background image

5

DEHUM -- will only turn on if humidity is 3% over setpoint.
The speed is determined by indoor humidity and outdoor

temperature.

Cooling:

AUTO -- the ventilator selects the speed based on indoor
humidity and outdoor temperature. It may cycle on/off every

30 minutes depending on humidity and outside temperature.
LOW -- low speed all of the time.
HIGH -- high speed all of the time.

If the fan speed is set to Auto and the ventilator wants to run, the
fan speed will run at High continuous speed. Otherwise, the fan

will stay at the chosen continuous fan speed.

ELECTRICAL CONNECTIONS

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than 1 disconnect

switch.

!

WARNING

115 VAC Wiring

The ERV operates on 115 VAC. It comes with a power cord

attached to unit and ready to plug into a fused outlet. Unit must be
grounded for proper operation.
All electrical connections must comply with National and Local
Electrical Codes, or other ordinances that might apply.

12 VDC Wiring

The ERV circuit board, wall control, and accessories operate on 12

VDC. See Wall Control section, item Wiring and Fig. 7 and 8 for
more information.
The ERV comes with an integrated interlock. The interlock can be

wired to the system blower to ensure that the blower is running
when there is a call for ventilation. See the wiring diagram for

proper wiring of the interlock circuit.

ACCESSORIES

20 Minute Timer

A push button timer can be used to override the wall control and

put the ERV into high speed for 20 minutes. Connect switches in

parallel and connect leads to ERV terminals I, OC, and OL (see
Fig. 9). Push button locations are ideal in special activity areas,

such as bathrooms or kitchens, where high--speed exhaust
operation is needed for a short period of time.

NOTE

: The 20 minute timer will not function properly unless

ERV wall control is applied and working correctly. Timing
function is internal to electronic circuit board, it is activated by a
momentary contact between OC and OL. The I connection is to
illuminate the push button. The maximum number of push button
timers that can be applied is 5.

60 Minute Adjustable Timer

A 60 minute adjustable timer can also be used to override wall

control and put ERV into high--speed operation for a select amount
of time. Connect timer in parallel with push button timers, or to

ERV terminals OC and OL (see Fig. 9).

BALANCING ERV

Balancing intake and exhaust airflow is very important for proper

system operation and optimum performance when applying an

ERV. Unit balancing prevents a positive and/or negative pressure

within the home. Balancing the ERV is done by using balancing
dampers in the fresh air intake and stale air exhaust ducts.
Airflow is determined by temporarily connecting a magnehelic
gauge to the pressure taps on ERV. (See Fig. 10.) Balancing chart is

located on unit door.

A98400

Fig. 10 -- Magnehelic Gauge

If supply--air from outside is greater than exhaust--air from the

house, an imbalance can result over pressurizing the home. If
exhaust--air is greater than supply--air, combustion appliances may

backdraft, bringing exhaust fumes into the house. A balanced
condition will ensure optimum performance, provide satisfied

customers, and avoid expensive callbacks.
Before proceeding with balancing, all windows, doors, and
fireplace flues should be tightly closed. No exhaust systems such as

range top exhausts, dryer exhaust, fume hoods, bath or roof fans
should be in operation. The forced--air furnace (if used for

circulation) should be operating in continuous fan mode for normal
operating speed.

Balancing Procedure
Step 1 — Set the unit to high speed.

Make sure that the furnace/air handler blower is ON if the

installation is in any way connected to the ductwork of the cold air

return. If not, leave furnace/air handler blower OFF. If the outside
temperature is below 32

_

F (0

_

C), make sure the unit is not running

in defrost while balancing. (By waiting 10 minutes after plugging
the unit in, you are assured that the unit is not in a defrost cycle.)

Step 2 — Magnehelic gauge placement.

Place the magnehelic gauge on a level surface and adjust it to zero.

Step 3 — Connect tubing from gauge to EXHAUST air

flow pressure taps.

Be sure to connect the tubes to their appropriate high/low fittings.

(See Fig. 11.) If the gauge drops below zero, reverse the tubing
connections.

NOTE

: It is suggested to start with the exhaust air flow reading

because the exhaust has typically more restriction than the fresh air,

especially in cases of fully ducted installations or source point

ventilation. Place the magnehelic gauge upright and level. Record
equivalent AIR FLOW of the reading according to the balancing

chart.

Step 4 — Move tubing to FRESH air flow pressure

taps.

Adjust the fresh air balancing damper until the fresh air flow is
approximately the same as the EXHAUST air flow. If fresh air

flow is less than exhaust air flow, then go back and adjust the

exhaust balancing damper to equal the fresh air flow. (See Fig. 11.)

Step 5 — Secure both dampers thumb screw in place

with tape.
Step 6 — Record air flow information.

Write the required air flow information on a label and stick it near
the unit for future reference (date, maximum speed air flows, your

name, phone number and business address).

ER

V

Summary of Contents for ERVBBLHA Series

Page 1: ...CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result...

Page 2: ... air pickup registers throughout the home Fresh air registers are normally located in bedrooms dining rooms living rooms and basements It is recommended that registers be placed 6 to 12 152 to 305 mm from the ceiling on an interior wall and airflow directed toward the ceiling If registers are floor installed airflow should be directed toward the wall A92269 Fig 4 Chain Spring Installation CARBON M...

Page 3: ...g between ERV and exterior wall Fresh air intake and stale air exhaust must be separated by at least 6 ft 1 8 m Fresh air intake must be positioned at least 10 ft 3 m from nearest dryer vent furnace exhaust driveway gas meter or oil fill pipe Fresh air intake must be positioned as far as possible from garbage containers and potential chemical fumes When possible it is advised to locate the intake ...

Page 4: ...35 45 4 F 20 C 30 45 22 F 30 C 25 35 NOTE The ERV may be controlled using the Evolution system control The ERV may be connected using either a NIM or a 4 Zone Damper Module See the appropriate instructions if using the NIM of a 4 Zone Damper Module for connection instructions OneTouch Control The OneTouch control may be used as the primary wall control for the ERV This control will step through th...

Page 5: ...d optimum performance when applying an ERV Unit balancing prevents a positive and or negative pressure within the home Balancing the ERV is done by using balancing dampers in the fresh air intake and stale air exhaust ducts Airflow is determined by temporarily connecting a magnehelic gauge to the pressure taps on ERV See Fig 10 Balancing chart is located on unit door A98400 Fig 10 Magnehelic Gauge...

Page 6: ...h configuration setup shown in Fig 12 under Jumper Table Jumpers are factory set and do not require any changes unless control board is replaced If control board is replaced or unusual start up operation is encountered check jumpers to make sure they are located properly NOTE Power disconnect for 30 seconds is required to reset the CPU when changing jumpers Outdoor Ambient Below 23_ F 5_ C The ERV...

Page 7: ...n outdoor temperature is between 60 F and 75 F 16 C and 24 C and it is dry UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation DO NOT use water to clean core or damage will result In addition before servicing or removing the core inspect the edges to see if they appear soft or slightly expanded This can be normal and due to moisture in t...

Page 8: ...ory connected to electronic control board on HIGH and LOW speed taps of blowers Installer can easily change low speed tap to medium speed tap so electronic control will select between high and medium speed Connections can be changed at motor location see Table 9 and 10 To change low speed to medium speed proceed as follows 1 Unplug unit from 115 VAC 2 Remove filters and core from ERV 3 Slide blowe...

Page 9: ...l may be defective S Remove the wall control and test it right beside the unit using another shorter wire If the wall control works there change the wire If it does not change the wall control S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The wires may be broken S Inspect every wire and replace any that are damaged S Th...

Page 10: ...er Le non respect de ces instructions peut causer un décès ou un choc électrique ADVERTENCIA PELIGRO DE CHOQUE ELÉCTRICO Desconecte el suministro de energía antes de reparar de mantener o de cablear in situ Vuelva a colocar todos los paneles antes de hacer lo funcionar No seguir estas instrucciones puede causar la muerte o choque eléctrico NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 IF...

Page 11: ... 11 860 72 22 11 270 74 23 10 750 76 24 10 250 78 26 9 750 80 27 9 300 82 28 8 840 84 29 8 432 86 30 8 042 88 31 7 668 90 32 7 310 92 33 6 993 94 34 6 661 96 36 6 368 98 37 6 085 100 38 5 811 102 39 5 571 104 40 5 313 106 41 5 088 108 42 4 869 110 43 4 660 112 44 4 450 114 46 4 268 116 47 4 019 118 48 3 918 120 49 3 750 Table 9 Factory Set Blower Connection HIGH or LOW Speed Control Module Main El...

Page 12: ... change at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Replaces IIERVLHA 01 Catalog No IIERVLHA 02 ERV ...

Reviews: