ELECTRICAL DATA

MODEL

UNIT

SIZE---

SERIES

V---PH---Hz

OPER

VOLTS*

COMPR

FAN

MCA

MIN

WIRE

SIZE

{

MIN

WIRE

SIZE

{

MAX

LENGTH

ft (m)

}

MAX

LENGTH

ft (m)

}

MAX

FUSE*

* or

CKT

BRK

AMPS

MAX

MIN

LRA

RLA

FLA

60

°

C

75

°

C

60

°

C

75

°

C

187BNA

024---A

208/230---1---60

253

197

52.0

10.30

0.7

13.6

14.00

14.00

60 (18.3)

57 (17.4)

20

036---A

208/230---1---60

82.0

16.70

1.2

22.1

14.00

14.00

45 (13.7)

44 (13.4)

35

048---A

208/230---1---60

96.0

21.20

1.3

27.8

12.00

12.00

51 (15.5)

49 (14.9)

40

060---A

208/230---1---60

118.0

23.00

1.3

30.1

8.00

10.00

93 (28.3)

57 (17.4)

50

180BNA

036---A

208/230---1---60

253

197

82.0

16.70

2.4

23.3

14.00

14.00

45 (13.7)

44 (13.4)

35

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{

If wire is applied at ambient greater than 30

_

C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade

name ROMEX, shall be that of 60

_

C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75

_

C insulation, copper

wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}

Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.

** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA

--- Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE

: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.

All motors/compressors contain internal overload protection.

Complies with 2007 requirements of ASHRAE Standards 90.1

A--WEIGHTED SOUND POWER (dBA)

UNIT SIZE

STANDARD

RATING (dBA)

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

187BNA024

*71---low stage

53.0

62.0

64.5

66.5

63.0

60.5

52.5

72---high stage

54.0

61.5

66.5

66.5

63.5

60.5

55.5

187BNA036

*72---low stage

54.0

61.5

66.5

68.0

63.5

60.5

53.5

72---high stage

54.5

61.5

67.5

68.0

62.0

59.5

54.5

187BNA048

*72---low stage

54.5

63.0

67.0

67.0

64.5

61.0

56.5

73---high stage

55.0

63.0

68.0

67.5

63.5

62.0

57.5

187BNA060

*73---low stage

56.5

62.0

67.5

69.5

64.5

60.0

53.5

73---high stage

55.0

62.0

67.0

68.5

64.5

60.0

53.5

180BNA036

*72---low stage

55.5

58.5

64.0

67.0

64.5

59.5

53.5

72---high stage

56.5

60.0

66.0

66.0

60.0

56.5

53.0

NOTE

: Tested in accordance with AHRI Standard 270---08. (Not listed with AHRI).

CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)

UNIT SIZE --- SERIES

REQUIRED SUBCOOLING

_

F (

_

C)

187BNA024---A

10 (5.6)

187BNA036---A

10 (5.6)

187BNA048---A

10 (5.6)

187BNA060---A

10 (5.6)

180BNA036---A

10 (5.6)

187B

/180B

Summary of Contents for EVOLUTION 180B

Page 1: ...tory org for the most up to date ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 20 SEER 11 6 14 5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessor...

Page 2: ...may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual produ...

Page 3: ...Maximum Total Equivalent Length Outdoor unit ABOVE Indoor Vertical Separation ft m 25 7 6 26 50 7 9 15 2 51 75 15 5 22 9 76 100 23 2 30 5 101 125 30 8 38 1 126 150 38 4 45 7 151 175 46 0 53 3 176 200...

Page 4: ...t Line Length ft m 26 50 7 9 15 2 51 80 15 5 24 4 81 100 24 7 30 5 101 125 30 8 38 1 126 150 38 4 45 7 151 175 46 0 50 3 176 200 53 6 60 0 201 225 61 3 68 6 226 250 68 9 76 2 024 2 Stage Puron AC 3 8...

Page 5: ...rvice panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and require...

Page 6: ...1 Evolution Remote Room Sensor Monitors temperature in an individual zone SYSTXBBSAM01 Evolution System Access Module Hardware for wireless access and control via phone or internet SYSTXBBNIM01 Evolut...

Page 7: ...s 3 Evaporator Freeze Thermostat An SPST temperature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required when low ambient kit has been added...

Page 8: ...A X O 0 0 31 3 16 38 15 16 3 7 8 7 8 6 9 16 24 11 16 9 1 8 2 15 16 5 8 14 1 4 17 1 4 19 1 2 224 263 32 15 16 X 35 1 2 X 46 1 8 187B048 A X O 0 0 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 1...

Page 9: ...231 3 70 9 12 8 362 0 438 2 495 3 100 7 118 4 187B036 A X O 0 0 792 5 988 3 97 9 22 2 166 1 626 3 231 3 74 5 16 3 362 0 438 2 495 3 101 6 119 3 187B048 A X O 0 0 889 0 1022 9 97 9 22 2 166 1 722 8 23...

Page 10: ...SHIPPING WEIGHT lbs SHIPPING DIMENSIONS L x W x H 180B036 A X O 0 0 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 16 16 1 2 17 1 4 306 372 36 1 8 X 39 1 4 X 46 1 8 X YES O NO A B C 3 1 2 1 7 8...

Page 11: ...TERISTICS A B C D E F G K L M N P OPERATING WEIGHT Kgs SHIPPING 180B036 A X O 0 0 889 0 1022 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 406 4 419 1 438 2 139 169 X YES O NO SQ FIELD CONTROL SUPPLY CONN 2...

Page 12: ...ce 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm IMPORTANT When installing multiple units in an alcove roof well or partia...

Page 13: ...25 000 21 000 13 0 16 0 820 640 3747184 187BNA024 A CAP 3619A TDR 24 000 20 000 11 8 14 0 700 560 3747105 187BNA024 A CAP 3621A TDR 24 400 20 200 11 9 14 0 700 560 3747109 187BNA024 A CAP 3621A UI 31...

Page 14: ...09 187BNA024 A CNPV 3617A 374RAN036105 24 600 20 200 13 0 16 0 660 520 3747124 187BNA024 A CNPV 3617A TDR 24 400 20 000 11 9 14 0 700 560 3747126 187BNA024 A CNPV 3617A UI 315 A J AV048090 24 800 20 4...

Page 15: ...085 955 3747363 187BNA036 A CAP 3621A 368RAN036105 36 000 29 400 12 5 16 0 1065 880 3747365 187BNA036 A CAP 3621A 368RAN060120 36 400 30 000 12 5 16 5 1170 1005 3747362 187BNA036 A CAP 3621A 374RAN036...

Page 16: ...55 A C AV042080 35 600 29 000 12 4 16 0 1030 825 3747279 187BNA036 A CNPH 3617A UI 355 A C AV060080 35 600 28 800 12 5 16 0 1010 810 3747280 187BNA036 A CNPH 3617A UI 355 A C AV060100 35 800 29 000 12...

Page 17: ...87BNA036 A CNPV 4221A UI 355 A C AV060100 36 200 29 200 12 8 16 5 1040 810 3747495 187BNA036 A CNPV 4221A UI 355BAV042080 36 200 29 400 12 6 16 0 1030 840 3747496 187BNA036 A CNPV 4221A UI 355BAV06008...

Page 18: ...5 A J AV066135 37 000 29 800 13 2 17 0 1010 810 3747347 187BNA036 A CSPH 4812A UI 315 A J AV066155 37 200 30 200 13 3 17 0 1015 810 3747339 187BNA036 A CSPH 4812A UI 355 A C AV042080 37 000 29 800 12...

Page 19: ...0 870 3748030 180BNA036 A CNPH 4821A 313 AV048070 37 600 31 200 13 9 19 0 1080 960 3748031 180BNA036 A CNPH 4821A 313 AV048090 37 800 31 400 13 8 19 0 1090 985 3748032 180BNA036 A CNPH 4821A 353 A B A...

Page 20: ...950 3748011 180BNA036 A CNPV 4221A 353 A B AV036060 36 800 30 600 13 5 18 5 1080 920 3748012 180BNA036 A CNPV 4221A 353 A B AV036080 37 000 30 800 13 5 18 5 1055 980 3748013 180BNA036 A CNPV 4221A 353...

Page 21: ...180BNA036 A CSPH 3612A 353 A B AV036080 37 400 31 200 13 7 18 5 1055 980 3748039 180BNA036 A CSPH 3612A 353 A B AV048080 37 400 31 000 13 4 18 0 1080 925 3748055 180BNA036 A CSPH 3612A 359BAV036060 3...

Page 22: ...0 39 000 12 2 15 5 1350 1170 3747847 187BNA048 A CAP 4821A 374RAN060120 47 000 39 000 12 1 15 5 1355 1155 3747715 187BNA048 A CAP 4821A TDR 48 000 38 500 12 0 14 5 1600 1120 3747716 187BNA048 A CAP 48...

Page 23: ...7BNA048 A CNPH 6024A UI 355 A C AV060100 48 500 39 500 12 6 16 0 1395 1115 3747771 187BNA048 A CNPH 6024A UI 355 A C AV060120 48 000 39 500 12 8 16 5 1360 1090 3747808 187BNA048 A CNPH 6124A 313 AV048...

Page 24: ...90 3747756 187BNA048 A CNPV 6124A UI 355 A C AV060100 50 500 41 500 13 4 17 0 1395 1115 3747757 187BNA048 A CNPV 6124A UI 355 A C AV060120 50 500 41 500 13 6 17 5 1360 1090 3747872 187BNA048 A CNPV 61...

Page 25: ...44 187BNA060 A CAP 6025A TDR 57 000 46 000 11 8 14 5 1750 1400 3747418 187BNA060 A CNPH 6024A 313 AV060110 58 500 47 000 13 0 16 5 1700 1275 3747419 187BNA060 A CNPH 6024A 313 AV060135 58 500 47 000 1...

Page 26: ...353 A B AV060100 58 500 47 000 13 1 16 5 1650 1270 3747457 187BNA060 A CSPH 6012A 353 A B AV060120 59 000 47 000 13 2 16 5 1660 1290 3747466 187BNA060 A CSPH 6012A 374RAN060120 58 500 47 500 12 4 16...

Page 27: ...44 2 54 72 22 2 31 08 16 19 1 63 29 73 15 52 1 78 28 31 14 84 1 95 26 81 14 16 2 13 25 21 13 46 2 34 23 49 12 75 2 56 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105...

Page 28: ...9 353 A B AV036060 CSPH 2412A 1 00 1 00 0 98 0 98 353 A B AV036060 CSPH 3012A 1 01 0 99 1 00 0 98 353 A B AV036060 CSPH 3612A 1 03 0 99 1 03 0 99 353 A B AV036060 CAP 2417A 1 00 0 99 1 01 1 00 353AAV0...

Page 29: ...1 3 71 72 22 2 45 89 24 52 2 43 43 73 23 47 2 65 41 48 22 42 2 89 39 13 21 36 3 15 36 66 20 29 3 44 34 06 19 21 3 76 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40...

Page 30: ...0 CSPH 4212A 1 03 1 03 0 99 0 97 353 A B AV036060 CSPH 4812A 1 04 1 03 1 00 0 97 353 A B AV036060 CAP 3617A 1 00 1 02 0 99 1 01 353 A B AV036080 CAP 4817A 1 03 1 03 1 01 1 00 353 A B AV036080 CNPH 361...

Page 31: ...21A 1 03 1 04 1 00 1 00 368RAN036105 CAP 3621A 1 01 1 05 1 00 1 01 368RAN060120 CAP 4221A 1 02 1 04 1 01 1 01 368RAN060120 CNPV 4221A 1 02 1 05 1 01 1 02 368RAN060120 CNPV 4821A 1 04 1 04 1 02 1 01 36...

Page 32: ...8 3 47 72 22 2 47 09 25 93 2 24 44 62 24 35 2 45 42 10 22 81 2 69 39 51 21 30 2 94 36 84 19 81 3 22 34 08 18 35 3 52 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40...

Page 33: ...60 CSPH 3612A 0 98 1 04 1 00 1 08 353 A B AV036060 CSPH 4212A 0 99 1 04 1 01 1 08 353 A B AV036060 CSPH 4812A 0 99 1 04 1 01 1 08 353 A B AV036060 CNPH 3617A 0 96 1 04 0 98 1 11 353 A B AV036080 CNPH...

Page 34: ...359BAV060100 CSPH 4812A 0 94 1 05 0 95 1 08 359BAV060100 CNPV 3621A 0 96 1 05 0 96 1 07 368RAN036105 CNPV 4221A 0 96 1 05 0 90 1 02 368RAN036105 CNPV 4821A 0 98 1 05 0 90 1 01 368RAN036105 CNPV 4221A...

Page 35: ...3 4 97 72 22 2 61 38 31 16 3 34 58 85 30 03 3 62 56 08 28 84 3 92 53 02 27 59 4 26 49 66 26 28 4 62 45 93 24 89 5 02 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40...

Page 36: ...B AV048080 CNPH 6024A 0 97 1 02 0 96 0 94 353 A B AV048080 CNPH 6124A 1 01 1 01 0 99 0 96 353 A B AV048080 CNPV 4821A 0 95 1 01 0 96 0 93 353 A B AV048080 CSPH 4812A 0 96 1 02 0 96 0 95 353 A B AV048...

Page 37: ...6 09 72 22 2 72 57 37 29 3 98 69 61 36 36 4 34 66 35 35 32 4 74 62 79 34 19 5 17 58 84 32 94 5 65 54 49 31 56 6 17 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40...

Page 38: ...AP 6024A 0 99 0 98 1 00 1 00 353 A B AV060120 CNPH 6024A 0 99 0 99 1 00 1 00 353 A B AV060120 CNPH 6124A 0 99 0 98 1 00 1 00 353 A B AV060120 CNPV 6024A 0 99 0 98 1 00 1 00 353 A B AV060120 CNPV 6124A...

Page 39: ...56 TCG 27 70 26 30 24 80 23 30 21 80 20 20 18 50 16 80 SDT 67 60 77 00 86 40 95 80 105 20 114 60 124 00 133 40 KW 0 75 0 88 1 01 1 16 1 34 1 54 1 78 2 06 187BNA036 HI 30 1 11 TCG 32 00 30 20 28 40 26...

Page 40: ...35 60 15 56 TCG 41 20 38 60 36 00 33 50 31 00 28 50 26 00 23 60 SDT 70 10 79 40 88 60 97 90 107 10 116 40 125 60 134 80 KW 0 89 1 04 1 20 1 37 1 55 1 77 2 02 2 31 187BNA048 HI 30 1 11 TCG 40 30 38 40...

Page 41: ...133 40 141 90 KW 2 74 3 06 3 40 3 78 4 19 4 64 5 14 5 70 187BNA060 A LO 30 1 11 TCG 34 80 33 30 31 50 29 60 27 50 25 30 23 00 20 60 SDT 64 40 74 00 83 60 93 10 102 70 112 20 121 60 131 10 KW 1 65 1 96...

Page 42: ...SPLIT SYSTEM AIR CONDITIONER 187B 180B 2 TO 5 NOMINAL TONS Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corros...

Page 43: ...ter than 80 ft 23 4 m and or 35 ft 10 7 m vertical differential consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor 6 If any refrigerant tubing is...

Page 44: ...ge at any time specifications or designs without notice and without incurring obligations EBryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 03 10 Rep...

Reviews: