background image

Failure to heed these warnings could result in death or serious injury.
1.   Improper respirator use could result in death or serious injury. Improper use may also cause certain life-threatening delayed lung 

diseases such as silicosis, pneumoconiosis or asbestosis.

2.   This respirator, when properly fitted and used, significantly reduces, but does not completely eliminate, the breathing of contaminants 

by the respirator wearer. Where excessive airborne contaminant levels are found, you may obtain better respiratory protection from 
other types of respiratory protection equipment such as a valve-operated pressure-demand airline respirator or a pressure-demand 
self-contained breathing apparatus respirator. 

3.   Regulations require that the employer provide training to the user on the proper use, maintenance and limitations of this equipment. 

Each person using this respirator must first read and understand this entire instruction manual. The CC20 Series respirators should 
only be used in accordance with these operating and maintenance instructions. If you have any questions concerning the use of this 
respirator, ask your employer or call Bullard Technical Support at 877-BULLARD (285-5273). 

 4.   Before using these respirators, be sure your employer has determined that ambient airborne contaminant concentrations do not 

exceed those allowed by applicable OSHA, MSHA, EPA, NIOSH or ACGIH regulations and recommendations, or any other applicable 
regulations. Before using the above respirator, Federal law requires that the employer shall identify and evaluate the respiratory 
hazard(s) in the workplace, and that this evaluation shall include a reasonable estimate of employee exposures to respiratory 
hazard(s), and an identification of the contaminant’s chemical state and physical form.

5.   DO NOT wear this respirator if any of the following ambient conditions exist:
 

- Atmosphere is immediately dangerous to your life or health (IDLH). IDLH is defined in 29 CFR 1910.134(b). 

 

 

- You CANNOT escape without the aid of the respirator.   

 

- Atmosphere contains less than 19.5% oxygen. 

 

 

- Work area is poorly ventilated. 

 

 

- Unknown contaminants are present. 

 

 

-  Contaminant concentrations are in excess of regulations or recommendations (as described in item 4 above).

6.   There are users, environments and chemicals for which these respirators are not suitable. It is the responsibility of the user and 

the employer to determine that these respirators are appropriate for the intended use. These respirators should not be used 
around heat, open flames, sparks or in any potentially flammable or explosive environment.  CC20 materials will burn and will melt. 
DuPont Tychem

®

 spunbonded olefin apparel fabrics have “Class 1 - Normal Flammability” characteristics, as tested according to the 

Flammable Fabrics Act. “Class 1” fabrics will burn and do not provide thermal protection if a fire or explosion should occur.

 

 CC20 materials may create static electricity under low relative humidity. Surface resistance and charge dissipation are proportional 
to the amount of antistatic agent on the fabric and the ambient relative humidity. Since the antistatic agent is water soluble, it can be 
washed off with water. In addition, other clothing items that are not anti-static treated might be a potential source of static formation 
and discharge. Contact your employer or DuPont at 1-800-44-TYVEK on this material.

 7.   Bullard recommends that you DO NOT wear these respirators until you have passed a complete physical exam (including a chest 

x-ray), conducted by qualified medical personnel.

 8.    Do not modify or alter these respirators in any manner. Use only CC20 components and replacement parts manufactured by Bullard 

and approved by NIOSH for use with this respirator. Failure to use Bullard components and replacement parts approved by NIOSH 
for use with this respirator voids NIOSH approval of the entire respirator, invalidates all Bullard warranties, and could result in death 
or serious injury, lung disease or exposure to other hazardous or life-threatening conditions.

9.   Inspect all components of these respirator systems during cleaning and before and after each use for signs of wear, tear or damage 

that might reduce the degree of protection originally provided. Immediately replace worn or damaged components with Bullard CC20 
components approved by NIOSH for use with this respirator, or remove the respirator from service. (See INSPECTION, CLEANING 
AND STORAGE section for instructions on proper maintenance of CC20 Series Series respirators.) 

10.   DO NOT connect the respirators’ air supply hose to nitrogen, oxygen, toxic or inert gases. To prevent this, airline couplings used for this 

respirator shall be incompatible with outlets for other gas systems. Failure to connect to the proper air source could result in death or 
serious injury. Be certain your employer has determined that the breathing air source provides at least Grade D breathable air.  

11.    DO NOT use these respirators in poorly ventilated areas, areas where oxygen is less than 19.5%, or in confined spaces such as 

tanks, small rooms, tunnels or vessels unless the confined space is well-ventilated and contaminant concentrations are below the 
upper limit recommended for this respirator. The procedures for confined space entry, operation and exit are defined in applicable 
regulations and standards, including 29 CFR 1910.146. 

12.  DO NOT use these respirators for abrasive blasting or underwater diving.
13.   DO NOT reach your hand into the hood head cover in atmospheres containing air contaminants. Leave the contaminated area and 

clean hands before reaching inside the hood.

WarNiNg

CC20 Series airline respirator

User Manual

5

Warning

Summary of Contents for CC20 Series

Page 1: ...C20 Series respirators are approved by NIOSH for use with optional Bullard climate control devices Contact Bullard or its local authorized distributor for more information about these and other accessories for CC20 Series respirators All Bullard parts must be present and properly assembled to constitute a NIOSH approved respirator For technical assistance contact Bullard Technical Support at 877 B...

Page 2: ...able regulations N Never substitute modify add or omit parts Use only exact replacement parts in the configuration specified by the manufacturer O Refer to User s Instructions and or maintenance manuals for information on use and maintenance of these respirators S Special or critical User s Instruction and or specific use limitationa apply Refer to User s Instructions before donning TC PROTECTION1...

Page 3: ... V2025STSHUTOFF V2025ST V2010ST V2050ST V20100STSHUTOFF V20100ST V52535BLACK V55035BLACK V55033FS V55033GRN V52533FF V52533FS V52533 V55030GRN V55031 V55030 V55033 V55032 V52531 V52530 V52530GREEN V52532 V55033FF V5KF2530XXX V5KF2531XXX V5KF2532XXX V5KF2533XXX V5KF2535XXX V5KF5030XXX V5KF5031XXX V5KF5032XXX V5KF5033XXX V5KF5035XXX V5KF2533XXXFF V5KF2533XXXFS V5KF5033XXXFF V5KF5033XXXFS 20LCL 36501...

Page 4: ...n strap Headband Suspension or Head Protection Hard hat models C30 C30R S51 or S51R or suspension models 20TG and 20RT 20LFM 20LFL 20LF2S 20LF2M AND 20LF2L have sewn in elastic headband suspensions Breathing Tube for CC20 Respirators 20BT RTBT For 20TJ 20TIC 20TICH 20TICS 20SIC and 20SICH 20LFBT For 20LFM 20LFL 20LF2S 20LF2M 20LF2L 20LFBTXL For 20LFM 20LFL 20LF2S 20LF2M 20LF2L 20LFBTXS For 20LFM 2...

Page 5: ... according to the Flammable Fabrics Act Class 1 fabrics will burn and do not provide thermal protection if a fire or explosion should occur CC20 materials may create static electricity under low relative humidity Surface resistance and charge dissipation are proportional to the amount of antistatic agent on the fabric and the ambient relative humidity Since the antistatic agent is water soluble it...

Page 6: ...e applications including pharmaceutical manufacturing chemical and pesticide handling tank cleaning spray painting and other industrial or agricultural applications in which hazardous compounds are present The CC20 respirators are not approved for use in any atmosphere immediately dan gerous to life or health IDLH or from which the wearer cannot escape without the aid of the respirator IDLH is def...

Page 7: ...ecessary to provide CC20 Series respirators with a volume of air that falls within the required range of 6 15 cfm or 170 425 lpm Ref 42 CFR Part 84 Subpart J 84 150 Make sure you understand the information in the Breathing Air Pressure Table before using this respirator 1 Determine the type of air source you are using Column 1 then find your flow control valve climate control device Column 2 2 Be ...

Page 8: ...25 34 31 39 F35 F35B V5 25 50 1 2 12 18 19 23 F40 F40B F40S F41 F42 F43 F44 F47 V10 25 50 75 150 200 250 300 1 2 3 5 5 22 25 24 27 27 37 33 40 38 45 V5 25 50 1 2 22 26 25 30 AC100030 AC100030B AC100030S AC100031 AC100032 AC100033 AC100034 AC10035B AC100037 V10 25 50 75 150 175 300 2 3 5 55 65 60 70 65 75 V5 25 50 1 1 55 65 56 69 DC5040 DC5040B DC5040S DC5041 DC5042 DC5043 DC5044 DC5047 V10 50 75 1...

Page 9: ...ng the four pins into the sizing holes Figure 4 NOTE If using the optional 20RT ratchet headband suspension refer to the instruction sheet provided with the 20RT Adjust Crown Straps for Vertical Fit To improve suspension comfort adjust crown straps vertically by repositioning the crown strap posts in the crown straps Vertical adjustment makes the headband ride higher or lower on the wearer s head ...

Page 10: ...at about 1 4 up from the edge Apply shorter Velcro tab to the underside of the brim of the hard hat see Figure 7 5 Insert hard hat into respirator hood with cap visor facing front of hood see Figure 6 6 Tuck cap brim on top of front elastic Velcro band sewn into hood see Figure 7 7 Loop the Velcro strip sewn inside the hood around the back of the cap and affix it to the corresponding Velcro tab pr...

Page 11: ...ting facepieces have a sewn in breathing tube connector on the back The 20LFBT breathing tube has a special connector on the hood end with bayonet type pins 2 Insert the bayonet connector of the 20LFBT breathing tube in the hood connector and turn clockwise until it locks in place see Figure 12 Using Climate Control Devices for CC20 Series Airline Respirators CC20 Series Airline Respirators are ap...

Page 12: ... visor Pull the hood over your head and adjust the headband around your head and the elasticized edge of the faceseal under your chin Make sure that the breathing tube is not twisted after donning 8 Tuck inner bib of hood except on 20TJ 20TP 20LFM 20LFL 20LF2S 20LF2M and 20LF2L into shirt or protec tive clothing for additional splash and overspray protection see Figure 16 9 Pull respirator outer b...

Page 13: ...ge is detected replace immediately with Bullard replace ment part s or remove the respirator from service Cleaning Bullard does not recommend laundering the hood When the hood becomes dirty it should be discarded and replaced The respira tor s plastic lens headband suspension and optional chin strap should be hand sponged with warm water and mild detergent rinsed and air dried Mineral spirits may ...

Page 14: ...are fully inspect flow control valve climate control device for signs of damage If any signs of excessive wear are present replace the flow control valve climate control device or remove the respirator from service Air Supply Hoses Inspection Air supply hose s should be inspected closely for abrasions cor rosion cuts cracks and blistering Be sure the hose fittings are crimped tightly to the hose s...

Page 15: ...er lens no suspension Hood with inner bib for use with Bullard hard hat 20TICH Tychem QC hard hat not included 20SICH Tychem SL with taped and sealed seams hard hat not included Hood with inner bib and long outer bib for use with headband suspension 20TICS Tychem QC with taped and sealed seams and 20TG headband suspension 20TICSN Tychem QC with taped and sealed seams no headband suspension 20SIC T...

Page 16: ...hrader steel quick disconnect nipple X32 With 1 4 Snap Tite steel quick disconnect nipple X33 With 1 4 Snap Tite brass quick disconnect nipple Constant Flow Breathing Tube Assemblies For use with Bullard Free Air Pumps V35 With 1 2 Industrial Interchange steel Hansen compatible quick disconnect nipple X35 For 20LF and 20LF2 Series hoods with 1 2 Industrial Interchange steel Hansen compatible quick...

Page 17: ...ect nipple Hot Cold Tubes Adjustable Flow HC2400 With 1 4 Industrial Interchange steel Hansen compatible quick disconnect nipple HC240031 With 1 4 Schrader steel quick disconnect nipple HC240032 With 1 4 Snap Tite steel quick disconnect nipple Dual CooL Climate Control Device DC5040 With 1 4 Industrial Interchange steel Hansen compatible quick disconnect nipple Includes CH60 connector hose and nyl...

Page 18: ...pler and 1 4 male quick disconnect nipple V5KF2530XXX 25 7 6 m with 1 4 Industrial Interchange steel Hansen compatible fittings V5KF5030XXX 50 15 2 m with 1 4 Industrial Interchange steel Hansen compatible fittings V5KF2531XXX 25 7 6 m with 1 4 Schrader steel quick disconnect fittings V5KF5031XXX 50 15 2 m with 1 4 Schrader steel quick disconnect fittings V5KF2532XXX 25 7 6m with 1 4 Snap Tite ste...

Page 19: ...ontaminated materials Products suspected to be contaminated will be professionally discarded at the customer s expense 4 Ship returned products including those under warranty with all transportation charges pre paid Bullard cannot accept returned goods on a freight collect basis 5 Returned products will be inspected upon return to the Bullard facility Bullard Technical Support will telephone you w...

Page 20: ...ark of Velcro USA ISO 9001 certified Americas E D Bullard Company 1898 Safety Way Cynthiana KY 41031 9303 Toll free 877 BULLARD 285 5273 Tel 859 234 6616 Fax 859 234 8987 www bullard com Europe Bullard GmbH Lilienthalstrasse 12 53424 Remagen Germany Tel 49 2642 999980 Fax 49 2642 9999829 www bullardextrem com Asia Pacific Bullard Asia Pacific Pte Ltd LHK Building 701 Sims Drive 04 03 Singapore 387...

Page 21: ...21C 0922 PAPRFC3 Powered Air Purifying Respirator with OV AG HE Filter Cartridges for organic vapors chlorine hydrogen chloride sulfur dioxide chlorine dioxide hydrogen fluoride and particulates Approval No TC 23C 2765 PAPRFC4 Powered Air Purifying Respirator with AM FM MA AG HE Filter Cartridges for ammonia formaldehyde methylamine chlorine hydrogen chloride sulfur dioxide chlorine dioxide hydrog...

Page 22: ...r is provided to check that there is an adequate volume of air available to the wearer prior to use The system is designed to operate at a minimum air flow of approximately 7 cubic feet of air per minute 198 liters per minute in the hood under normal use on the standard speed setting and 8 5 cubic feet of air per minute 240 liters per minute in the hood under normal use on the high speed setting A...

Page 23: ...nd undamaged Inspect for deterioration physical damage and improper assembly 2 Filter Cartridges Inspect the filter cartridge for any physical damage Check the label to ensure the filter cartridge has not exceeded its use by date Inspect the gasket on the filter for any phsyical damage NOTE Each filter comes with a permanent gasket Ensure that the correct filter cartridge is appropriate for the co...

Page 24: ...ficiency Particulate OV Organic Vapor AM Ammonia CD Chlorine Dioxide CL Chlorine FM Formaldehyde HC Hydrogen Chloride HF Hydrogen fluoride MA Methylamine SD Sulfur Dioxide WARNING Use only the filter cartridge s described in the above table Do not change cartridges while in a hazardous atmosphere Incorrect cartridge selection will invalidate all performance statements and approvals for this equipm...

Page 25: ...er crown strap post Figure 18 NOTE If the hood rises off your head during use first verify proper air pressure then select a different hood for your application or use the optional chin strap Adjusting and Installing Hard Hat in Respirator Hood 20SICH 20TICH 1 Assemble and adjust the standard Bullard hard hat suspensions RS4PC or RS6PC or the optional ratchet suspensions RS4RC or RS6RC by followin...

Page 26: ...the neck cuff is down below the chin and that the air outlets of the cuff see Figure 27 are not restricted If the neck cuff is not below the chin then pull down before continuing See Figure 27 RT Series Hood Use Installing Breathing Tube Assembly in RT Series Respirator Hoods For hoods without a threaded port at the rear Breathing Tubes PA1BT PA1BTXS and PA1BTXL will attach to the hood with a clam...

Page 27: ...nd of breathing tube to blower unit if not already attached by screwing adapters together Remove any protective film covering the lens of the headpiece Put on the belt and blower assembly and make any final adjustments to the belt as necessary keeping the breathing tube and hood behind the head Turn the blower on by depressing and holding the on off switch Figure 33 for approximately 1 second indi...

Page 28: ...ELOW or PARTLY BELOW the PASS LINE with a fully charged battery the filter cartridges may need to be changed Doffing the Respirator Prepare to doff the blower battery and hood in a safe hazard free area and do the following in conjunction with your employer s standard operating procedures Remove the hood Turn the blower off by holding down the on off switch for 5 seconds This is confirmed by a lon...

Page 29: ...iency Particulate Air Filter for Powered Air Purifying Respirators OV Organic Vapor AM Ammonia CD Chlorine Dioxide CL Chlorine FM Formaldehyde HC Hydrogen Chloride HF Hydrogen Fluoride MA Methylamine SD Sulfur Dioxide RESPIRATOR COMPONENTS TC PROTECTION 1 ALTERNATE HOOD ASSEMBLIES ALTERNATE SUSPENSION HARD HAT AS SEMBLIES ALTERNATE BREATHING TUBES BLOWERUNITASSEMBLY FILTERASSEMBLY ALTERNATECARTRID...

Page 30: ...lasts so the above limitations or exclusion may not apply to you This warranty gives you specific Return Authorization The following steps must be completed before Bullard will accept any returned goods Please read carefully Follow the steps outlined below to return goods to Bullard for repair or replacement under warranty or for paid repairs 1 Contact Bullard Sales Support by telephone or in writ...

Page 31: ...ble bib hood for use without a headband suspension RT1 RT1T Tychem 2000 QC Inflatable neck collar RT2 RT2T Tychem 4000 SL Inflatable neck collar RT3 RT3T Tychem 2000 QC Sport neck collar RT4 RT4T Tychem 4000 SL Sport neck collar Accessory Items for Hoods 20LCL Mylar lens covers CC20 Series 25 pkg RTLC Mylar lens covers RT Series 25 pkg Headband Suspensions and Hard Hats 20TG Standard headband susp...

Page 32: ...1 859 234 8987 Europe Bullard GmbH Lilienthalstrasse 12 53424 Remagen Germany Tel 49 2642 999980 Fax 49 2642 9999829 Asia Pacific Bullard Asia Pacific Pte Ltd LHK Building 701 Sims Drive 04 03 Singapore 387383 Tel 65 6745 0556 Fax 65 6745 5176 2017 Bullard All rights reserved 6081509758G 0517 ISO 9001 certified www bullard com ...

Reviews: