13
5 Connecting to power supply
LEVEL SWITCH 8110 • - contactless electronic switch
41765-EN-140211
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
•
Connect only in the complete absence of line voltage
The instrument is connected with standard two-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Use cable with round cross section. Depending on the plug connec-
tion, you have to select the outer diameter of the cable respectively so
that the seal effect of the cable gland is ensured.
•
Valve plug ISO 4400, ø 4.5 … 7 mm
•
Valve plug ISO 4400 with IDC crimping technology, ø 5.5 … 8 mm
Use cable with a round wire cross section and tighten the cable gland.
When mounting outdoors, on cooled vessels or in moist areas in
which cleaning is made with steam or high pressure, the sealing of
the cable gland is very important.
5.2 Wiring plan
2
1
2
Fig. 7: Overview of the connection versions
1 Valve plug ISO 4400
2 Valve plug ISO 4400 with IDC method of termination
Note safety instructions
Connection cable
Cable glands
Housing overview
Summary of Contents for LEVEL SWITCH 8110
Page 1: ...Operating Instructions LEVEL SWITCH 8110 contactless electronic switch...
Page 28: ...The smart choice of Fluid Control Systems www burkert com 41765 EN 140211...
Page 29: ...Bedienungsanleitung LEVEL SWITCH 8110 kontaktloser Schalter...
Page 57: ...29 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 58: ...30 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 59: ...31 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 60: ...The smart choice of Fluid Control Systems www buerkert com 41765 DE 140211...
Page 61: ...Mise en service LEVEL SWITCH 8110 sortie lectronique statique...
Page 88: ...The smart choice of Fluid Control Systems www burkert com 41765 FR 140211...