Boiler positioning
7
Logano GE515 - We reserve the right to make any changes due to technical modifications.
16
7.2
Recommended wall clearances
You may hang the burner door for l.h. or r.h. opening (in
the "as delivered condition" the door will be hinged on
the r.h. side).
When installing your boiler, please maintain the
recommended minimum dimensions (shown in
brackets). Select the recommended clearances
between wall and boiler to enable easy access during
installation, maintenance and service work.
The distance from the wall on the hinge side must at
least permit the burner withdrawal (AB). We recommend
a distance between wall and boiler of AB + 100 mm.
If a front clearance less than the recommended
dimension A (Fig. 6) is chosen, you will not be able to
clean the boiler with the optional cleaning kit. As an
alternative we would recommend the use of shorter
(length approx. 1 m) cleaning devices or wet cleaning.
Fig. 6
Boiler room with boiler (dimensions in mm)
USER NOTE
z
We recommend you maintain the
indicated clearance between boiler and
walls, which is required in order to be
able to install the boiler and for opening
the burner door, as well as for cleaning
and maintaining your system (
Æ
and table below).
Boiler size
Clearance A in mm
kW
Boiler
sections
Recommen
-dation
There
follows
240–350
7–9
1 700
1 000
400–510
10–12
2 200
1 000