26 - 8625-2 Standard
english
increase digit
next digit
2 s
set decimal point
Î
Select the reset time T
N
in a range from 0.1 to 200.1 sec (works setting:
0.50).
Higher values result automatically in the display 0.1 and a value within the
range must be entered.
6.6.5
INTG
- setting the reset time T
N
The reset time T
N
is the time that is needed to obtain the same magnitude of
change in the controller output with the I fraction as occurs with the P fraction.
Fig.: Setting the reset time T
N