background image

 

 12

 

 

 

CAUTION 

Low flue gas temperatures increase the risk of 
condensation. Adjust the total temperature at or higher 
then 204°C (400°F) in order for the heat exchanger 
warranty to remain in force. 

3.3.3 Combustion 

Check 

 

IMPORTANT

 

The heat exchanger metal surfaces may have oil and the 
baffle insulation also contains binders. These products will 
burn or evaporate when the unit operates for the first time. 
Because of that, the smoke reading may be skewed during the 
first minutes of operation. Therefore, the unit must operate 
during at least 60 minutes before taking any readings to adjust 
the combustion quality. Let the unit cool down before making 
any adjustments. 

 

IMPORTANT

 

The combustion check verification MUST be performed after 
the nozzle replacement or the burner cleaning. After these 
manipulations, the combustion parameters are necessarily 
modified. Refer also to the burner instruction manual.  

 

1. 

Pierce a test hole in the flue pipe, approximately 18 inches 
from the furnace breech. Insert the smoke test probe into 
the hole. For installation using a sidewall venting, use the 
orifice provided on the breech plate; 

2. 

From a cold start, let the unit operate for about 5  minutes; 

3. 

Set the burner air setting until you have between 0 and 1 
on the Bacharach Scale (or a ‘’trace’’); 

4. 

Take a CO

2

 sample at the same test location where the 

#1 smoke reading was taken and make note of it. 
Example: 13.8% of CO

2

 or 2.5% of O

2

5. 

Adjust the burner air setting to obtain a CO

reading 1.5% 

lower (or a O

2

 reading 2.0% higher) than the reading 

associated with the ‘’trace’’ of smoke. Example: 12.3% of 
CO

2

 or 4.5% of O

2

6. 

This method of adjusting the burner will result in clean 
combustion (Bacharach smoke scale between 0 and a 
‘’trace’’) and ensure the proper functioning of the system. 
The optimum CO

2

 level is around 12% to 13% (or 3.5% to 

5.0% of O

2

). 

3.3.4 

Draft Regulator adjustment 

On chimney installations only, a barometric draft regulator 
(supplied with the furnace) must be installed, in order to ensure 
proper draft through the furnace. The barometric damper must 
be mounted with the hinge pins in a horizontal position and the 
face of the damper vertical for proper functioning (see 
instructions included with the damper.) After the furnace has 
been firing for at least five minutes, the draft regulator should 
be set to between -0.025" and -0.060" W.C. 

3.3.5 

Overfire pressure test 

The overfire draft that is taken through the observation port, 
located above the burner, is a measurement necessary to 
determine if there is a blockage in the heat exchanger or the 
flue pipe. Refer to the Technical Specifications in this manual 
for overfire pressure values. A high pressure condition may be 
caused by excessive combustion air, due to the air band being 
too wide open, or a lack of flue draft (chimney effect) or some 
other blockage, such as soot in the secondary section of the 
heat exchanger or the use of an oversize nozzle input or high 
pressure pump. 

3.3.6  Vent Temperature Test  

1. 

After having adjusted the burner combustion, insert a 
thermometer into the test hole in the breech pipe; 

2. 

The total vent temperature should be between 204 
and 302°C (400 and 575°F). If not, check for improper 
air temperature rise, pump pressure, nozzle size or a 
badly sooted heat exchanger. 

 

3.3.7  Supply Air Temperature Rise Test 

1. 

Operate the burner for at least 10 minutes; 

2. 

Measure the air temperature in the return air plenum; 

3. 

Measuring the air temperature in the largest trunk 
coming off the supply air plenum, just outside the 
range of radiant heat from the heat exchanger. 0.3 m 
(12") from the plenum of the main take-off is usually 
sufficient; 

4. 

The temperature rise is calculated by subtracting the 
return air temperature from the supply air 
temperature; 

5. 

If the temperature rise is lower or exceeds the 
temperature specified in Table 6, change to the next 
lower or higher blower speed tap, until the 
temperature rise falls to the target. If the excessive 
temperature rise cannot be increased or reduced by 
changing fan speed, investigate for ductwork 
obstructions, dirty or improper air filter, improper firing 
caused by improper pump pressure or nozzle sizing. 

3.3.8  Limit Control Check 

After operating the furnace for at least 15 minutes, restrict 
the return air supply by blocking the filters or the return air 
register and allow the furnace to shut off on High Limit. 
The burner will shut off but the blower will continue to run. 

 

Remove the obstruction and the burner should restart 
after a few minutes. The time required for the restart also 
depends on the adjustment of the blower “OFF” delay. 

3.3.9  Restart after Burner Failure 

1. 

Set the thermostat lower than room temperature; 

2. 

Press the reset button on the burner primary control 
(relay); 

3. 

Set the thermostat higher than room temperature; 

4. 

If the burner motor does not start or ignition fails, turn 
off the disconnect switch and CALL A QUALIFIED 
SERVICE TECHNICIAN. 

 

 
 

 

CAUTION 

 

Do not attempt to start the burner when excess oil has 
accumulated, when the furnace is full of vapour or when 
the combustion chamber is hot. 
 

Summary of Contents for OBM098

Page 1: ...on in this booklet to service the appliance and affix the booklet adjacent to the appliance after servicing C US Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the progr...

Page 2: ...VENTING 8 2 8 COMBUSTION AIR SUPPLY AND VENTILATION 8 2 9 OIL TANK 9 2 10 DUCTING 9 2 11 SUPPLY AIR ADJUSTMENTS 4 SPEED MOTORS 9 2 12 SUPPLY AIR ADJUSTMENTS ECM VARIABLE SPEED MOTORS 10 2 13 INSTALLA...

Page 3: ...d motor PSC 23 Table 11 Parts list with variable speed motor ECM 25 FIGURES Figure 1 Location and dimensions of ventilation air openings in a closet door 5 Figure 2 Upflow installation 5 Figure 3 Down...

Page 4: ...ired information such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must c...

Page 5: ...nstallation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to premature failure of the...

Page 6: ...2 3 ELECTRICAL SYSTEM CAUTION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied wit...

Page 7: ...he air and turbulator settings to those listed in this manual Table 6 Once the burner becomes operational final adjustments will be required Refer to section 3 of this manual 2 5 3 Post purge delay ad...

Page 8: ...se of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furna...

Page 9: ...ance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal duct...

Page 10: ...OSITION Input USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel b...

Page 11: ...stop delays are satisfactory 9 The thermostat of the room is in the heating mode and is set higher than the ambient temperature To start the unit turn the main electrical switch on 3 2 OPERATING SEQU...

Page 12: ...located above the burner is a measurement necessary to determine if there is a blockage in the heat exchanger or the flue pipe Refer to the Technical Specifications in this manual for overfire pressu...

Page 13: ...xchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the burn...

Page 14: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure Lb in 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 15: ...t turbulator damper 0 3 25 0 4 1 5 25 0 3 25 0 4 1 5 25 AFUE FromCSA B212 standard and Canadian regulation 85 0 84 2 81 9 85 0 84 2 81 9 AFUE FromASHRAE103 standard and USregulation 85 0 83 9 81 9 85...

Page 16: ...F 2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 30 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Le...

Page 17: ...URNACE2 N A 5 08 cm 2 N A FLUEPIPE AROUND FLUEPIPE 22 86 cm 9 22 86 cm 9 22 86 cm 9 FRONT FURNACE BURNER SIDE 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 1 These are horizontal dimensions 2 These are vertic...

Page 18: ...18 Figure 9 Furnace dimensions...

Page 19: ...19 Figure 10 Wiring diagram 4 speed motor PSC...

Page 20: ...20 Figure 11 Wiring diagram variable speed motor ECM...

Page 21: ...21 COMPONENTS AND REPLACEMENT PARTS...

Page 22: ...22 Figure 12 Parts list with 4 speed motor PSC B50064G...

Page 23: ...PANEL ASSEMBLY LEFT Panel insulation and baffle included 31 B03480 FILTER RACK KIT 32 B03450 02 LATERAL BAFFLE 33 B30513 BLOWER SLIDE One slide included 34 B03441 BLOWER DIVIDER 35 B03451 REAR BAFFLE...

Page 24: ...24 Figure 13 Parts list with variable speed motor ECM B50074H...

Page 25: ...8 B03470 FLOOR 29 B03426 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 30 B03480 FILTER RACK KIT 31 B03450 02 LATERAL BAFFLE 32 B30513 BLOWER SLIDE One slide included 33 B03441 BLOW...

Page 26: ...RVICE Utiliser l information contenue dans ce manuel afin d effectuer l entretien de l appareil Garder ce manual pr s de l unit pour r f rences ult rieures C US Use of the AHRI Certified TM Mark indic...

Page 27: ...R SERVOIR DE MAZOUT 10 2 10 SYST ME DE DISTRIBUTION D AIR 10 2 11 AJUSTEMENT DES D BITS D AIR DE VENTILATION MOTEUR 4 VITESSES 10 2 12 AJUSTEMENT DES D BITS D AIR DE VENTILATION MOTEUR VITESSE VARIABL...

Page 28: ...11 Diagramme lectrique moteur vitesse variable ECM 21 Figure 12 Liste de pi ces avec moteur 4 vitesses PSC 23 Figure 13 Liste de pi ces avec moteur vitesse variable ECM 25 TABLEAUX Tableau 1 Ajusteme...

Page 29: ...iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service ayez en main la page de la fiche technique section 5 de ce manuel pou...

Page 30: ...e chauffage au mazout ANSI NFPA 90B Syst mes de chauffage air chaud et syst me d air climatis ANSI NFPA 211 Chemin e Foyers vents et appareils de chauffage ANSI NFPA 70 Code National d lectricit CSA C...

Page 31: ...e pour un retour par le plancher FRB 101 ou KLARB0101DET Le br leur doit toujours tre install dans le m me sens peu importe l orientation de la fournaise Voir figure 3 pour plus de d tails Figure 3 D...

Page 32: ...uffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 4 INSTALLATION DU THERMOSTAT L installation d un thermostat de contr le de la temp rature de l...

Page 33: ...contr le du br leur pour plus de d tail concernant l ajustement du d lai post purge 2 6 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions...

Page 34: ...rme APPELER UN TECHNICIEN QUALIFI 2 8 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone R f rer aux codes d installation des appareils...

Page 35: ...tour de mazout vers le r servoir avec une pompe appropri une l vation de 2 4 m 8 et plus requi rent une pompe deux stage et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives...

Page 36: ...T Chauffage Position interrupteurs DIP 1 2 POSITION Consommation USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL Tableau 3 Ajustements des d bits d air mode climatisation SW2 COOL Climati...

Page 37: ...br leur est conforme aux tableaux des sp cifications de ce manuel 7 L ajustement des vitesses de ventilation en chauffage et climatisation sont ad quats et selon les sp cifications de ce manuel 8 Les...

Page 38: ...es pins l horizontale et le devant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r gulateur de tirage apr s que l appareil ait fonctionn e au moins cinq minut...

Page 39: ...l interrupteur d alimentation principal de la fournaise est en position ON 4 Ajuster le thermostat au dessus de la temp rature ambiante 5 Si l allumage du br leur de s effectue pas couper l alimentati...

Page 40: ...ILE Filtre du r servoir Remplacer le filtre du r servoir au besoin Suivre les instructions du fabriquant Filtre secondaire Remplacer les cartouches des filtres de 10 microns ou moins une fois par ann...

Page 41: ...AFUE partir du standard CSAB212 et des lois canadiennes 85 0 84 2 81 9 85 0 84 2 81 9 AFUE partir du standard ASHRAE103 et des lois am ricaines 85 0 83 9 81 9 85 0 83 9 81 9 BR LEUR RIELLO MOD LE40 B...

Page 42: ...0 D 1 ON 2 ON 1 5 600 660 540 SW4 D LAI Position interrupteurs DIP Consommation Chauffage USGPH PreRun D lai On Niveau PCM Temps ShortRun D lai On NiveauPCM Temps D lai Off Niveau PCM Temps A 1 OFF 2...

Page 43: ...cm 2 N A TUYAU DE RACCORDEMENT DEVANT FOURNAISE C T BR LEUR 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 1 Ce sont des dimensions horizontales 2 Ce sont des dimensions verticales 3 Pour respecter cette dime...

Page 44: ...19 Figure 9 Dimensions de la fournaise...

Page 45: ...20 Figure 10 Diagramme lectrique moteur 4 vitesses PSC...

Page 46: ...21 Figure 11 Diagramme lectrique moteur vitesse variable ECM...

Page 47: ...22 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 48: ...23 B50064G Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...

Page 49: ...t d flecteur 31 B03480 KIT SUPPORT A FILTRE 32 B03450 02 DEFLECTEUR LATERAL 33 B30513 GLISSIERE DU VENTILATEUR Comprend une seule glissi re 34 B03441 SEPARATEUR DU VENTILATEUR 35 B03451 DEFLECTEUR ARR...

Page 50: ...25 B50074G Figure 13 Liste de pi ces avec moteur vitesse variable ECM...

Page 51: ...UCHE Comprend panneau isolation et d flecteur 30 B03480 KIT SUPPORT A FILTRE 31 B03450 02 DEFLECTEUR LATERAL 32 B30513 GLISSIERE DU VENTILATEUR Comprend une seule glissi re 33 B03441 SEPARATEUR DU VEN...

Reviews: