109
Auxiliary functions
Type 8792, 8793 REV.2
•
Safepos
- Outputting the message: Actuator in safety position
•
ERR.SP/CMD
- Outputting the message: Sensor break for process set-point value/set-point position
Only available if the function in the
SIG.ERR
menu has been activated (
SIG.ERR
→
SP/CMD input
→
Error on).
See chapter “26.2.12. SIG.ERROR – Configuration of signal level fault detection”.
•
ERR.PV
- Outputting the message: Sensor break for process actual value (for Type 8793 only)
Only available if the function in the
SIG.ERR
menu has been activated (
SIG.ERR
→
PV Input
→
Error on).
See chapter “26.2.12. SIG.ERROR – Configuration of signal level fault detection”.
•
Remote
- Output AUTOMATIC / MANUAL operating state
•
Tune.Status
- Output TUNE (process optimization)
Specify the output as follows:
→
/ Select
suboptions
.
(Safepos, ERR.SP/CMD, ERR.PV, Remote
or
Tune.Status).
→
Select
SELEC
. Acknowledge submenu option as output function for the digital output. The
selection is marked by a filled circle .
Then set the required switching status in the
OUT.type
submenu.
You have specified the output.
•
DIAG.State-1/2
- Diagnostic output (option)
Outputting the message: Diagnostic message from selected status signal
For description see chapter “26.2.22. DIAGNOSE – Menu for monitoring valves (option)”.
Enter the
OUT.type
as follows:
→
/ Select
DIAG.State-1/2
.
→
Select
SELEC
. The status signals, which can be activated for outputting the message, are
displayed.
→
/ Select
status signal
. Select the status signal which is to be assigned to the diagnostic output.
→
Select
SELEC
. Activate the selection by checking the box or deactivate it by unchecking the
box .
→
If required, activate further status signals for the diagnostic output by pressing the / and
SELEC
keys.
→
Select
EXIT
. Acknowledgment and simultaneous return to the
OUT BIN 1/2
menu.
Then set the required switching status in the
OUT.type
submenu.
You have entered
OUT.type
.
english