Boiler operating conditions for countries outside the EU
12
63
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
12.3 Conditions for air supply and flue pipes
12.4 Conditions for fuel – natural gas H (physical requirements)
Operating conditions
Dimension Boiler output (in case of multi-boiler
systems = total output) in kW
Air supply cross-section in cm
2
(unrestricted aperture)
Cross-section for the
supply of combustion air
from outside – total
output of all combustion
equipment in kW
cm
2
100 to 150
350
150 to 200
450
200 to 250
550
250 to 300
650
300 to 350
750
350 to 400
850
Operating conditions
Dimension
Notes – More detailed requirements
Required flue gas system
draught (negative pressure
inside the flue pipe)
Pa
3 – 30
Only operate these boilers with a chimney or flue gas system,
which supply the stated draught during operation. Only use non-
flammable materials.
Tab. 25 Air supply and flue pipe
Operating conditions
Dimension
Notes – More detailed requirements
General information
–
–
Only use natural gas as fuel. The following are, amongst others,
not permissible:
!
Propane:air mixtures
!
Sewer gas
!
Biogas
!
Pit gas
!
Methane
Wobbe index (W
S
)
kWh/m
3
n
12.0 – 16.1
W
S
at 0 °C; 1013 hPA
Gross calorific value (H
S
)
kWh/m
3
n
9.5 – 13.1
Relative density
–
0.55 – 0.75
Water content – dewpoint
°C
max. + 5
Dust, mist, liquid
–
–
Technically free, i.e. a constant operation of gas systems will not
lead to accumulation, which causes reductions in the cross-
section of valves, strainers and filters.
Hydrocarbons – condensing
point
°C
–
Ground temperature at the respective pipe pressure.
Supply pressure
mbar
17.0 – 25.0
(10.0)
The additional "Gas pressure switch" is required for systems,
where the supply pressure can temporarily fall below 17 mbar.
Static pressure (burner OFF)
mbar
max. 30
Protection against
overpressure upstream of the
boiler
mbar
max. 100.0
The stated pressure must not be exceeded in case of faults
caused by a failure of the supply network pressure regulator.
Ensure the protection against overpressure through the
installation of a safety shut-off valve or a safety blow-off valve.
Tab. 26 Fuel – natural gas H (physical requirements)