filler panel and rotate up-

wards to gain access to screws attaching burner box to cell

panel.

10. Remove screws attaching burner box to cell panel. (See Fig.

6.)

NOTE

: Burner box, cover, manifold, gas valve, and burner

assembly should be removed as one assembly.

11. Clean heat exchanger openings with a vacuum and a soft

brush. (See Fig. 8.)

NOTE

: After cleaning, inspect the heat exchangers to ensure they

are free of all foreign objects that may restrict flow of combustion
products.

PRIMARY HX

INLET OPENINGS

A96305

Fig. 8 -- Cleaning Inlet Openings of Primary

Heat Exchangers

UNIT MAY NOT OPERATE

Failure to follow this caution may result in improper or

intermittent unit operation.
The ground wire from the gas valve MUST be attached to

the burner box attachment screw.

CAUTION

!

12. Reverse items 3 through 10 for reassembly.

NOTE

: Be sure burner box gasket is installed between burner box

and cell panel. (See Fig. 6.) If gasket is damaged, replace it.

NOTE

: Inspect combustion--air intake housing. If foamed gasket

was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn nor canola oil, halogenated
hydrocarbons nor aromatic content, to prevent inadequate seal
from occurring) to burner box and apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to edge
of combustion--air intake housing. (See Fig. 9.)

340AA

V

Summary of Contents for Deluxe 340AAV

Page 1: ...potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or produ...

Page 2: ... operation CAUTION GENERAL This furnace can be installed as a direct vent 2 pipe or non direct vent 1 pipe condensing gas furnace These instructions are written as if the furnace is installed in an upflow application An upflow furnace application is where the blower is located below the combustion and controls section of the furnace and conditioned air is discharged upward Since this furnace can b...

Page 3: ...the label attached to the furnace WARNING The minimum maintenance that should be performed on this equipment is as follows 1 Check and clean or replace air filter each month as needed 2 Check blower motor and wheel for cleanliness annually 3 Check electrical connections for tightness and controls for proper operation each heating season Service as necessary 4 Check for proper condensate drainage C...

Page 4: ...nfiguration Shown with Blower Access Panel Removed 1 Turn off electrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disp...

Page 5: ... CAUTION g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 9 Reassemble motor and blower wheel by reversing items 8b through 8f Ensure wheel is positioned for proper rotation Be sure to reattach ground wire Tighten setscrew to 140 to 160 in lb torque NOTE Be sure to attach ground wire to blower housing 10 Reinstall blower assembly in furnace 11 Reinstall control box...

Page 6: ...move screws attaching burner assembly in burner box NOTE Use care when removing and reinstalling burners not to strike the hot surface igniter IGNITER WIRES MUST BE PLACED IN THIS SLOT A05074 Fig 7 Igniter Wire Placement 12 Remove burner assembly from burner box NOTE All burners are attached to burner bracket and can be removed as one assembly 13 Clean burners with soft brush and vacuum 14 Reinsta...

Page 7: ...sconnect wires or connectors to flame rollout switch gas valve igniter and flame sensor 4 Disconnect combustion air intake pipe from intake hous ing 5 Remove the pressure switch tube from intake housing 6 Remove screws attaching intake housing to burner box and rotate intake housing away from burner box for removal 7 Using backup wrench disconnect gas supply pipe from fur nace gas control valve 8 ...

Page 8: ...n made specifically for the detection of leaks to check all connections WARNING 18 Replace main furnace door Secondary Heat Exchangers NOTE The condensing side inside of the secondary heat exchangers CANNOT be serviced or inspected A small number of bottom outlet openings can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removin...

Page 9: ...onnection as shown 3 HORIZONTAL LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap Refer to the Installation Instructions for further details NOTE 324999 201 REV C FIELD INSTALLED FACTORY SUPPLIED DRAINTUBE COUPLING RIGHT DRAIN OPTION BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY BURNER ENCLOSURE PRESSUR...

Page 10: ...triking the igniter on surrounding parts Note that the igniter bracket has a handle that extends to the front of the burner box to aid in handling See Fig 13 d Inspect igniter for signs of damage or failure UNIT DAMAGE HAZARD Failure to follow this caution may result in premature failure of the igniter The igniter is fragile DO NOT allow it to hit burner box parts while removing or replacing it CA...

Page 11: ...se to blow If fuse replacement is required use ONLY a fuse of identical size The furnace control LED will flash status code 24 when fuse needs to be replaced With power to the unit disconnected check all electrical connections for tightness Tighten all screws on electrical connections If any smoky or burned connections are found disassemble the connection clean all parts strip wire and reassemble ...

Page 12: ... same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A02174 Fig 15 Field Wiring BLW NUETRAL STATUS CODE LED SEC 2 SEC 1 EAC 2 L2 FUSE 3 AMP 0 5 AMP 24VAC HUM TEST TWIN G Com W Y R 24V 120 180 90 150 BLOWER OFF DELAY PLT 1 COOL HEAT SPARE 1 SPARE 2 EAC 1 1 AMP 115VAC PR 1 L1 PL2 1 24 V THERMOSTAT TERMINALS 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 115 VAC L2 NEUTRAL CONNECTIONS COOL HEA...

Page 13: ...omotive type CAUTION 6 Replace drain connection cap and clamp to inducer housing 7 Replace main furnace door 8 Propylene glycol need not be removed before restarting fur nace WIRING DIAGRAMS See Fig 21 for wiring diagram A07911 Fig 17 Freeze Protection TROUBLESHOOTING Use the troubleshooting guide the status code LED on the furnace control and the component test to isolate furnace operation proble...

Page 14: ... COM 24v terminals are jumpered longer than 2 sec LED will flash rapidly and ignore component test request A99119 Fig 19 Funnel in Drain Tube and Antifreeze Running Through Trap Component test sequence for single stage furnace is as follows a LED will display status code 11 four times b Inducer motor starts and continues to run until Step f of component test sequence c After 7 sec the hot surface ...

Page 15: ...T CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low inducer voltage 115VAC Defective pressure switch Inadequate combustion air supply Restricted vent Disconnected or obstructed pressure tubing Low inlet gas pressure if LGPS used If it opens during blower on delay period blower wil...

Page 16: ...AFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES RED LGPS LOW GAS PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 11 CIRCUIT PCB CONNECTOR P...

Page 17: ...est sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to W...

Page 18: ... switch open Restricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected...

Page 19: ...heory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Package...

Page 20: ...hange at any time specifications or designs without notice and without incurring obligations E2008 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 12 08 Replaces SP05 72 Catalog No SM340AAV 01 340AAV ...

Reviews: