background image

6

NOTE

:

The unit is considered balanced even if there is a

difference of

±

10 CFM (or

±

5 l/s or 17 m

3

/h) between the two air

flows.

Balancing Dampers

Balancing dampers (sometimes called butterfly dampers) are
located in fresh--air intake and stale--air exhaust of the ERV. (See

Fig. 11.) Some field modification may be required to ensure proper
adjustment of balancing dampers while located in flexible duct.

Insulating over these dampers is strongly recommended after

balancing is complete to prevent condensation problems.

NOTE

: Temporary flow collars are not needed with the new

ERVBBHA models since the air flow pressure taps are
incorporated in the access door. (See Fig. 11.)

VENTILATION EVALUATION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit

efficiency, capacity or unit life.
DO NOT use ERV during construction of a house or when

sanding drywall. This type of dust may damage system.

CAUTION

!

Ventilator Sizing

Tables 3 and 4 should be used to determine the required airflow for

a home. These guidelines are taken from ANSI/ASHRAE
62.2--2007.

Table 3 – Ventilation Air Requirements, cfm

FLOOR

AREA (ft

2

)

BEDROOMS

0---1

2---3

4---5

6---7

>7

<1500

30

45

60

75

90

1501---3000

45

60

75

90

105

3001---4500

60

75

90

105

120

4501---6000

75

90

105

120

135

6001---7500

90

105

120

135

150

>7500

105

120

135

150

165

Table 4 – Ventilation Air Requirements, L/s

FLOOR

AREA (m

2

)

BEDROOMS

0---1

2---3

4---5

6---7

>7

<139

14

21

28

35

42

139.1---279

21

28

35

42

50

279.1---418

28

35

42

50

57

418.1---557

35

42

50

57

64

557.1---697

42

50

57

64

71

>697

50

57

64

71

78

Fresh air flow

Exhaust Air Flow

A05264

Fig. 11 -- Balancing ERVBBHA

CONTROL BOARD OPERATION

Board Function

To ensure proper operation of ERV, configuration jumpers are
located on electronic control board and must match configuration

setup shown in Fig. 12 under Jumper Table. Jumpers are factory set
and do not require any changes unless control board is replaced. If

control board is replaced, or unusual start--up operation is
encountered, check jumpers to make sure they are located properly.

NOTE

: Power disconnect for 30 seconds is required to reset the

CPU when changing jumpers.

Outdoor Ambient Below 23

_

F (--5

_

C)

The ERV continually monitors outside air temperature. If outside

air is at or below 23

_

F (--5

_

C), ERV will cycle between air

exchange and defrost.
The ERV measure the incoming air temperature and will cycle unit
in and out of defrost, depending on outdoor ambient. The intake

damper will close and circulate indoor air through the core for 6 to
10 minutes. This time depends on jumper location. Refer to Table 5

for defrost cycle.

Table 5 – Defrost Cycle

ERV DEFROST CYCLES

Outside

Temp

°

F /

°

C

Standard

Defrost (as shipped)

Extended Defrost

(Jumper JU1---F

Removed)

Above 23

°

F /

---5

°

C

No Defrost

No Defrost

23 to 5

°

F /

---5 to ---15

°

C

10 Minute Defrost/60

Minute Exchange

10 Minute Defrost/30

Minute Exchange

4 to ---17

°

F /

---16 to ---27

°

C

10 Minute Defrost/30

Minute Exchange

10 Minute Defrost/20

Minute Exchange

Below ---18

°

F /

---28

°

C

10 Minute Defrost/20

Minute Exchange

10 Minute Defrost/15

Minute Exchange

OFF and INTERMITTENT/OFF Mode

When ERV is Off, K1 relay is open (see Fig. 12).

High--Speed Air Exchange

When high--speed air exchange occurs, K1 relay closes and K2 (12

VDC relay) is energized. This opens low--speed contacts, and
closes high--speed contacts. Then, 115 VAC is applied between

orange and gray wires on Molex

R

plug (pins 1 and 6) and blower

motor runs in high--speed operation. Also, 115 VAC is applied

across pins 5 and 7, this energizes interlock relay (see Fig. 12).

Low--Speed Air Exchange

When low--speed air exchange occurs, K1 relay closes and K2 (12
VDC relay) is de--energized. This keeps low--speed contacts closed

and high--speed contacts open. Then, 115 VAC is applied between

ER

V

Summary of Contents for ERVBBLHA Series

Page 1: ...CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result...

Page 2: ... air pickup registers throughout the home Fresh air registers are normally located in bedrooms dining rooms living rooms and basements It is recommended that registers be placed 6 to 12 152 to 305 mm from the ceiling on an interior wall and airflow directed toward the ceiling If registers are floor installed airflow should be directed toward the wall A92269 Fig 4 Chain Spring Installation CARBON M...

Page 3: ...g between ERV and exterior wall Fresh air intake and stale air exhaust must be separated by at least 6 ft 1 8 m Fresh air intake must be positioned at least 10 ft 3 m from nearest dryer vent furnace exhaust driveway gas meter or oil fill pipe Fresh air intake must be positioned as far as possible from garbage containers and potential chemical fumes When possible it is advised to locate the intake ...

Page 4: ...35 45 4 F 20 C 30 45 22 F 30 C 25 35 NOTE The ERV may be controlled using the Evolution system control The ERV may be connected using either a NIM or a 4 Zone Damper Module See the appropriate instructions if using the NIM of a 4 Zone Damper Module for connection instructions OneTouch Control The OneTouch control may be used as the primary wall control for the ERV This control will step through th...

Page 5: ...d optimum performance when applying an ERV Unit balancing prevents a positive and or negative pressure within the home Balancing the ERV is done by using balancing dampers in the fresh air intake and stale air exhaust ducts Airflow is determined by temporarily connecting a magnehelic gauge to the pressure taps on ERV See Fig 10 Balancing chart is located on unit door A98400 Fig 10 Magnehelic Gauge...

Page 6: ...h configuration setup shown in Fig 12 under Jumper Table Jumpers are factory set and do not require any changes unless control board is replaced If control board is replaced or unusual start up operation is encountered check jumpers to make sure they are located properly NOTE Power disconnect for 30 seconds is required to reset the CPU when changing jumpers Outdoor Ambient Below 23_ F 5_ C The ERV...

Page 7: ...n outdoor temperature is between 60 F and 75 F 16 C and 24 C and it is dry UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation DO NOT use water to clean core or damage will result In addition before servicing or removing the core inspect the edges to see if they appear soft or slightly expanded This can be normal and due to moisture in t...

Page 8: ...ory connected to electronic control board on HIGH and LOW speed taps of blowers Installer can easily change low speed tap to medium speed tap so electronic control will select between high and medium speed Connections can be changed at motor location see Table 9 and 10 To change low speed to medium speed proceed as follows 1 Unplug unit from 115 VAC 2 Remove filters and core from ERV 3 Slide blowe...

Page 9: ...l may be defective S Remove the wall control and test it right beside the unit using another shorter wire If the wall control works there change the wire If it does not change the wall control S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The wires may be broken S Inspect every wire and replace any that are damaged S Th...

Page 10: ...er Le non respect de ces instructions peut causer un décès ou un choc électrique ADVERTENCIA PELIGRO DE CHOQUE ELÉCTRICO Desconecte el suministro de energía antes de reparar de mantener o de cablear in situ Vuelva a colocar todos los paneles antes de hacer lo funcionar No seguir estas instrucciones puede causar la muerte o choque eléctrico NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 IF...

Page 11: ... 11 860 72 22 11 270 74 23 10 750 76 24 10 250 78 26 9 750 80 27 9 300 82 28 8 840 84 29 8 432 86 30 8 042 88 31 7 668 90 32 7 310 92 33 6 993 94 34 6 661 96 36 6 368 98 37 6 085 100 38 5 811 102 39 5 571 104 40 5 313 106 41 5 088 108 42 4 869 110 43 4 660 112 44 4 450 114 46 4 268 116 47 4 019 118 48 3 918 120 49 3 750 Table 9 Factory Set Blower Connection HIGH or LOW Speed Control Module Main El...

Page 12: ... change at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Replaces IIERVLHA 01 Catalog No IIERVLHA 02 ERV ...

Reviews: