11
Technical data
Type 8025/8035 /
part
material
Housing
• 8025, compact or remote
versions
• 8025, wall-mounted versions
• 8035
• PC
• ABS
• PC
Cover
• 8025 compact versions or
8035
• 8025 panel versions
• 8025, wall-mounted versions
• PC (Cover with lid)
• PC
• ABS
Front foil
Polyester
Screws (4)
Stainless steel
Male fixed connector and
female connector (type 2508)
PA
Cable glands
PA
6.5.
electrical data
Power supply 12-36 V DC
• filtered and regulated
• SELV circuit (safety extra low
voltage), with a safe energy
level
• oscillation rate: ±10 %
Power supply (not supplied)
• limited power source
according to § 9.3 of
EN 61010-1 standard
• or class 2 source according
to UL 1310/1585 and
EN 60950-1 standards
Power supply 115/230 V AC
• frequency
• supplied voltage
• current
• integrated protection
• power
• 50/60 Hz
• 27 V DC, regulated
• max. 250 mA
• 250 mA time-delay fuse
• Compact version: 6 VA
• Wall-mounted version 3 VA
Current consumption (without the
consumption of the 4-20 mA output)
• 12-36 V DC version with relays
• 12-36 V DC version without
relays
• 115/230 V AC compact version
• 115/230 V AC wall-mounted
version
• 70 mA max. (at 12 V DC)
• 25 mA max. (at 12 V DC)
• 125 mA max. (at 27 V DC)
• 250 mA max. (at 27 V DC)