11 Burner installation
This chapter explains the main installation steps for
burners.
z
Close the burner door and secure with 4 bolts
(M16 x 140) (
chapter 8.8 "Installing boiler fittings
and the burner door", Fig. 32,
[3]
to
[6]
). Tighten the
screws alternately in a cross pattern.
z
Cut the steel insert plate
[1]
) on site using
oxy-acetylene or a drill according to the required
blast tube diameter (Ø max. 270 mm). Drill the
burner mounting holes according to the hole pattern
of the burner connection flange.
z
Secure the burner plate on the burner door with
screws provided (seal with GP packing cord
Ø 10 mm).
z
Screw the burner to the burner plate.
z
Cut out insulating rings according to the burner pipe
diameter (Fig. 66,
[2]
).
z
Fill the remaining gap between the thermal insulation
on the burner door and the blast tube (Fig. 66,
[4]
)
with suitably adapted insulating rings (Fig. 66,
[3]
).
z
Connect the breather tube on the sight glass with the
burner to keep the glass free from condensation.
CAUTION!
SYSTEM DAMAGE
through incorrect burner.
z
Only use burners which meet the
technical preconditions of
Logano GE515 (
Fig. 66 Install the burner (dimensions in mm)
1
2
3
4
USER NOTE
Upon request, you may order pre-drilled
burner plates (accessory) from Buderus.