Commands
Set up your command (output) channels from the Commands tab.
M
Mo
od
de
e.. Use the drop-down menu in the Mode field to select
whether the output type is Momentary or Latching.
Momentary is for command signals that last for as long as
the specified duration setting. Select Latching if the
command signal stays active until changed by another
command. Latching command outputs ignore any duration
setting.
Note: If you change the mode from latching to momentary
while the latching command is active, the channel will remain
latched until a new command is issued on that channel.
Note: When you set a channel for latching, both the A and B
output for that channel must be configured as latching since
the two work in conjunction with each other. Similarly, if your
output is configured for momentary, both the A and B state
must be set for momentary even though the A and B states
work independently.
D
Du
urra
attiio
on
n.. In the Duration field, specify the amount of time the command output is to be active – anywhere from
0.1 to 25.5 seconds, definable in 1/10-second increments. Command channels A and B are mutually exclusive
(when channel B is active, channel A is inactive, and vice-versa).
A
A LLa
ab
be
ell // B
B LLa
ab
be
ell.. A and B labels correspond to A and B output channels on the Command Relay. Specify a label
to identify both command actions. These labels are displayed in the command buttons in the Lynx monitor view,
as well as in the drop-down menus you use during alarm/action setup. If you are using a Voice Interface,
command labels will also be announced during a voice session.
Timed Events
Use the Timed Events tab to schedule activities at your site.
The GSC3000 and VRC2500 can perform data captures,
commands and macros on the schedule you determine here.
Events saved to one I/O can involve actions on any I/O unit
at the same site.
T
Tiim
me
e.. Click the Time field, followed by the drop-down arrow
that appears, for a pop-up dialog allowing you to set the
schedule for this action.
In the Date area, choose whether the event will occur Every
Day, on one Specific Weekday, or on one Specific Day of the
Month, and choose the day within the week or month as
appropriate. For the Month field, indicate whether this event
will occur Every Month or during one Specific Month. In the
Time area, select whether this event will occur Every Hour,
Every Minute, or Every Second on the specified day(s), or
designate the Specific Time for the event to take place.
CHAPTER 4: I/O UNIT CONFIGURATION
39
CUSTOMER SUPPORT: 978-486-3711 • support@burk.com • www.burk.com
Summary of Contents for GSC3000
Page 8: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL viii ...
Page 22: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 14 ...
Page 32: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 24 ...
Page 40: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 32 ...
Page 52: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 44 ...
Page 68: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 60 ...
Page 120: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 112 ...
Page 128: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 120 ...
Page 132: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 124 ...
Page 140: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 132 ...
Page 144: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 136 ...