Correcting burner faults
15
Logano GE515 - We reserve the right to make any changes due to technical modifications.
65
15 Correcting burner faults
Heating system faults are indicated in the control device
display. You will find detailed information regarding fault
displays in the service instructions of each respective
control device. In addition any burner fault is indicated
by a fault lamp on the burner.
z
Press the burner reset button (
Æ
burner operating
instructions).
See the technical burner documentation for information
regarding the resetting of the burner, if the burner will not
start after three attempts.
CAUTION!
SYSTEM DAMAGE
through frequent activation of the reset
button.
The burner ignition transformer may be
damaged if you press the reset button
more than three times in succession after
the burner refuses to start.
z
Do not attempt to clear a fault more
than three times in succession by using
the reset button.