134
Auxiliary functions
Type 8792, 8793 REV.2
Display
TRAVEL.ACCU
Description of the functions
EXIT
INPUT
29-6-1
TRAVEL.ACCU
HUB
LIMIT
NEXT.M
HISTORY
1000000 cm
999954 cm
20.0 mm
The
HUB
submenu specifies the total stroke of the actuator piston. The
total stroke is automatically determined during the basic setting of the
device (running
X.TUNE)
.
In the case of an analog position sensor, the total stroke must be entered
by pressing the
INPUT
key.
The interval for outputting the message can be changed in the
LIMIT
submenu. A piston movement which covers 10 km has been preset at the
factory.
After
NEXT.M
the remaining piston movement distance is displayed until
the next message appears.
The history entries of the last 3 messages can be viewed and deleted in
the
HISTORY
submenu.
Table 44:
TRAVEL.ACCU; path accumulator
Specify the interval for outputting messages as follows:
→
/ Select
TRAVEL.ACCU
.
(To do this, the
TRAVEL.ACCU
function must be incorporated into the
DIAGNOSE
main menu.
See chapter “16.1.24.3. Activation of diagnostic functions”).
→
Select
ENTER
. The menu is displayed.
* Required for analog position sensor only (setting the
HUB
submenu)
→
/ Select
HUB
.
→
Select
INPUT
*. The preset value is displayed.
→
/
+
Increase value
<-
Changing the decimal place
Setting total stroke of the actuator piston.
→
/ Select
LIMIT
.
→
Select
INPUT
*. The preset value is displayed.
→
/
+
Increase value
<-
Changing the decimal place
Setting interval for outputting the message (limit for sum of the piston movement).
→
Select
OK
. Return to the
TRAVEL.ACCU
menu.
→
Select
EXIT
. Return to the
DIAGNOSE
main menu.
You have specified the
interval for outputting messages.
english