METER ACTIONS
Meter Actions instruct the ARC Plus to automatically issue a command or run/stop a macro when a meter channel
crosses a limit. Each limit is individually configurable. In firmware versions prior to 5.0.8.1, the meter action is
executed immediately when the limit is crossed. In firmware version 5.0.8.1 or later, the meter action is executed
after the corresponding Alarm Delay, as configured on the Meter Alarms tab. See
Meter Actions Tab
To configure an action, navigate to the
Meter Actions
tab. Hover over
the cell
and click the […] button for the channel and limit that you
want to set. Select the type of action (raise, lower, run macro or stop
macro), and the target channel/macro.