7 Maintenance and fault rectification
LEVEL SWITCH 8110 • - contactless electronic switch
41765-EN-140211
7 Maintenance and fault rectification
7.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
7.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
LEVEL SWITCH 8110 offers maximum reliability. Nevertheless, faults
can occur during operation. These may be caused by the following,
e.g.:
•
Sensor
•
Process
•
Voltage supply
•
Signal processing
The first measure to be taken is to check the output signal. In many
cases, the causes can be determined this way and the faults rectified.
Error
Cause
Rectification
Green signal
lamp off
Voltage supply in-
terrupted.
Check the voltage supply and the ca-
ble connection
Electronics de-
fective
Exchange the instrument or send it in
for repair
Red signal lamp
lights (switching
output high-im-
pedance)
Error with the
electrical con-
nection
Connect the instrument according to
the wiring plan
Shortcircuit or
overload
Check the electrical connection
Red signal lamp
flashes (switching
output high-im-
pedance)
Virbating fre-
quency out of
specification
Check the vibrating element on build-
up and remove it
Buildup on the vi-
brating element
Check the vibrating element and
the sensor if there is buildup and re-
move it
Vibrating element
damaged
Check if the vibrating element is dam-
age or extremely corroded
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Set up
" may have to be carried out again.
Reaction when malfunc-
tions occur
Failure reasons
Fault rectification
Checking the switching
signal
Reaction after fault recti-
fication
Summary of Contents for LEVEL SWITCH 8110
Page 1: ...Operating Instructions LEVEL SWITCH 8110 contactless electronic switch...
Page 28: ...The smart choice of Fluid Control Systems www burkert com 41765 EN 140211...
Page 29: ...Bedienungsanleitung LEVEL SWITCH 8110 kontaktloser Schalter...
Page 57: ...29 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 58: ...30 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 59: ...31 Notizen LEVEL SWITCH 8110 kontaktloser Schalter 41765 DE 140211...
Page 60: ...The smart choice of Fluid Control Systems www buerkert com 41765 DE 140211...
Page 61: ...Mise en service LEVEL SWITCH 8110 sortie lectronique statique...
Page 88: ...The smart choice of Fluid Control Systems www burkert com 41765 FR 140211...