10
I. Product Description, Specifications and Dimensional Data
(continued)
Table 2a: rating Data - Models aPX399, aPX500 and aPX800 (0 to 5000 Feet Elevation above Sea Level)
Table 2B: rating Data - Models aPX399, aPX500 and aPX800 (5001 to 10000 Feet Elevation above Sea Level)
apex Series gas-Fired Boilers
Model
number
input (MBH)
* Output
(MBH)
net aHri
ratings Water
(MBH)
Thermal
Efficiency
(%)
Combustion
Efficiency (%)
Boiler Water
Volume (gal.)
Heat Transfer
area
(Sq. Ft.)
Min.
Max.
APX399
80
399
375
326
94.1
94.5
3.4
41.8
APX500
100
500
475
413
95.0
95.0
4.2
50.8
APX800
160
800
760
661
95.0
93.0
5.0
65.3
notes:
* Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI
Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from
Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800)
Maximum Allowable Temperature, Water - 210°F
APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be field adjusted for LP
gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
apex Series gas-Fired Boilers
Model
number
input (MBH) * Output
(MBH)
net aHri
ratings
Water (MBH)
Thermal
Efficiency
(%)
Combustion
Efficiency (%)
Boiler Water
Volume
(gal.)
Heat Transfer
area
(Sq. Ft.)
Min. Max.
APX399
80
399
375
328
94.1
94.5
3.4
41.8
APX500
167
500
475
413
95.0
95.0
4.2
50.8
APX800
267
800
760
661
95.0
93.0
5.0
65.3
notes:
* Gross Output
Maximum Allowable Working Pressure, Water - 160 PSI
Safety Relief Valve Pressure, Water - 50 PSI Shipped from Factory (std.) (APX399 and APX500); 60 PSI Shipped from
Factory (std.) (APX800); 80 PSI and 100 PSI - optional (APX399, APX500 and APX800)
Maximum Allowable Temperature, Water - 210°F
APX399 and APX500 Boiler models are factory shipped as Natural Gas builds and have to be field adjusted for LP
gas application. Refer to ‘System Start- Up Section of this manual for detailed procedure.
APX800 Boiler Model is factory shipped as either Natural Gas build or LP gas build.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet,
ratings should be reduced at the rate of two and half percent (2.5%) for each 1000 Feet above sea level.
ii. Unpacking Boiler
CaUTiOn
Do not drop boiler.
A.
Move boiler
to approximate installed position.
B.
Remove
all
crate fasteners.
C.
Lift and remove
outside container.
D.
Remove boiler
from cardboard positioning sleeve on
shipping skid.
Warning
installation of this boiler should be undertaken
only by trained and skilled personnel from a
qualified service agency.
E.
Move boiler
to its permanent location.
Summary of Contents for Apex APX399
Page 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Page 66: ...66 VIII Electrical continued ...
Page 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Page 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Page 116: ...116 XIII Repair Parts continued ...
Page 118: ...118 XIII Repair Parts continued ...
Page 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...