background image

3

A07617

Fig. 5 -- Exhaust Ventilation

FLEXIBLE
DUCT

FRESH-AIR
SUPPLY

STALE-AIR
RETURN

DUCTS CONNECTING TO

RETURN-AIR DUCT SYSTEM

A07610

Fig. 6 -- Flexible Duct Fit--Up

Connect Ducts to ERV

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in minor property

damage from sweating duct or loss of unit efficiency and

capacity.
ERV should be installed in a conditioned space with insulated

flex duct for supply and exhaust air to the outdoor ambient.

CAUTION

!

Insulated flexible duct is required on both fresh--air inlet and

exhaust--air outlet ducts connecting to exterior wall.

When

using insulated flexible duct, the vapor barrier of the flexible ducts

must be taped very tightly to prevent condensation problems. To
reduce pressure drop, stretch the flex duct and support it in a proper

manner to avoid reduced airflow.
When connecting the ERV to a return--air duct system, insulated
flexible duct can be used. When using metal duct from fresh--air

supply to system duct work, the metal duct should be insulated (see
Fig. 6). However, when metal or rigid ducts are applied use

approximately 18” (457 mm) of flexible duct at ERV ports for

fresh--air supply and stale--air return. This can act as a silencer
when connecting ducts to return--air duct system. This should

eliminate transmission of noise or vibration from unit to main duct
system. In addition, there are four 30” (762 mm) duct ties provided

to help fasten flexible duct to port on ERV.

Locate and Install Exterior Hoods

IMPORTANT

: To prevent condensation problems, insulated

flexible ducts are required on both fresh--air inlet and exhaust--air
outlet ducts connecting between ERV and exterior wall.
Fresh--air intake and stale--air exhaust must be separated by at least
6 ft (1.8 m). Fresh--air intake must be positioned at least 10 ft (3 m)

from nearest dryer vent, furnace exhaust, driveway, gas meter, or
oil fill pipe. Fresh--air intake must be positioned as far as possible

from garbage containers and potential chemical fumes. When

possible, it is advised to locate the intake and exhaust hoods on
same side of house or building. The intake and exhaust hoods

should never be located on interior corners or in dead air pockets
(see Fig. 5). Both intake and exhaust hoods must be 18” (457 mm)

from ground and at least 12” (305 mm) above anticipated snow

level.
After selecting proper hood locations, make appropriate size hole

through exterior wall, pass flexible duct through hole and insert
hood tube into duct. Tape duct vapor barrier tightly around hood

tube and insert assembly back into wall and fasten securely.

WALL CONTROL

Location

The ERV wall control is unique to this unit. The ERV will not
operate without it. This control senses humidity not temperature. It

must be located in an area where it will continually monitor fresh
air circulating within the home. Install ERV wall control as close as

possible to main system thermostat and follow same guidelines as

installing a thermostat (locate approximately 5 ft (1.5 m) above
floor, mount on an inside partitioning wall, etc.).

Wiring

Remove top cover assembly from wall control and pass thermostat
wire through hole located on back of control before attaching to

wall. Connect Y, R, G, and B (yellow, red, green, and black)

between wall control and ERV connector following color code (see
Fig. 7 and 8). Replace top cover assembly.

NOTE

: ERV wall control and circuit board operate on 12 VDC.

 YELLOW

Y

R

GB

 RED

 GREEN

 BLACK

A00112

Fig. 7 -- Typical Wall Control

ER

V

Summary of Contents for ERVBBLHA Series

Page 1: ...CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result...

Page 2: ... air pickup registers throughout the home Fresh air registers are normally located in bedrooms dining rooms living rooms and basements It is recommended that registers be placed 6 to 12 152 to 305 mm from the ceiling on an interior wall and airflow directed toward the ceiling If registers are floor installed airflow should be directed toward the wall A92269 Fig 4 Chain Spring Installation CARBON M...

Page 3: ...g between ERV and exterior wall Fresh air intake and stale air exhaust must be separated by at least 6 ft 1 8 m Fresh air intake must be positioned at least 10 ft 3 m from nearest dryer vent furnace exhaust driveway gas meter or oil fill pipe Fresh air intake must be positioned as far as possible from garbage containers and potential chemical fumes When possible it is advised to locate the intake ...

Page 4: ...35 45 4 F 20 C 30 45 22 F 30 C 25 35 NOTE The ERV may be controlled using the Evolution system control The ERV may be connected using either a NIM or a 4 Zone Damper Module See the appropriate instructions if using the NIM of a 4 Zone Damper Module for connection instructions OneTouch Control The OneTouch control may be used as the primary wall control for the ERV This control will step through th...

Page 5: ...d optimum performance when applying an ERV Unit balancing prevents a positive and or negative pressure within the home Balancing the ERV is done by using balancing dampers in the fresh air intake and stale air exhaust ducts Airflow is determined by temporarily connecting a magnehelic gauge to the pressure taps on ERV See Fig 10 Balancing chart is located on unit door A98400 Fig 10 Magnehelic Gauge...

Page 6: ...h configuration setup shown in Fig 12 under Jumper Table Jumpers are factory set and do not require any changes unless control board is replaced If control board is replaced or unusual start up operation is encountered check jumpers to make sure they are located properly NOTE Power disconnect for 30 seconds is required to reset the CPU when changing jumpers Outdoor Ambient Below 23_ F 5_ C The ERV...

Page 7: ...n outdoor temperature is between 60 F and 75 F 16 C and 24 C and it is dry UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation DO NOT use water to clean core or damage will result In addition before servicing or removing the core inspect the edges to see if they appear soft or slightly expanded This can be normal and due to moisture in t...

Page 8: ...ory connected to electronic control board on HIGH and LOW speed taps of blowers Installer can easily change low speed tap to medium speed tap so electronic control will select between high and medium speed Connections can be changed at motor location see Table 9 and 10 To change low speed to medium speed proceed as follows 1 Unplug unit from 115 VAC 2 Remove filters and core from ERV 3 Slide blowe...

Page 9: ...l may be defective S Remove the wall control and test it right beside the unit using another shorter wire If the wall control works there change the wire If it does not change the wall control S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The wires may be broken S Inspect every wire and replace any that are damaged S Th...

Page 10: ...er Le non respect de ces instructions peut causer un décès ou un choc électrique ADVERTENCIA PELIGRO DE CHOQUE ELÉCTRICO Desconecte el suministro de energía antes de reparar de mantener o de cablear in situ Vuelva a colocar todos los paneles antes de hacer lo funcionar No seguir estas instrucciones puede causar la muerte o choque eléctrico NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 IF...

Page 11: ... 11 860 72 22 11 270 74 23 10 750 76 24 10 250 78 26 9 750 80 27 9 300 82 28 8 840 84 29 8 432 86 30 8 042 88 31 7 668 90 32 7 310 92 33 6 993 94 34 6 661 96 36 6 368 98 37 6 085 100 38 5 811 102 39 5 571 104 40 5 313 106 41 5 088 108 42 4 869 110 43 4 660 112 44 4 450 114 46 4 268 116 47 4 019 118 48 3 918 120 49 3 750 Table 9 Factory Set Blower Connection HIGH or LOW Speed Control Module Main El...

Page 12: ... change at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Replaces IIERVLHA 01 Catalog No IIERVLHA 02 ERV ...

Reviews: