CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V,
10A,
240W,
S
INGLE
P
HASE
I
NPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/30
17.
P
ROTECTION
F
EATURES
Output protection
Electronically protected against overload, no-load and short-circuits. In case of a
protection event, audible noise may occur.
Output over-voltage protection Typ.
30.5Vdc
Max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 4mm
E.g. screws, small parts
Over-temperature protection
Yes
Output shut-down with automatic restart.
The temperature sensor is installed on critical
components inside the unit and turns the unit off in
safety critical situations, which can happen e.g. when
de-rating requirements are not observed, ambient
temperature is too high, ventilation is obstructed or
the de-rating requirements for different mounting
orientation is not followed. There is no correlation
between the operating temperature and turn-off
temperature since this is dependent on input voltage,
load and installation methods.
Input transient protection
MOV
(Metal Oxide Varistor)
For protection values see chapter 15 (EMC).
Internal input fuse
Included
Not user replaceable slow-blow high-braking capacity
fuse
18.
S
AFETY
F
EATURES
Input / output separation
Double or reinforced galvanic isolation
SELV
IEC/EN
60950-1
PELV
IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 500MOhm
At delivered condition between input and output,
measured with 500Vdc
> 500MOhm
At delivered condition between input and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance
< 0.1Ohm
Resistance between PE terminal and the housing in the
area of the DIN-rail mounting bracket.
Touch current (leakage current)
Typ. 0.14mA / 0.36mA
At 100Vac, 50Hz, TN-,TT-mains / IT-mains
Typ. 0.20mA / 0.50mA
At 120Vac, 60Hz, TN-,TT-mains / IT-mains
Typ. 0.33mA / 0.86mA
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.18mA / 0.43mA
At 110Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.26mA / 0.61mA
At 132Vac, 60Hz, TN-,TT-mains / IT-mains
Max. 0.44mA / 1.05mA
At 264Vac, 50Hz, TN-,TT-mains / IT-mains