background image

10

The outdoor fan output (ODF) will remain off for 20 seconds after
termination. This delay will allow time for the system to capture

the heat from the outdoor coil and reduce the “steam cloud” effect
that may occur on transition from defrost to the heating cycle. The

outdoor fan output OFF delay of 20 seconds may be defeated to

enable the fan to energize immediately at the time of termination
and 12 seconds prior to the reversing valve de--energizing, through

the User Interface setup screen available with SYSTXBBUID01--C
UI, or forced defrost pins as follows:

S

The ODF fan delay defeat can be toggled by shorting the
forced defrost pins for >15 seconds while in the standby
mode (status LED on solid). The LED will start to flash when
the toggle has taken place.

S

Status code 4 shows the fan delay defeat is active (no delay)

S

Status code 3 shows that it is not active (20 second delay)

The code will continue to be displayed until after the short is

removed. Once the short is removed, there is a 5 second wait
before the code is cancelled. The code that is flashing will finish

before going back to sold LED. the control is shipped with the
ODF fan delay defeat NOT active.

the change in status is

remembered until toggled to a new status. A power down / power

up sequence will not reset the status. It may be necessary to do the
toggle twice to cycle to the desired state of defeat.

Defrost Hold

In a non--communicating system, if the thermostat becomes

satisfied (Y1 or Y1 and Y2) before the defrost cycle is terminated,
the control will “hold” in defrost mode and finish the defrost cycle

on the next call for heat.
On 286A and 288A models, with communicating Evolution

Control, defrost hold is not needed in a communicating system
because the User Interface will complete the defrost cycle before

shutting down the system.

Forced Defrost

With non--communicating (non--Evolution) control, forced defrost
can be initiated by manually shorting the 2--pin header labeled

FORCED DEFROST (see Fig 6) on the control board for 5

seconds then releasing.
On 286A and 288A with communicating (Evolution) control,

forced defrost is initiated with the User Interface.
On all models, during a Forced Defrost:

S

If coil temperature is at defrost temperature of 32

_

F (0

_

C),

and outdoor air temperature is below 50

_

F (10

_

C), a full

defrost sequence will occur.

S

If coil temperature or outdoor air temperature does not meet

the above requirements, an abbreviated 30 second defrost will

occur.

Quiet Shift

Quiet Shift is a field--selectable defrost mode which may eliminate

occasional noise that could be heard at the start of the defrost cycle
and restarting of the heating cycle. With a non--communicating

system, this feature must be enabled by selecting the 3rd position
of the 3--position dip switch. For 286A and 288A models with

communicating (Evolution) systems, it must be enabled at the User

Interface. When activated, the following sequence of operation
will occur. Reversing valve will energize and compressor will turn

off for 30 seconds, then turn back on to complete defrost. At the
end of the defrost cycle, the reversing valve de--energizes,

compressor will turn off for another 30 seconds, and the fan will

turn off for 40 seconds, before starting in the heating mode.

Liquid--Line Solenoid Accessory

In heat pump long--line applications, a liquid--line solenoid is

required to control refrigerant migration in the heating mode. The
solenoid should be installed near the outdoor unit with the arrow

facing the outdoor unit. This is the direction of flow control. See

application manual for long--line application details.

Accessory Liquid Solenoid with Evolution Communicating

Control:

When using the Evolution Control, the liquid--line

solenoid output is provided at the Y1 connection. Connect the
solenoid as shown in the wiring label diagram. This is a 24vac

output that is energized whenever the compressor is energized. It

closes, in the compressor off mode, to prevent refrigerant migration
into the unit through the liquid--line.

On Models with Accessory Liquid Solenoid Using a

Non--Communicating Thermostat:

The liquid solenoid is

connect to the Y1 and C terminal connections. The liquid solenoid

closes, in the compressor off mode, to prevent refrigerant migration
into the unit through the liquid--line.

Check Charge

All 286A units must be charged in high stage only.

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be
favorable for subcooling charging. Favorable conditions exist

when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft of 3/8 liquid line above or below
15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to
drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor
and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

Heating Check Chart Procedure

To check system operation during heating cycle, refer to the Heat

Pump Charging Instructions label on outdoor unit. This chart
indicates whether a correct relationship exists between system

operating pressure and air temperature entering indoor and outdoor
units. If pressure and temperature do not match on chart, system

refrigerant charge may not be correct. Do not use chart to adjust

refrigerant charge.

NOTE

: In heating mode, check refrigerant charge only when

pressures are stable. If in doubt, remove charge and weigh in
correct refrigerant charge.

NOTE

: When charging is necessary during heating season, charge

must be weighed in accordance with unit rating plate,

±

0.6 oz./ft.

of 3/8--in. liquid--line above or below 15 ft., respectively.

EXAMPLE

:

To calculate additional charge required for a 25--ft. line set:
25 ft. -- 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge.

286A

/288A

Summary of Contents for Evolutiont 286A

Page 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Page 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Page 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Page 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Page 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Page 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Page 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Page 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Page 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Page 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Page 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Page 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Page 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Page 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Page 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Page 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Reviews: