7
→
Insert the Ethernet cable into the sockets of the X1 and X2 interfaces.
The X1 and X2 interfaces for RJ45 plug-in connectors are equivalent.
note!
To ensure electromagnetic compatibility (EMC)
▶
Only use shielded Ethernet cables.
▶
Connect the Ethernet cables of all devices to the top hat rail to
ground the cable shielding.
5.3.1
CC-Link version
Configuration of plug-in connector D-Sub, 9-pin
D-Sub, 9-pin
Pin
Signal
Function
Connection
1
2
6
3
7
4
8
5
9
1 and 2
not used
3
DA
Data line minus
(A conductor)
Mandatory
4
DG
Data ground
Mandatory
5, 6 and 7 not used
8
DB
Data line plus
(B conductor)
Mandatory
9
not used
Fig. 3:
CC-Link, Configuration of plug-in connector D-Sub, 9-pin
5.3.2
PROFIBUS version
Configuration of plug-in connector D-Sub, 9-pin
D-Sub, 9-pin
Pin
Signal
Function
Connection
1
2
6
3
7
4
8
5
9
1 and 2 not used
3
RxD/TxD-P
Data line minus
(A conductor)
Mandatory
4
CNTR-P
Repeater direc-
tional control
Optional
5
DGND
Ground for bus
terminating
resistor
Optional
6
VP
+5 V supply for
bus terminating
resistor
Optional
7 and 9 not used
8
RxD/TxD-N
Data line plus
(B conductor)
Mandatory
Fig. 4:
PROFIBUS, Configuration of plug-in connector D-Sub, 9-pin