CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V,
10A,
240W,
S
INGLE
P
HASE
I
NPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14.
F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 14-1
Front side CP10.241
Fig. 14-2
Front side CP10.241-C1
Fig. 14-3
Front side CP10.241-S1
Fig. 14-4
Front side CP10.241-S2
Fig. 14-5
Front side CP10.242
A Input
Terminals
CP10.241, CP10.241-C1, CP10.242: Screw terminals
CP10.241-S1: Spring-clamp terminals
CP10.241-S2: Push-in terminals
N,
L
Line input
PE (Protective Earth) input
B Output
Terminals
(two ide poles and three identical - poles)
CP10.241, CP10.241-C1, CP10.242: Screw terminals
CP10.241-S1: Spring-clamp terminals
CP10.241-S2: Push-in terminals
+
Positive output
–
Negative (return) output
C Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 24.1V
D DC-OK
LED
(green)
On, when the output voltage is in range and the DC-OK contact is closed.
E DC-OK
Relay
Contact
(push-in terminals)
Monitors the output voltage of the running power supply. See chapter 8 for details.
14/30