52
General settings - Parameter
Type 8098
10.6.4
Deactivating the device internal termination resistor
If the device is not installed at the end of büS or of a CANopen fieldbus, deactivate the device internal ter
-
mination resistor.
Max. 2 120
W
termination resistors can equip büS or a CANopen fieldbus.
To deactivate the device internal termination resistor, do the following:
→
Select the device in the navigation area.
→
General settings
→
Parameter
→
büS
Advanced
→
Termination resistor
→
Off
The internal 120
W
termination resistor is deactivated.
10.6.5
Changing the address of the device connected to a CANopen
fieldbus
The address of the device is used by büS or the CANopen fieldbus the device can be connected to.
•
If the device is connected to büS, büS automatically addresses the device. By default, the address of the
device on büS is 30.
• If the device is connected to a CANopen fieldbus, the addresses are not set automatically.
→
Make sure that each participant, including the device, connected to the CANopen fieldbus has a specifc
address.
If the device is connected to a CANopen fieldbus and another participant connected to the fieldbus has the
same address, do the following to change the address of the device:
→
Select the device in the navigation area.
→
General settings
→
Parameter
→
büS
Advanced
→
büS address
→
Change the address of the device. Make sure you enter an address that is not already used on the same
CANopen fieldbus.
The address of the device is changed.
→
Start the device to take the new address into account. See chpt.
English