niitt.. Enter the unit of measurement (i.e. volts, watts, amps, etc.) used by this metering channel (up to four
characters). The Voice Interface is able to recognize the following abbreviations and speak the full unit name:
%
%
Percent
A
AM
MP
PS
S Amps
D
DB
B
Decibels
D
DE
EG
G
Degrees
G
GA
ALL
Gallons
K
KV
V
Kilovolts
K
KW
W
Kilowatts
LLB
BS
S
Pounds
M
MA
A
Milliamps
M
MIIN
N
Minutes
M
MV
V
Millivolts
P
PO
OW
WR
R Power
S
SE
EC
C
Seconds
V
VLLT
TS
S
Volts
W
WA
AT
TT
T Watts
T
Ty
yp
pe
e.. Click in the Type field and use the drop down menu to select the type of metering this channel uses:
After you set up names, units and input types for your
channels, click the + sign to the left of the channel
number to set up limits and alarms, and to associate
events with those channel alarms.
LLiim
miittss.. You can set up four separate limit parameters for each channel (two lower limits and two upper limits),
allowing different alarms to be issued and actions to be taken depending on which limit has been exceeded.
Enter the limits in ascending order, according to the metering value:
S
Se
ecco
on
nd
d LLo
ow
we
err
The lowest limit value. Any meter reading at or below this value will cause the
alarm/action associated with the Second Lower limit.
FFiirrsstt LLo
ow
we
err
The higher of the two lower limits. When the monitored value reaches the First
Lower limit, the associated alarm/action is initiated until the value reaches the
Second Lower limit. If only one lower limit is needed, use the second lower limit, as
the system responds only to the second limit when both are exceeded. Leave the
first lower limit set to 0.
GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL
CHAPTER 4: I/O UNIT CONFIGURATION
36
0
0 tto
o 1
10
0
Allows an analog input of 0VDC up to +10VDC with the same ratio assigned for all
values in that range.
--5
5 tto
o +
+5
5
Allows an analog input of –5VDC to +5VDC with the same ratio assigned for all
values in that range.
LLiin
ne
ea
arr tto
o P
Po
ow
we
err
Allows an analog input to this channel of 0VDC up to +10VDC with an exponential
ratio calculated for all values in that range.
IIn
nd
diirre
ecctt P
Po
ow
we
err
Disables direct input to the channel. The displayed value is based on the input
values of the previous two channels. For example, the value of Channel 2 and the
value of Channel 3 are multiplied to give the value for Channel 4.
Summary of Contents for GSC3000
Page 8: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL viii ...
Page 22: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 14 ...
Page 32: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 24 ...
Page 40: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 32 ...
Page 52: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 44 ...
Page 68: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 60 ...
Page 120: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 112 ...
Page 128: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 120 ...
Page 132: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 124 ...
Page 140: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 132 ...
Page 144: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 136 ...