66
Maintenanceandtroubleshooting
red
leD
current
output
transistor
output
icon message
displayed in the
info menu
possible cause
recommended action
ON
22 mA
1)
depending
on
thresholds
ERR
+
"E:Temperature" The fluid temperature is
out of range.
The message is
displayed if the
monitoring of the fluid
temperature has been
activated, depending on
the set thresholds ERR
LO and ERR HI (see
chpt. 9.13.4).
→
Go into the "Sensor"
function of the
Diagnostic menu to
read the measured
fluid temperature
(chpt. 9.13.4).
→
If necessary, check
whether the built-in
Pt1000 is working
correctly by measuring
a fluid with a known
temperature,
→
If the Pt1000 is faulty,
return the device to
Bürkert,
→
If the Pt1000 is not the
cause of the problem,
check the process.
1)
if the MODE DIAG function of the “Output.AC1” or “Output.AC2” menu is set to “22 mA” (see chpt. 9.11.9); else, the
current output delivers a standard current between 4 and 20 mA
English
Type 8222 ELEMENT