Table 1 – Physical Data-Unit
UNIT SIZE
24
30
36
42
48
60
NOMINAL CAPACITY (ton)
2
2-1/2
3
3-1/2
4
5
SHIPPING WEIGHT lb.
SHIPPING WEIGHT (kg)
307
139
316
143
354
161
388
176
437
198
481
218
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R-410A)
Quantity lb
Quantity (kg)
6.4
2.9
6.0
2.7
5.75
2.6
6.0
2.7
9.0
4.1
10.0
4.5
REFRIGERANT METERING DEVICE
Orifice
ORIFICE ID in./mm
.059 / 1.5
.063 / 1.60
.070 / 1.78
.073 / 1.85
.080 / 2.03
.084 / 2.14
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
1...21
11.9
1...21
13.6
1...21
13.6
1...21
13.6
1...21
23.3
1...21
23.3
OUTDOOR FAN
Nominal Cfm
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
2500
24
609.6
1/12 (810)
3200
24
609.6
1/5 (810)
3500
26
660.4
1/5 (810)
3500
26
660.4
1/5 (810)
3500
26
660.4
1/5 (810)
3500
26
660.4
1/5 (810)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
3.7
3...17
3.7
2...17
5.6
3...17
4.7
3...17
5.6
3...17
5.6
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size in.
Size (mm.)
Motor HP (RPM)
750
10x10
254x254
1/2 (1050)
950
10x10
254x254
1/2 (1050)
1150
11x10
279.4x254
1/2(1000)
1350
11x10
279.4x254
3/4 (1075)
1600
11x10
279.4x254
1.0 (1075)
1750
11x10
279.4x254
1.0 (1040)
HIGH-PRESSURE SWITCH
(psig) Cut-out Reset (Auto)
650 +/- 15
420 +/- 25
LOSS-OF-CHARGE / LOW-PRESSURE
SWITCH (psig) cut-out Reset (auto)
N/A
RETURN-AIR FILTERS
*
†
Throwaway Size in.
Throwaway Size (mm)
*. Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 to 350
ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. W.C.
†. If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
2 each 20x12x1
(508x305x25)
1 each 24x18x1
(610x457x25)
24x16x1
(610x406x25)
1 each 24x14 x1
(610x356x25)
24x16x1
(610x406x25)
1 each 24x18x1
(610x457x25)
24x16x1
(610x406x25)
Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)
SIZE
24
30
36
42
48
60
Cfm
800
1000
1200
1400
1600
1750