TABLE 6—MODEL 383KAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

(TABULATED DATA BASED ON 22,000 BTUH PER BURNER, DERATED 4 PERCENT PER 1000 FT ABOVE SEA LEVEL)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

and

Canada

850

42

3.6

42

3.8

41

3.5

41

3.6

41

3.7

875

42

3.4

42

3.6

42

3.7

42

3.8

41

3.5

900

42

3.2

42

3.4

42

3.5

42

3.6

42

3.7

0

925

43

3.7

42

3.2

42

3.3

42

3.4

42

3.5

950

43

3.6

43

3.7

43

3.8

42

3.2

42

3.3

to

975

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

1000

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

2000

1025

44

3.5

43

3.2

43

3.3

43

3.4

43

3.5

1050

44

3.3

44

3.4

44

3.6

43

3.2

43

3.3

1075

45

3.8

44

3.3

44

3.4

44

3.5

43

3.2

1100

45

3.7

45

3.8

44

3.2

44

3.4

44

3.5

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

and

Canada

U.S.A.

775

42

3.4

42

3.5

42

3.6

42

3.7

42

3.8

Altitudes

800

43

3.8

42

3.3

42

3.4

42

3.5

42

3.6

2001

825

43

3.6

43

3.7

42

3.2

42

3.3

42

3.4

to

850

43

3.4

43

3.5

43

3.6

43

3.8

42

3.2

3000

875

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

or

900

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

Canada

925

43

2.9

43

3.0

43

3.1

43

3.2

43

3.3

Altitudes

950

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

2000

975

43

2.6

43

2.7

43

2.8

43

2.9

43

2.9

to

1000

43

2.5

43

2.5

43

2.6

43

2.7

43

2.8

4500

1025

43

2.3

43

2.4

43

2.5

43

2.6

43

2.7

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

750

43

3.8

42

3.3

42

3.4

42

3.5

42

3.6

775

43

3.6

43

3.7

43

3.8

42

3.3

42

3.4

800

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

3001

825

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

850

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

to

875

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

900

43

2.7

43

2.8

43

2.9

43

2.9

43

3.0

4000

925

43

2.5

43

2.6

43

2.7

43

2.8

43

2.9

950

43

2.4

43

2.5

43

2.6

43

2.6

43

2.7

975

43

2.3

43

2.4

43

2.4

43

2.5

43

2.6

1000

43

2.2

43

2.2

43

2.3

43

2.4

43

2.5

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

725

43

3.6

43

3.7

42

3.2

42

3.3

42

3.4

750

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

775

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

4001

800

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

825

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

to

850

43

2.6

43

2.7

43

2.8

43

2.9

43

3.0

875

43

2.5

43

2.6

43

2.6

43

2.7

43

2.8

5000

900

43

2.3

43

2.4

43

2.5

43

2.6

43

2.7

925

43

2.2

43

2.3

43

2.4

43

2.4

43

2.5

950

43

2.1

43

2.2

43

2.2

43

2.3

43

2.4

—13—

Summary of Contents for Series G 383KAV

Page 1: ...PA 90B In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2 M95 Natural Gas and Propane Installation Codes NSCNGPIC Wear safety glasses and work gloves Have f...

Page 2: ...LB 024045 14 3 16 12 9 16 12 11 16 4 122 036045 14 3 16 12 9 16 12 11 16 4 124 024070 14 3 16 12 9 16 12 11 16 4 132 036070 14 3 16 12 9 16 12 11 16 4 134 042091 17 1 2 15 7 8 16 4 150 048091 21 19 3...

Page 3: ...oper installation or misapplication of the furnace can require excessive servicing or cause prema ture component failure This furnace is designed for a minimum continuous return air temperature of 60...

Page 4: ...on must not be contami nated by halogen compounds which include fluoride chloride bromide and iodide These elements are found in aerosol sprays detergents bleaches cleaning solvents salts air freshene...

Page 5: ...y connect The minimum dimension of ducts must not be less than 3 in See Fig 4 WARNING Do not install the furnace on its back or sides Safety control operation will be adversely affected Never connect...

Page 6: ...ble 3 indicates filter size location and quantity shipped with the furnace For bottom air return applications filter may need to be cut to fit some furnace casing widths A bottom closure panel is fact...

Page 7: ...istant to the action of propane gas An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in of the furnace A 1 8 in NPT plugged tapping accessible fo...

Page 8: ...024045 115 60 1 127 104 6 0 14 47 15 036045 115 60 1 127 104 8 3 14 34 15 024070 115 60 1 127 104 5 9 14 47 15 036070 115 60 1 127 104 8 7 14 32 15 042091 115 60 1 127 104 9 0 14 31 15 048091 115 60...

Page 9: ...automotive type 3 amp fuse located on the main control board Any direct shorts during installation service or maintenance could cause this fuse to blow If fuse replacement is required use ONLY a 3 am...

Page 10: ...nic air cleaner are energized g Blower off delay When thermostat is satisfied circuit between R W is broken de energizing gas valve stop ping gas flow to burners The blower motor and EAC remain energi...

Page 11: ...RING 24VAC FIELD WIRING 115VAC FIELD WIRING 24VAC CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 NEUTRAL L1 BLWR HI LO TO 115VAC FIELD DISCONNECT...

Page 12: ...ion to find orifice size and manifold pressure settings for proper operation EXAMPLE 0 2000 ft altitude Heating value 1025 Btu cu ft Specific gravity 0 62 Therefore Orifice No 43 Manifold pressure 3 3...

Page 13: ...43 3 4 Canada 925 43 2 9 43 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 4...

Page 14: ...8 43 2 9 43 3 0 43 3 1 750 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 4...

Page 15: ...RCENT PER 1000 FT ABOVE SEA LEVEL ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 0 66 Orifice No Manifold Pressure Orifice No Manifold P...

Page 16: ...h 3 Check pressure switch This control proves operation of draft inducer blower a Turn off 115 v power to furnace b Remove control door and disconnect inducer motor lead wires from wire harness c Turn...

Reviews: