QUICK START GUIDE
To set up a Plus-X device, please refer to the manual for
your specific Plus-X unit.
Once the Plus-X device is set up, use AutoLoad Plus
to add the Plus-X device to the ARC Plus SL. In the
AutoLoad Plus menu, select Edit->Plus-X Devices and
click “Add”. The dialog box shown below will be
displayed.
•
Select the type of Plus X device and enter its
network information.
Note:
If adding more than one Plus X device to an
ARC Plus, adjust the starting channel so that
other assigned channels are not overwritten.
•
Select OK to confirm the first Plus X device.
•
If adding more than one Plus X device, repeat
the same steps.
•
Save the configuration by selecting File>Save in
AutoLoad Plus.
To confirm that everything is communicating, log in to
the ARC Plus SL using the web browser. All assigned
channels should show their default values.
Note:
If the meter or status inputs show as offline or
a warning is displayed, check the network
configuration and ensure the configuration is
saved within AutoLoad Plus.
4
ADDING PLUS-X DEVICES
For information on configuring input and output channels and calibrating meter inputs, see the ARC Plus SL
Instruction Manual.
Connecting a Meter or Status Input
1. Connect your site equipment to the provided
push-on block connectors. Secure the wires with
the built-in setscrews. The status or metering
sample connects to the + terminal, and a common
ground connects to the – terminal.
2. Connect the push-on blocks to the rear panel of
the Plus-X device with the setscrews facing up. Be
sure to precisely align the connector terminals to
the + and – contacts on the back panel of the unit.
Connecting a Relay Output
1. Connect your site equipment to the provided
three-terminal push-on block connectors. Secure
the wires with the built-in setscrews. Connections
are standard, from left to right: common (C),
normally open (NO), and normally closed (NC).
2. Connect the push-on blocks to the rear panel of
the Plus-X device with the setscrews facing up.
Use care to properly align each terminal with the
contacts on the back panel of the unit.
5
CONNECTING STATUS, METERS AND RELAYS ON PLUS-X DEVICES
6
ADDING SNMP DEVICES
In order to use SNMP Manager functionality within ARC Plus SL,
an add-on SNMP Plus license is required. To add SNMP devices to
your ARC Plus SL, select Edit>SNMP Devices in the AutoLoad Plus
menu. The SNMP Devices dialog box shown below will be displayed,
allowing you to add, edit or delete entries in the ARC Plus SL SNMP
device list.
To add a new device, Click the “Add” button then assign a name
to the unit and enter the IP address in the dialog box shown below.
Browse to and select the MIB file for the new SNMP device. The
added unit will now show up in the list of SNMP Devices.
AutoPilot
®
and Jet
TM
Active Flowcharts Software Licenses
In order to manage multiple remote sites and create your own
Custom Views with features like group selection and editing,
autoscaling and embedded HTML5 web pages and RTSP cameras
an AutoPilot software license is required.
Jet Active Flowcharts, available as an extension of AutoPilot, makes
it easy to automate site control by drawing simple flowcharts
that describe how the remote control should respond to different
conditions.
Refer to the ARC Plus SL Instruction Manual for further information