Converting the boiler to a different gas type
9
9
Converting the boiler to a different gas type
The Logano GE434 gas-fired special boiler is factory-set
to natural gas. Should you wish to change the gas type,
proceed as follows:
9.1
Conversion within a gas family
!
Isolate the heating system from the mains electrical
supply; to do that, set the ON/OFF switch to "0"
(OFF).
!
Close the gas shut-off valve.
!
Remove the boiler side panels.
!
Replace the main gas nozzle for those used with the
new gas type, and use new gaskets.
!
Check the main gas nozzles by means of their
designation Table 17 and Fig. 25.
!
Carry out all commissioning steps and complete the
commissioning report.
!
Affix the label for the new gas type on the type plate.
CAUTION!
OPERATING FAULT
through an error during gas type
conversion.
!
Strictly observe the sequence of the
steps described.
!
Complete all steps.
Main gas nozzle designation
Natural gas
H (G20)
GZ 50
Natural gas
L (G25)
S (G25.1)
LPG
Propane
P (G31)
LPG
B/P (G30)
295
340
190
180
Tab. 17 Main gas nozzle designation
PLEASE NOTE
The following applies to Belgium (BE):
Only Buderus service engineers may
carry out a conversion to another gas
type.
Fig. 25
Checking the main gas nozzle
Item 1:
Short version (natural gas L (G25), S (G25.1))
Item 2:
Long version (natural gas H (G20), GZ50 or LPG)
1
2