Summary of Contents for Bull Blade (9U)

Page 1: ...Site Preparation Guide NOVASCALE REFERENCE 86 A1 87EF 10...

Page 2: ...BLANK...

Page 3: ...NOVASCALE Site Preparation Guide January 2008 BULL CEDOC 357 AVENUE PATTON B P 20845 49008 ANGERS CEDEX 01 FRANCE REFERENCE 86 A1 87EF 10 Hardware...

Page 4: ...hnical Publications you are invited to use the Ordering Form also provided at the end of this book Trademarks and Acknowledgements We acknowledge the rights of the proprietors of the trademarks mentio...

Page 5: ...ter Layout 2 1 Planning Installation 2 3 Cable Cut outs 2 3 Power Cables 2 3 Network Cables 2 4 Service Clearance 2 5 Electrical Electromagnetic Interference 2 7 Fire Protection 2 7 Fire Detection 2 7...

Page 6: ...Series Server Cabinet Specifications A 10 Novascale 3025 Server CPU Drawer Specifications A 12 NovaScale 3045 Server CPU Drawer Specifications A 13 NovaScale 3045 COMPACT Server CPU Drawer Specificati...

Page 7: ...clearance 2 5 Figure 7 Layout grid 2 6 Figure 8 Raised floor cross section 2 9 Figure 9 Raised floor structure 2 10 Figure 10 Example of poor air distribution 3 3 Figure 11 Example of obstacles that...

Page 8: ...045 COMPACT Server CPU drawer specifications A 14 Table 16 NovaScale 4020 4040 Server cabinet specifications A 16 Table 17 NovaScale 4020 Server CPU drawer specifications A 17 Table 18 NovaScale 4040...

Page 9: ...r Conditioning describes site air conditioning requirements Chapter 4 Power Supply describes site power supply requirements Appendix A Specifications Appendix B Conversion Tables Definition of Safety...

Page 10: ...proofing protection from sunlight access control fire protection water protection air conditioning power supply Warning The installation of an on line Uninterruptible Power Supply UPS is strongly rec...

Page 11: ...ional CSA 60950 Canada European Community EC Council Directives This product is in conformity with the protection requirements of the following EC Council Directives Electromagnetic Compatibility 2004...

Page 12: ...this equipment Unauthorized changes or modifications could void the user s authority to operate the equipment Any changes or modifications not expressly approved by the grantee of this device could vo...

Page 13: ...336 EEC EN55022 Class A Limit Radiated Conducted Emissions EN55024 ITE Specific Immunity Standard EN61000 4 2 ESD Immunity Level 2 Contact Discharge Level 3 Air Dis charge EN61000 4 3 Radiated Immuni...

Page 14: ...27 IEC 60068 2 31 IEC 60068 2 47 IEC 60068 2 64 IEC 60050 ISO 2041 ISO 5348 ISO 5344 ISO 8626 Operating Mode on levelers Sinusoidal vibrations Duration 1 sweep 1 octave mn 5 16 Hz range 0 25 mm peak...

Page 15: ...9295 ISO 9296 IEC 61260 IEC 60651 Bull NovaScale 5xx5 Series Bull NovaScale 5xx5 Series IEC 61672 1 Bull NovaScale 4000 Series IEC 61672 2 Bull NovaScale 4000 Series Operating LwAd Acoustical Power 7...

Page 16: ...xiv Site Preparation Guide...

Page 17: ...servers It includes the following topics Server Cabinet on page 1 1 Delivery Conditions on page 1 2 Carry In Route on page 1 2 Unpacking Requirements on page 1 3 Server Cabinets The servers are delive...

Page 18: ...vice Engineers only Carry In Route The route from the unloading bay to the Computer Room must be checked to ensure that the server can be carried into the premises easily and that floors can support t...

Page 19: ...oading The Data Processing Site manager must set aside the required working area for unpacking as shown in the following figure See Appendix A Specifications for packing size Figure 2 Required unpacki...

Page 20: ...1 4 Site Preparation Guide...

Page 21: ...Ceiling on page 2 10 Sound proofing on page 2 11 Protection from Sunlight on page 2 11 Cleaning on page 2 11 Media Storage Room on page 2 12 Paper Storage Room on page 2 12 Printing Room on page 2 12...

Page 22: ...FFICE PRINTING ROOM ROOM ROOM STORAGE PAPER ANCILLARY TELECOM ROOM COMPUTER ENTRANCE LOCK EQUIPMENT POWER SUPPLY ROOM CONDITIONING ROOM AIR Figure 3 Recommended Data Processing Center layout Warning W...

Page 23: ...gure 7 Layout grid on page 2 6 cableways extension cables power and telephone sockets storage cabinets Cable Cut outs A cable cut out must be provided at the front or rear base of each cabinet 35 cm 1...

Page 24: ...cale 40x0 Servers 1 x 10 100 Mb Ethernet cable or1 Gigabit Ethernet cable per server CPU drawer NovaScale 5xx0 Servers NovaScale 6xx0 Servers NovaScale 5xx5 SMP Servers NovaScale 5xx5 Partitioned Serv...

Page 25: ...Rear door Server Wall Server Wall Figure 5 Single cabinet service clearance 100 cm 39 4 in 100 cm 39 4 in Depth 150 cm 59 in 100 cm 39 4 in Width Main Cabinet Cabinet Extension Rear doors Width Serve...

Page 26: ...2 6 Site Preparation Guide 1 square 60 x 60 cm Figure 7 Layout grid...

Page 27: ...fire protection walls partitions and doors Fire Detection The Customer must ensure that the following areas are monitored the raised floor plenum the Computer Room environment the suspended ceiling p...

Page 28: ...s is prohibited as from January 1 2003 Alarms A round the clock alarm transfer system is recommended via a watchroom a dedicated in house fire department a remote monitoring center Water Damage It is...

Page 29: ...ccording to slab cutouts and the hardware load The raised floor structure at the actuator base must be meshed with 20mm section flat tin plated copper braiding See Figure 15 Raised floor equipotential...

Page 30: ...0 meters Insufficient ceiling height may adversely affect the air conditioning system and make personnel uncomfortable The primary ceiling and wall drops located at suspended ceiling level must be coa...

Page 31: ...ernal protections only may be used coating canvas curtains or shutter blinds Note Venetian blinds may not be used inside the Computer Room Cleaning Dust has an adverse effect on the correct operation...

Page 32: ...nstall all printers including non impact printers laser magnetographic printers etc in a dedicated room with its own air conditioning system A large volume of rapid printing generates more paper dust...

Page 33: ...s each providing at least 66 of the total cooling power to ensure continuity of operation Note The air conditioning system will dry conditioned air It is therefore mandatory for the air conditioning s...

Page 34: ...ir Renewal Distribution Circulation Pollution and Filtering Renewal A fresh air supply is mandatory for the comfort and health of personnel The fresh air supply must be directly input at air condition...

Page 35: ...e obstructed by oversize pipes or cableways raised floor slabs must be correctly fitted Warning Do not place perforated damper slabs in the immediate vicinity of one or more air conditioning cabinets...

Page 36: ...ters and impaired thermal dissipation damaged connections contact points intermittent failures deterioration of magnetic media premature wear and tear of components and moving parts Note The Computer...

Page 37: ...omputer Room climatic environment conditions A weekly thermo hygrograph recording sheet must be displayed so that any disruptions in the air conditioning system can be viewed and recorded Thermo hygro...

Page 38: ...3 6 Site Preparation Guide...

Page 39: ...data cables must be laid in bulk on the primary slab in the raised floor plenum If cableways are required electricity distribution cables must be separated from data transmission cables separation of...

Page 40: ...ide Important Each Power Distribution Unit PDU and the UPS require an extra cable length of 1 5 meters for connection inside the cabinet The Central Subsystem CSS Module cable length allows connection...

Page 41: ...er is responsible for supplying and installing appropriate sockets for connection to the site power supply Except for UPS 7 5 10 KVA Power Cables are hard wired directly in the UPS without plug Figure...

Page 42: ...ugh 4 Unscrew the base of the socket A insert the cable through the socket base B and wire to the socket head as shown in Figure 14 Figure 14 PDU UPS Power socket 5 Screw the socket base back to the s...

Page 43: ...minate the occurrence different transient potentials within the same unit Electric protection wire characteristics in compliance with Standard NFC 15 100 flexible multi strand black noise free groundi...

Page 44: ...the PE wire are connected to the same output point of the source the voltage measured between Neutral and Ground at any point in the installation must approach 0 Volt At the secondary winding of the...

Page 45: ...equipotential bar P E Y G Measurement bar Electricity Power Supply Interface Computer and peripherals cab cab Panel Data processing equipotential line flexible multi strand wire in compliance with st...

Page 46: ...hting Lighting must be separated from the data processing power supply by a specific distribution cabinet The position of lights must ensure homogeneous lighting It is preferable to flush mount lights...

Page 47: ...er specifications on page A 9 NovaScale 3005 series sever cabinet specifications on page A 10 NovaScale 3025 server CPU drawer specifications on page A 12 NovaScale 3045 server CPU drawer specificatio...

Page 48: ...kg 947 lb Service Clearance Front Rear Side left and right 150 cm 60 in 100 cm 40 in 100 cm 40 in Power cables PDU 2 4 M 32A 1100H L cabinets AC 32A Cable type Connector type 1 per PDU 3 x AWG10 3 x 6...

Page 49: ...ited States of America Nominal voltage Voltage range Frequency 208 VAC Phase Neutral 182 229 VAC 60 Hz 0 3 Japan Nominal voltage Voltage range Frequency 200 VAC Phase Neutral 188 212 VAC 60 Hz 0 2 Bra...

Page 50: ...Btu hr Temperature Requirements Operating Limit Non Operating Dry Bulb Temperature 10 to 35 C 40 to 60 C 50 to 95 F 40 to 140 F Humidity Requirements Operating Limit Non Operating noncondensing 8 to...

Page 51: ...on 4x2900 Watt redundant power supplies 8000 Watts 27280 Btu hr Temperature Requirements Operating Limit Non Operating Dry Bulb Temperature 10 to 35 C 40 to 60 C 50 to 95 F 40 to 140 F Humidity Requir...

Page 52: ...Btu hr Temperature Requirements Operating Limit Non Operating Dry Bulb Temperature 10 to 35 C 40 to 60 C 50 to 95 F 40 to 140 F Humidity Requirements Operating Limit Non Operating noncondensing 8 to...

Page 53: ...ver Specifications Dimensions Weight Height 24 5 cm 9 7 in Width 2 9 cm 1 14 in Depth 44 6 cm 17 6 in Maximum Weight 5 4 kg 12 lbs Electrical Power Redundant 12 VDC 300W max Voltage range VDC 12 VDC T...

Page 54: ...Server Specifications Dimensions Weight Height 24 5 cm 9 7 in Width 2 9 cm 1 14 in Depth 44 6 cm 17 6 in Maximum Weight 5 4 kg 12 lbs Electrical Power Dual redundant 12 VDC 400 W max Voltage range VDC...

Page 55: ...ver Specifications Dimensions Weight Height 24 5 cm 9 7 in Width 5 8 cm 2 28 in Depth 44 6 cm 17 6 in Maximum Weight 9 0 kg 20 lbs Electrical Power Dual redundant 12 VDC 400 W max Voltage range VDC 12...

Page 56: ...empty Weight full 100 0 cm 39 4 in 65 0 cm 25 6 in 113 6 cm 44 7 in 200 kg 440 lb 390 kg 860 lb Height Width Depth Weight empty Weight full 118 0 cm 46 49 in 80 0 cm 31 5 in 120 0 cm 47 2 in 230 kg 5...

Page 57: ...al voltage Voltage range Frequency 230 VAC Phase Neutral 207 244 VAC 50 Hz 1 United States of America Nominal voltage Voltage range Frequency 208 VAC Phase Neutral 182 229 VAC 60 Hz 0 3 Japan Nominal...

Page 58: ...Requirements Operating Non operating Dry Bulb Temperature Gradient 5 to 35 C 41 to 95 F Not stated 10 to 43 C 14 to 109 4 F Not stated Humidity Requirements Operating Non operating non condensing Grad...

Page 59: ...e Requirements Operating Non operating Dry Bulb Temperature Gradient 5 to 35 C 41 to 95 F Not stated 10 to 43 C 14 to 109 4 F Not stated Humidity Requirements Operating Non operating non condensing Gr...

Page 60: ...put typical 1280VA 200 VAC to 240 nominal autoranging 6 10 50 to 60 Hz 5 6 4 amps 1280 VA Temperature Requirements Operating Non operating Dry Bulb Temperature Gradient 5 to 35 C 41 to 95 F Not stated...

Page 61: ...in Weight empty 91 kg 201 lb Weight max 471 kg 1038 lb 1100L Height 108 0 cm 42 5 in Width 80 0 cm 31 5 in Depth 122 0 cm 48 0 in Weight empty 121 kg 267 lb Weight max 501 kg 1120 lb Service Clearanc...

Page 62: ...Voltage range Frequency 230 VAC Phase Neutral 207 244 VAC 50 Hz 1 United States of America Nominal voltage Voltage range Frequency 208 VAC Phase Neutral 182 229 VAC 60 Hz 0 3 Japan Nominal voltage Vol...

Page 63: ...ing Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not stated Not stated Humidity Operating Non Operating non condensing Not stated 95 RH 25 to 30 C 77 to 86...

Page 64: ...rating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not stated Not stated Humidity Operating Non Operating non condensing Not stated 95 RH 25 to 30 C 77 to...

Page 65: ...tput typical 2300 Btu hr Temperature Operating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not stated Not stated Humidity Operating Non Operating non conde...

Page 66: ...ut typical 2300 Btu hr Temperature Operating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not stated Not stated Humidity Operating Non Operating non condens...

Page 67: ...er 600 Watts w PFC 80 efficiency Voltage range VAC 110 VAC to 220 VAC Frequency 50 to 60 Hz Current Not available Thermal output typical Not available Temperature Operating Non Operating Dry Bulb Temp...

Page 68: ...VAC Frequency 50 to 60 Hz Current 14 6 Thermal output typical Not available Temperature Operating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not availabl...

Page 69: ...urrent 10 Amp 4 Amp Thermal output typical Not available Temperature Operating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not available Not available Humi...

Page 70: ...ent 10 Amp 4 Amp Thermal output typical Not available Temperature Operating Non Operating Dry Bulb Temperature 10 to 35 C 40 to 70 C 50 to 95 F 40 to 158 F Gradient Not available Not available Humidit...

Page 71: ...ax wet bulb temperature Moisture content Pressure Elevation 15 C to 30 C 59 F to 86 F Gradient 5 C h 41 F h 35 to 60 Gradient 5 h 24 C 75 2 F 0 019 kg water kg dry air Sea level 2500 m Optimum Operati...

Page 72: ...are auto sensing and auto ranging Current draw Power consumption Thermal dissipation 15 A max at 200 VAC input 3000 VA per full CSS module 1500 VA per PDU 2700 W 9250 BTU per full CSS module 1300 W 4...

Page 73: ...0 Gradient 5 h Relative humidity non condensing Max wet bulb temperature 35 to 60 Gradient 5 h 24 C 75 2 F Max wet bulb temperature Moisture content Pressure Elevation 24 C 75 2 F 0 019 kg water kg dr...

Page 74: ...Power consumption Thermal dissipation 29 5 A max at 200 VAC input 3000 VA per full CSS module 1500 VA per PDU 2700 W 9250 BTU per full CSS module 1300 W 4610 BTU per PDU Europe Nominal voltage Voltage...

Page 75: ...100 cm 100 cm Operating Limits Dry bulb temperature range Relative humidity non condensing Max wet bulb temperature Moisture content Pressure Elevation 15 C to 30 C 59 F to 86 F Gradient 5 C h 41 F h...

Page 76: ...are auto sensing and auto ranging Current draw Power consumption Thermal dissipation 11 A max at 200 VAC input 2400 VA per full CSS module 2400 W 8190 BTU per full CSS mod ule Europe Nominal voltage...

Page 77: ...Service Clearance Front Rear Side free side 150 cm 100 cm 100 cm Operating Limits Dry bulb temperature range Relative humidity non condensing Max wet bulb temperature Moisture content Pressure Elevat...

Page 78: ...e cabinet Electrical Specifications power supplies are auto sensing and auto ranging Current draw Power consumption Thermal dissipation 11 A max at 200 VAC input 2400 VA per full CSS module 2400 W 819...

Page 79: ...lb temperature Moisture content Pressure Elevation 15 C to 30 C 59 F to 86 F Gradient 5 C h 41 F h 35 to 60 Gradient 5 h 24 C 75 2 F 0 019 kg water kg dry air Sea level 2500 m Optimum Operational Reli...

Page 80: ...are auto sensing and auto ranging Current draw Power consumption Thermal dissipation 11 A max at 200 VAC input 2400 VA per full CSS module 2400 W 8190 BTU per full CSS module Europe Nominal voltage V...

Page 81: ...lb temperature Moisture content Pressure Elevation 15 C to 30 C 59 F to 86 F Gradient 5 C h 41 F h 35 to 60 Gradient 5 h 24 C 75 2 F 0 019 kg water kg dry air Sea level 2500 m Optimum Operational Reli...

Page 82: ...are auto sensing and auto ranging Current draw Power consumption Thermal dissipation 11 A max at 200 VAC input 2400 VA per full CSS module 2400 W 8190 BTU per full CSS module Europe Nominal voltage V...

Page 83: ...6000 4 4 1 8000 Input Power Cables Max Input Current Voltage Range Mains Cable Type Mains Plug Type Mains Socket Type 16A 160 280V 3xAWG14 IEC320 C20 IEC320 C19 24A 160 280V 3xAWG10 IEC320 60309 IEC3...

Page 84: ...A 38 Site Preparation Guide...

Page 85: ...conversion table Metric to Imperial 1 meter meter 3 3 feet 1 09 yd yards 1 centimeter cm 0 3937 inches 1 kilometer km 0 62 mi miles 1 gram g 0 04 oz ounces avdp 1 kilogram kg 2 2 lbs pounds avdp 1 sq...

Page 86: ...B 2 Site Preparation Guide...

Page 87: ...e 2 7 protection 2 7 Floor computer room 2 9 primary 2 9 raised 2 9 Floor plan system 2 6 G Grounding 4 5 raised floor 4 5 H Heat dissipation 3 1 Hygrometry control 3 1 I Installation server 2 3 Inter...

Page 88: ...ale 4040 Server A 18 NovaScale 421 Servers A 19 NovaScale 422 Servers A 20 NovaScale 5080 5160 Servers A 25 NovaScale 5085 Servers A 29 NovaScale 5165 Server A 31 NovaScale 5245 Server A 33 NovaScale...

Page 89: ...will be promptly investigated by qualified technical personnel and action will be taken as required If you require a written reply please include your complete mailing address below NAME Date COMPANY...

Page 90: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 91: ...BLANK...

Page 92: ...BULL CEDOC 357 AVENUE PATTON B P 20845 49008 ANGERS CEDEX 01 FRANCE 86 A1 87EF 10 REFERENCE...

Page 93: ...es de d coupe pour obtenir les tiquettes Use the cut marks to get the labels 86 A1 87EF 10 Site Preparation Guide NOVASCALE 86 A1 87EF 10 Site Preparation Guide NOVASCALE 86 A1 87EF 10 Site Preparatio...

Page 94: ......