79
Basic setting of the process controller
Type 8792, 8793 REV.2
If the submenu is left by pressing the left selection key
ESC
, the value remains unchanged.
15.3.5
X0
– Operating point of the process controller
The operating point corresponds to the operating point of the proportional portion when control difference = 0.
Factory setting: 0.0%
Enter the parameters as follows:
→
/ Select
PID.PARAMETER
.
→
Select
ENTER
. The menu for parameterizing the process controller is displayed.
→
/ Select
menu option
.
→
Select
INPUT
. The input screen is opened.
→
/
+
Increase value and
-
reduce value
Set value at
X0 0.0%
→
Select
OK
. Return to
PID.PARAMETER.
→
Select
EXIT
. Return to
P.CONTROL.
→
Select
EXIT
. Return to the main menu (MAIN).
→
Select
EXIT
. Return to
P.CONTROL.
Switching from setting level
process level.
You have set the parameter.
If the submenu is left by pressing the left selection key
ESC
, the value remains unchanged.
15.3.6
FILTER
– Filtering of the process actual value input
The filter is valid for all process actual value types and has a low-pass behavior (PT1).
Factory setting: 0
Enter the parameters as follows:
→
/ Select
PID.PARAMETER
.
→
Select
ENTER
. The menu for parameterizing the process controller is displayed.
→
/ Select
menu option
.
→
Select
INPUT
. The input screen is opened.
→
/
+
Increase value and
-
reduce value
Set value at
FILTER 0
→
Select
OK
. Return to
PID.PARAMETER.
→
Select
EXIT
. Return to
P.CONTROL.
english