CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V,
10A,
240W,
S
INGLE
P
HASE
I
NPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3.
AC-I
NPUT
AC input
Nom.
AC 100-240V
Suitable for TN-, TT- and IT mains networks
AC input range
Min.
85-264Vac
Continuous operation
Min.
264-300Vac
For maximal 500ms
Allowed voltage L or N to earth
Max.
300Vac
Continuous according to IEC 62477-1
Input frequency
Nom.
50–60Hz
±6%
Turn-on voltage
Typ.
80Vac
Steady-state value, see Fig. 3-1
Shut-down voltage
Typ.
70Vac
Steady-state value, see Fig. 3-1
Typ.
55Vac
Dynamic value for maximal 250ms
External input protection
See recommendations in chapter 24.3.
AC 100V
AC 120V
AC 230V
Input current
Typ.
2.60A
2.15A
1.13A
At 24V, 10A, see Fig. 3-3
Power factor
*)
Typ.
0.99 0.99 0.97
At
24V, 10A, see Fig. 3-4
Crest factor
**)
Typ.
1.5
1.5
1.65
At 24V, 10A
Start-up
delay
Typ. 300ms 290ms 240ms
See
Fig. 3-2
Rise
time
Typ. 30ms 30ms 30ms
At 24V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
Typ.
75ms
75ms
75ms
at 24V, 10A const. current load,
10mF load capacitance,, see Fig. 3-2
Turn-on overshoot
Max.
200mV 200mV 200mV
See
Fig. 3-2
External input protection
See recommendations in chapter 24.3.
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-down
Start-up
delay
Rise
Time
O
v
e
rshoot
- 5%
Output
Voltage
Input
Voltage
4/30