System start-up
12
Logano GE515 - We reserve the right to make any changes due to technical modifications.
53
12.5.3 Slightly raising the flue gas temperature
z
Remove the Allen screw (Fig. 69,
[3]
) inside each hot
gas check plate and remove the l.h. and r.h. hot gas
check plates (Fig. 68,
[1]
and
[2]
).
z
Position the hot gas check plate onto the support, so
that the notches (Fig. 69,
[1]
and
[2]
) are hollow to
the bottom. With a hammer knock one segment each
off the l.h. and r.h. hot gas check plate.
z
With the Allen screw, reinstall the hot gas check plate
on the front section.
z
The second segment of the hot gas check plates may
be separated in the same way, if the resulting flue
gas temperature rise is insufficient; otherwise you
may remove the complete hot gas check plates as
described above.
Fig. 69 Hot gas check plate
1
2
3