background image

16

When the gas supply being used has a different heating value or
specific gravity, refer to national and local codes, or contact your

distributor to determine the required orifice size.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit

and/or component life.

Do Not

redrill an orifice. Improper drilling (burrs,

out--of--round holes, etc.) can cause excessive burner noise

and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check

orifice hole with a numbered drill bit of correct size.

!

CAUTION

Adjust Gas Input

The gas input to the unit is determined by measuring the gas flow
at the meter or by measuring the manifold pressure. Measuring the

gas flow at the meter is recommended for natural gas units. The

manifold pressure must be measured to determine the input of
propane gas units.

Measure Gas Flow (Natural Gas Units)

Minor adjustment to the gas flow can be made by changing the

manifold pressure. The manifold pressure must be maintained
between 3.2 and 3.8 IN. W.C.

REGULATOR 
COVER SCREW

ADJUSTMENT
SCREW

REGULATOR SPRING
(PROPANE - WHITE)

NATURAL - SILVER)

GAS PRESSURE 
REGULATOR 
ADJUSTMENT

MANIFOLD 
PRESSURE TAP

INLET 
PRESSURE TAP

ON/OFF SWITCH

PLASTIC

(

A07751

Fig. 12 -- Single--Stage Gas Valve

If larger adjustments are required, change main burner orifices

following the recommendations of national and local codes.

NOTE

:

All other appliances that use the same meter must be

turned off when gas flow is measured at the meter.
Proceed as follows:

1. Turn off gas supply to unit.

2. Remove pipe plug on manifold (See Fig. 10) and connect

manometer. Turn on gas supply to unit.

3. Record number of seconds for gas meter test dial to make

one revolution.

4. Divide number of seconds in Step 3 into 3600 (number of

seconds in one hr).

5. Multiply result of Step 4 by the number of cubic feet (cu ft)

shown for one revolution of test dial to obtain cubic feet (cu

ft) of gas flow per hour.

6. Multiply result of Step 5 by Btu heating value of gas to

obtain total measured input in Btuh. Compare this value
with heating input shown in Table 3 (Consult the local gas

supplier if the heating value of gas is not known).

EXAMPLE: Assume that the size of test dial is 1 cu ft, one

revolution takes 32 sec, and the heating value of the gas is 1050

Btu/ft

3

. Proceed as follows:

1. 32 sec. to complete one revolution.
2. 3600

32 = 112.5.

3. 112.5 x 1 =112.5 ft

3

of gas flow/hr.

4. 112.5 x 1050 = 118,125 Btuh input.

If the desired gas input is 115,000 Btuh, only a minor change in the

manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas

input:

1. Remove regulator cover screw over plastic adjustment

screw on gas valve (See Fig. 12).

2. Turn plastic adjustment screw clockwise to increase gas

input, or turn plastic adjustment screw counterclockwise to

decrease input (See Fig. 12). Manifold pressure must be
between 3.2 and 3.8 IN. W.C.

FIRE AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure

is outside this range.

!

WARNING

3. Replace regulator cover screw on gas valve (See Fig. 12).
4. Turn off gas supply to unit. Remove manometer from

pressure tap and replace pipe plug on gas valve. (See Fig.

10.) Turn on gas to unit and check for leaks.

Measure Manifold Pressure (Propane Units)

Refer to propane kit installation instructions for properly checking
gas input.

NOTE

: For installations below 2,000 ft (610 m), refer to the unit

rating plate for proper propane conversion kit. For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.

Check Burner Flame

With control access panel (see Fig. 19) removed, observe the unit

heating operation. Watch the burner flames to see if they are light
blue and soft in appearance, and that the flames are approximately

the same for each burner. Propane will have blue flame (See Fig.

12). Refer to the Maintenance section for information on burner
removal.

Normal Operation

An LED (light--emitting diode) indicator is provided on the

integrated gas unit controller (IGC) to monitor operation. The IGC
is located by removing the control access panel (see Fig. 19).

During normal operation, the LED is continuously on (See Table 5
for error codes).

Airflow and Temperature Rise

The heating section for each size unit is designed and approved for

heating operation within the temperature--rise range stamped on the
unit rating plate.
Table 8 and 9 show the approved temperature rise range for each
heating input, and the air delivery cfm at various temperature rises

for a given external static pressure. The heating operation airflow

must produce a temperature rise that falls within the approved
range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust
heating airflow when required.

Limit Switches

Normally closed limit switch (LS) completes the control circuit.

Should the leaving--air temperature rise above the maximum
allowable temperature, the limit switch opens and the control

circuit “breaks.” Any interruption in the control circuit instantly

closes the gas valve and stops gas flow to the burners. The blower
motor continues to run until LS resets.

677C

--

--

C

Summary of Contents for Legacy 677C**C Series

Page 1: ...lower and Motor 49 Flue Gas Passageways 50 Limit Switch 50 Burner Ignition 50 Main Burners 50 Outdoor Coil Indoor Coil Condensate Drain Pan 50 A09034 Fig 1 Unit 677C C Outdoor Fan 51 Electrical Contro...

Page 2: ...ment IDENTIFY UNIT The unit model number and serial number are stamped on the unit information plate Check this information against shipping papers INSPECT SHIPMENT Inspect for shipping damage before...

Page 3: ...3 A150538 Fig 2 24 30 Unit Dimensions 677C C...

Page 4: ...4 A150539 Fig 3 36 60 Unit Dimensions 677C C...

Page 5: ...S 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of duct r...

Page 6: ...oof deck to comply with applicable fire codes Read unit rating plate for any required clearances around ductwork Cabinet return air static shall not exceed 25 IN W C Step 4 Provide Clearances The requ...

Page 7: ...pan from overflowing See Fig 6 Prime the trap with water When using a gravel apron make sure it slopes away from the unit If the installation requires draining the condensate water away from the unit...

Page 8: ...ll ground joint union close to heating section between unit manual shutoff and external manual main shut off valve 7 Pressure test all gas piping in accordance with local and national plumbing and gas...

Page 9: ...or local codes and ordinances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for horizontal duct installation by removing duct covers 2 Sele...

Page 10: ...4 x 254 1 2 800 10 x 10 254 x 254 1 2 1000 10 x 10 254 x 254 1 2 1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 1 2 1200 11 x 10 279 x 254 1 2 Furnace Section Burner Orifice 1 Phase Natural Gas Qty...

Page 11: ...24x15x1 610x406x25 1 each 24x16x1 610x406x25 24x18x1 610x457x25 Based on altitude of 0 to 2000 ft 0 610 m Required filter sizes shown are based on the larger of the AHRI Air Conditioning Heating and...

Page 12: ...unit gas combustion supply air louvers See unit wiring label Fig 15 and 16 and Fig 9 for reference when making high voltage connections Proceed as follows to complete the high voltage connections to t...

Page 13: ...his point the indoor supply air feels uncomfortable i e too cool This is purely subjective and will depend on the homeowner s idea of comfort Below this temperature the gas furnace should operate in o...

Page 14: ...point thermostat closes circuits R to G R to Y and R to O The unit delivers cooling airflow c HEAT PUMP HEATING MODE Outdoor temperature above balance point setpoint of thermostat 1 On a call for heat...

Page 15: ...ol break the 24 v power to W 5 The evaporator fan will turn on 45 sec after the flame has been established The evaporator fan will turn off 45 sec after the thermostat has been satisfied Please note t...

Page 16: ...e in the manifold pressure is required Observe manifold pressure and proceed as follows to adjust gas input 1 Remove regulator cover screw over plastic adjustment screw on gas valve See Fig 12 2 Turn...

Page 17: ...on When turning backwards the difference between compressor suction and discharge pressures will be near zero Checking and Adjusting Refrigerant Charge The refrigerant system is fully charged with Pur...

Page 18: ...e current speed tap wire from the GAS HEAT terminal on the interface fan board IFB Fig 14 and place vinyl cap over the connector on the wire 3 Connect the desired speed tap wire to the GAS HEAT termin...

Page 19: ...ed Low Speed Blue Low Speed DH DH DH DH DH DH DH DH Shunt in no dehumidification position Shunt in dehumidification position A14399 Fig 13 Single Phase IGC Board COM LOW HIGH GAS HEAT Q1 R1L C8 RL3 Q3...

Page 20: ...28 NA NA High Black CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 Heat Rise o F 25 26 28 30 32 33 35 38 43 49 Heat Rise o C 14 15 16 17 18 18 20...

Page 21: ...6 28 NA NA High Black CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 Heat Rise o F 25 26 28 30 32 33 35 38 43 49 Heat Rise o C 14 15 16 17 18 18 2...

Page 22: ...30 High Black CFM 1602 1535 1469 1404 1333 1260 1246 1192 1191 1131 BHP 0 46 0 47 0 48 0 50 0 50 0 51 0 52 0 53 0 54 0 55 Heat Rise o F 28 29 31 32 34 36 36 38 38 40 Heat Rise o C 16 16 17 18 19 20 2...

Page 23: ...24 High Black CFM 1575 1528 1488 1447 1406 1360 1314 1264 1213 1159 BHP 0 40 0 42 0 43 0 44 0 45 0 46 0 47 0 48 0 49 0 50 Heat Rise o F 28 29 30 31 32 33 34 35 37 39 Heat Rise o C 16 16 17 17 18 18 1...

Page 24: ...25 High Black CFM 2267 2201 2133 2071 1997 1923 1835 1739 1654 1551 BHP 1 03 1 00 0 97 0 93 0 89 0 86 0 82 0 78 0 74 0 69 Heat Rise o F NA NA NA NA NA 35 37 39 41 44 Heat Rise o C NA NA NA NA NA 20 2...

Page 25: ...36 High Black CFM 2267 2201 2133 2071 1997 1923 1835 1739 1654 1551 BHP 1 03 1 00 0 97 0 93 0 89 0 86 0 82 0 78 0 74 0 69 Heat Rise o F 42 44 45 46 48 50 52 55 58 62 Heat Rise o C 24 24 25 26 27 28 2...

Page 26: ...41 0 42 0 43 0 45 0 45 Heat Rise o F 59 60 NA NA NA NA NA NA NA NA Heat Rise o C 33 33 NA NA NA NA NA NA NA NA Medium 2 Red CFM 1736 1710 1668 1630 1600 1557 1522 1479 1450 1406 BHP 0 53 0 54 0 55 0...

Page 27: ...62 0 63 0 64 0 65 Heat Rise o F 55 56 57 59 60 62 63 65 NA NA Heat Rise o C 31 31 32 33 33 34 35 36 NA NA Med High 1 Orange CFM 1935 1909 1867 1836 1808 1766 1696 1619 1535 1454 BHP 0 71 0 73 0 74 0...

Page 28: ...48 52 Heating Rise o C 18 19 20 21 22 23 25 27 29 High Black CFM 1536 1470 1405 1333 1263 1204 1239 1181 1122 Heating Rise o F 28 29 31 33 34 36 35 37 39 Heating Rise o C 16 16 17 18 19 20 19 20 21 36...

Page 29: ...44 47 50 Heating Rise o C 18 19 19 20 22 23 24 26 28 High Black CFM 1472 1401 1326 1251 1275 1198 1139 1085 1023 Heating Rise o F 29 31 33 35 34 36 38 40 42 Heating Rise o C 16 17 18 19 19 20 21 22 2...

Page 30: ...35 36 37 Heating Rise o C NA NA NA NA NA NA 20 20 21 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F NA NA NA NA NA NA NA 35 37 Heating Rise o C NA NA NA NA NA NA NA 20 2...

Page 31: ...50 51 53 Heating Rise o C 25 25 26 26 27 27 28 28 29 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F 41 41 42 43 44 46 48 50 53 Heating Rise o C 23 23 23 24 25 26 27 28 2...

Page 32: ...o F 19 36 o C Low Blue CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1678 1635 1602 1558 151...

Page 33: ...NA NA NA NA NA NA NA Heating Rise o C 24 27 29 NA NA NA NA NA NA NA Medium 2 Red CFM 1222 1236 1195 1148 1101 1052 1004 957 916 868 WATTS 233 221 232 244 251 264 275 285 291 304 BHP 0 25 0 24 0 25 0...

Page 34: ...NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA NA Medium 2 Red CFM 1222 1236 1195 1148 1101 1052 1004 957 916 868 WATTS 256 270 283 289 301 313 320 331 343 349 BHP 0 27 0 29 0 30 0 3...

Page 35: ...F 43 46 49 53 NA NA NA NA NA NA Heating Rise o C 24 26 27 29 NA NA NA NA NA NA Medium Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0...

Page 36: ...NA NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA NA Medium 1 Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0...

Page 37: ...o F 43 44 46 47 48 50 51 53 55 57 Heating Rise o C 24 25 25 26 27 28 29 30 30 32 Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0...

Page 38: ...F 55 56 58 59 NA NA NA NA NA NA Heating Rise o C 30 31 32 33 NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 4...

Page 39: ...F 61 63 65 NA NA NA NA NA NA NA Heating Rise o C 34 35 36 NA NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 4...

Page 40: ...e o F 36 37 38 39 40 41 41 42 44 45 Heating Rise o C 20 21 21 22 22 23 23 24 24 25 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP...

Page 41: ...o F 46 47 48 49 50 52 53 54 56 58 Heating Rise o C 26 26 27 27 28 29 29 30 31 32 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP 0...

Page 42: ...57 0 58 0 59 0 61 0 62 0 64 0 65 Heating Rise o F 49 50 51 52 53 54 55 56 58 59 Heating Rise o C 27 28 28 29 29 30 31 31 32 33 Med High 1 Orange CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751...

Page 43: ...00 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 24 0 03 0 04 0 04 0 05 0 06 30 0 05 0 06 0 07 0 08 0 11 36 0 06 0 06 0 09 0 10 0 11 0 14 42 0 05 0 05 0 06 0 07 0 08 0 08 0 09 0 09 0 11 48 0...

Page 44: ...44 A150506 Fig 15 208 230 1 60 Connection Wiring Diagram 677C C...

Page 45: ...45 A150516 Fig 15 Cont 208 230 1 60 Ladder Wiring Diagram 677C C...

Page 46: ...46 A150507 Fig 16 208 230 3 60 Connection Wiring Diagram 677C C...

Page 47: ...47 A150517 Fig 16 Cont 208 230 3 60 Ladder Wiring Diagram 677C C...

Page 48: ...under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcooling charging Favorable conditions e...

Page 49: ...pect heating section before each heating season Clean and adjust when necessary 6 Check flue hood and remove any obstructions if necessary Air Filter IMPORTANT Never operate the unit without a suitabl...

Page 50: ...tation If lockout occurs unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at the thermostat Main Burners At the beginning of each...

Page 51: ...hen the electrical power to the unit Remove access panels see Fig 19 to locate all the electrical controls and wiring Check all electrical connections for tightness Tighten all screw connections If an...

Page 52: ...the liquid line and protects against low suction pressures caused by such events as loss of charge low airflow across indoor coil dirty filters etc It opens on a pressure drop at about 20 psig If syst...

Page 53: ...TOR THERMOSTAT INPUTS T1 ENABLES DEFROST TIMER MUST BE ENERGIZED FOR DEFROST TIMER TO START C COMMON O REVERSING VALVE SPEEDUP DEFROST THERMOSTAT MUST BE CLOSED BEFORE DEFROST TIMER BEGINS A150622 Fig...

Page 54: ...NDOOR COIL LCS LEGEND HPS High Pressure Switch LCS Loss of Charge Switch Accurater Metering Device Arrow indicates direction of flow TXV in Metering Position Bypass Position HPS C03011 Fig 26 Typical...

Page 55: ...ing to occur in one year or more When performing any service that may risk exposure of compressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage incl...

Page 56: ...old sets should be minimum 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detec...

Page 57: ...restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrig...

Page 58: ...ise is in accordance with the range on the unit nameplate Clean or replace filters Flame sense fault LED 3 flashes The IGC sensed flame that should not be present Reset unit If problem persists replac...

Page 59: ...N IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR C...

Page 60: ...ntinue or change at any time specifications or designs without notice and without incurring obligations E2015 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 12...

Reviews: