CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V,
10A,
240W,
S
INGLE
P
HASE
I
NPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/30
12.
T
ERMINALS AND
W
IRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
CP10.241, CP10.241-C1, CP10.242
Input
Output
DC-OK-Signal
Type Screw
termination
Screw
termination Push-in
termination
Solid wire
Max. 6mm
2
Max.
6mm
2
Max.
1.5mm
2
Stranded wire
Max. 4mm
2
Max.
4mm
2
Max.
1.5mm
2
American Wire Gauge
AWG 20-10
AWG 20-10
AWG 24-16
Max. wire diameter (including ferrules) 2.8mm
2.8mm
1.6mm
Recommended tightening torque
Max. 1Nm, 9lb-in
Max. 1Nm, 9lb-in
-
Wire stripping length
7mm / 0.28inch
7mm / 0.28inch
7mm / 0.28inch
Screwdriver
3.5mm slotted or cross-
head No 2
3.5mm slotted or cross-
head No 2
3mm slotted to open
the spring
CP10.241-S1 Input
Output
DC-OK-Signal
Type Quick-connect
spring-
clamp termination
Quick-connect spring-
clamp termination
Push-in termination
Solid wire
Max. 6mm
2
Max.
6mm
2
Max.
1.5mm
2
Stranded wire
Max. 4mm
2
Max.
4mm
2
Max.
1.5mm
2
American Wire Gauge
AWG 20-10
AWG 20-10
AWG 24-16
Max. wire diameter (including ferrules) 2.8mm
2.8mm
1.6mm
Wire stripping length
10mm / 0.4inch
10mm / 0.4inch
7mm / 0.28inch
Screwdriver
-
-
3mm slotted to open
the spring
CP10.241-S2 Input
Output
DC-OK-Signal
Type Push-in
termination
Push-in termination
Push-in termination
Solid wire
Max. 2.5mm
2
Max.
2.5mm
2
Max.
1.5mm
2
Stranded wire
Max. 2.5mm
2
Max.
2.5mm
2
Max.
1.5mm
2
Stranded wire with ferrules
Max. 1.5mm
2
Max.
1.5mm
2
Max.
1.5mm
2
American Wire Gauge
AWG 24-12
AWG 24-12
AWG 24-16
Max. wire diameter (including ferrules) 2.3mm
2.3mm
1.6mm
Wire stripping length
10mm / 0.4inch
10mm / 0.4inch
7mm / 0.28inch
Screwdriver
3.0mm slotted to open
the spring
3.0mm slotted to open
the spring
3mm slotted to open
the spring
Instructions for wiring:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.