26
Wiring
Type 8025/8035 /
Table 3: Positioning of the Source / Sink selector depending on
the wiring of the current output of a version with relays
Wiring the 4-20 mA output position of the source/sink
selector on a version with relays
Not wired (jumper wire in
place)
SOURCE
Sourcing mode
SOURCE
Sinking mode
SINK
8.3.3. 115/230 V Ac selector
The 115/230 V AC selector makes it possible to configure the
supply voltage of the device in a 115/230 V AC version.
230V
115V
→
Energize the
device with
a 230 V AC
voltage.
→
Energize the
device with
a 115 V AC
voltage.
Fig. 20: Selector of the supply voltage on a 115/230 V AC version
8.4.
Wiring the 8025 in compact
version and the 8035, with or
without relays, with cable glands
8.4.1. Wiring instructions
Seal the unused cable gland using the stopper gasket sup-
plied to make sure the device is tight.
→
Unscrew the nut of the cable gland.
→
Remove the transparent disc inside the cable gland.
→
Insert the stopper gasket.
→
Screw the nut back.
→
Lift the transparent lid after having unfastened the screw.
→
Untighten the 4 screws then remove the cover from the device.
→
For the versions with relays, insert the cable clip.
Supply
12..36Vdc
FLOW SENSOR
COIL
NPN
SOURCE SINK
L+
L-
PE
P-
P+
NC
L+
L-
PE
P-
P+
Iout
PULSE
OUTPUT
Without
With
Relays
PE