Warning
Follow installation instructions included by the original polypropylene venting component manufacturers,
M&g/DuraVent or Centrotherm, whichever applicable.
Flexible Polypropylene Vent must be installed in an UnUSED chimney. a chimney, either single or
multiple flue type, is considered UNUSED when none of the flues is being used for any appliance
venting.
Where one of the multiple flues is being used for an appliance venting, the flexible vent installation is
not permitted thru any of adjacent flues.
Observe all precautions outlined in either M&g/DuraVent or Centrotherm instructions in addition to
those outlined in these instructions.
Examine all components for possible shipping damage prior to installation.
Proper joint assembly is essential for safe installation.
The venting system must be free to expand and contract and supported in accordance with installation
instructions included by the original polypropylene venting component manufacturers, M&g/DuraVent
or Centrotherm, whichever applicable.
Do not mix vent components or joining methods for different vent systems.
Where a conflict arises between M&G/DuraVent or Centrotherm instructions and these instructions, the
more restrictive instructions shall govern.
Do not apply thermal insulation to vent pipe and fittings.
Do not obtain combustion air from within the building.
Figure 15: Flexible Vent in Masonry
Chimney with Separate air intake
iV. Venting
C. Polypropylene Venting (continued)
Venting of Other Appliances (or Fireplace)
into Chase or Adjacent Flues Prohibited!
Summary of Contents for Apex APX399
Page 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Page 66: ...66 VIII Electrical continued ...
Page 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Page 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Page 116: ...116 XIII Repair Parts continued ...
Page 118: ...118 XIII Repair Parts continued ...
Page 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...