A suitably qualified and competent engineer such as a Gas safe/ACS Registered Installer must 
carry out all the maintenance operations discussed in this section at least once a year.  
In the case of seasonal servicing, it is recommended that the service operations be carried out at 
the end of each heating season.  
In the case of continuous operation, the service operations should be carried out every six months.  

 

 

 

Before removing the burner from the appliance: 

 

1.  Ensure you have a replacement burner mounting gasket for re-fitting the burner afterwards. 
2.  Prepare an appropriately sized and relatively clean and tidy work area to conduct the 

maintenance operation.

 

 

7.1

 

Service Inspection 

 

Isolate and disconnect both the gas and electrical supplies from the burner. 
Supporting the weight of the burner, carefully remove the fixings securing it to the appliance and 
withdraw it from the chamber.  

 
7.1.1 

The condition of the burner head 

some discolouration of the burner material is normal, but the material should not be cracked or 
open. Under no circumstances should any of the perforated holes in the burner tube beneath the 
material be visible. Inspect the flange of the burner for any signs of cracking or severe overheating, 
which may indicate leakage.  
Any serious burner head defect would constitute an ‘

Immediate Danger’

 and the burner system 

SHOULD NOT

 be put back into operation until adequately repaired. 

 

7.1.2 

The condition of the electrodes 

Check the ceramics are not cracked or damaged and check that the wire head is still approximately 
4mm gap between the Ignition electrode and the burner surface. 

 

 

DO NOT 

clean the electrodes and if adjustment is required always try and adjust the wires near to 

the ceramic

 

and preferably using a blowtorch to pre-heat the wire.  

 
7.1.3 

The condition of the electrical circuits 

Check the condition and integrity of the internal burner wiring harness and plugs, ensuring that all 
connections are secure. Check that both the ignition and detection leads are in good condition. 

Summary of Contents for Inverterjet 50M

Page 1: ...rs Ltd INSTALLATION SERVICE USER MANUAL Inverterjet Burner Series Ultra Low NOx Burners MODEL PRODUCT CODE CLASS Inverterjet 50M 91320 Modulating Pre mix Burner Inverterjet 90M 91323 Modulating Pre mi...

Page 2: ...l Installation 12 4 5 Basic Electrical Safety 12 4 5 1 Burner Wiring Diagrams Inverterjet 50 M 90 M 13 5 Commissioning 14 5 1 Commissioning procedure 14 5 1 1 Turning on the Burner 15 5 1 2 Commission...

Page 3: ...cal Wiring Diagram in this burner manual For Burner Installation Operation advice please call Burnertech Technical on 0044 0 1204 393222 To ensure maximum product reliability we advise and request tha...

Page 4: ...Installation Service User Manual BURNERTECH 3...

Page 5: ...3 Installation Before connecting the burner make sure that the burner rating matches the appliance requirements and that both gas and electrical services are adequately rated The burners are designed...

Page 6: ...manufacturer s instructions as detailed in this manual Always ensure that inlet or exhaust grilles are unobstructed and filters cleaned regularly The Maximum operating conditions for the Gas Valve an...

Page 7: ...Nominal Voltage Range VAC 120 230 120 230 Frequency Hz 50 60 50 60 Phase 1 1 Fan Current Draw Max A 1 9 1 9 Gas Connection 1 2 BSP 1 2 BSP Gas Pressure Min Max mbar 10 60 10 60 3 2 Technical Descript...

Page 8: ...dimensions and weight The diagrams below show the major dimensions and weight of the burner MODEL A B C D1 D2 H L W Weight mm mm mm mm mm mm mm mm kg Inverterjet 50 M 92 71 91 101 6 170 244 365 238 5...

Page 9: ...pending on parameter setting 0 10 V control a DC voltage between zero and ten volts can be applied to connector X3 Pins 8 16 At zero volt the fan will run on Minimum Fan speed At ten volt the fan will...

Page 10: ...Installation Service User Manual BURNERTECH 9 3 4 2 2 Lock out reset The Control can be reset by depressing the internal external reset button 4 Installation 4 1 General Installation Information...

Page 11: ...r the burner Mounting Plate Appropriate dimensions are shown below When installing the burner please be sure to use the gasket provided for sealing and insulating between the Mounting Plate and the be...

Page 12: ...front of the Gas connection flange at the rear of the burner 2 Check the thread on the flange and ensure that there is no debris in the threads 3 Connect the corresponding gas pipe fittings to the Ga...

Page 13: ...Installation Service User Manual BURNERTECH 12 4 4 Electrical Installation The electrical wiring diagram for the Burners are shown in the following page 4 5 Basic Electrical Safety...

Page 14: ...Installation Service User Manual BURNERTECH 13 4 5 1 Burner Wiring Diagrams Inverterjet 50 M 90 M X3 Microfit X2 Communication see note X1 Minifit...

Page 15: ...e ventilation is available for the safe operation of the burners 4 Establish that the system pipe work is complete full purged and adequate system load and circulation exists to facilitate firing of t...

Page 16: ...adings are within the required tolerance and if an appropriate gas meter is available to conduct a heat input measurement whilst operating at maximum rate to ensure the rate is within 5 of that requir...

Page 17: ...1500 rpm Ignition 30 5 1 3 1 Fan speed adjustment The following flowchart Fan speed control flowchart shows how the fan speed is controlled during a complete burner sequence The basic states are Stan...

Page 18: ...Installation Service User Manual BURNERTECH 17 Flow chart fan speed...

Page 19: ...Installation Service User Manual BURNERTECH 18 6 User Instructions 6 1 Limitations on use of Burner...

Page 20: ...fan to a pre set ignition speed The ignition spark is generated at this point and the Burner will ignite If satisfactory ignition takes place the burner will remain alight and the fan speed will modu...

Page 21: ...m the chamber 7 1 1 The condition of the burner head some discolouration of the burner material is normal but the material should not be cracked or open Under no circumstances should any of the perfor...

Page 22: ...Electrodes Inspect the ignition and flame electrodes if extensive signs of damage are detected they must then be removed and replaced Fan The fan is not a serviceable component Simply ensure it is pos...

Page 23: ...ty times are constantly compared etc Any violation of programmable limits and or internal thermostat functions will lead to an error fault or warning condition Severe error will cause a lockout condit...

Page 24: ...d fan speed is not within 900 RPM of the requested fan speed in 20 seconds error will be generated FAULT 8 Flame circuit error during normal operation of the ignition controller flame circuit is regul...

Page 25: ...red a Windows based software along with a dedicated USB cable and driver is available to enable programming of certain parameters in the control and also to read fault codes etc An example screenshot...

Page 26: ...Installation Service User Manual BURNERTECH 25 7 3 4 Maintenance Notes...

Page 27: ...Installation Service User Manual BURNERTECH 26...

Page 28: ......

Reviews: