32
ii.
Combustion Air Termination
• After penetrating wall, install a 90°
elbow so that the elbow leg is in the up
direction.
• Install maximum vertical run of seven (7)
feet of combustion air pipe. See Figure
11.
• At top of vent pipe length install another
90° elbow os that the elbow leg is
opposite the building’s exterior surface.
• Install Rodent Screen (not supplied) and
horizontal vent terminal.
• Brace exterior piping if required.
5.
Vertical Vent Termination
a. Standard Two-Pipe Termination
Refer to Figures 12 and 13.
i.
Vent Termination
• Use the terminal supplied by the vent
system manufacturer shown in Table
11B. Follow manufacturer’s instructions
to attach terminal to vent system.
ii.
Combustion Air Termination
• Install vertical combustion air terminal.
Vertical combustion air terminal consists
of an 180° bend (comprised of two (2)
90° elbows) as shown in Figure 12.
• Install rodent screen (not supplied) in the
combustion air terminal. Use a screen
having 1/2” (2 x 2) or larger mesh.
E.
Concentric Polypropylene Venting
1. Vent Length Restrictions
a. Vent length restrictions are based on equivalent
length of vent pipe i.e. total length of straight
pipe plus equivalent length of fittings. See
Table 12 for specified vent length details. Do
not exceed maximum vent length. Table 13
lists available concentric vent components and
includes equivalent vent length for fittings.
b. The vent termination location is restricted as per
‘General Guidelines’, Paragraph A, 5 (refer to
Figure 4).
2.
Field Installation of Boiler Concentric Vent
Collar
a. Locate and remove six mounting screws from the
Miscellaneous Parts Carton.
b. Position the Collar onto jacket combination rear/
bottom panel and insert collar inner stainless
steel vent pipe into the heat exchanger vent
outlet.
iV. Venting
D. Stainless Steel Venting (continued)
Table 12: Concentric Vent Length
Boiler
Model
inner/Outer
Pipe Dia., mm
Vent Length
(Equiv. Ft.)
Wall Opening
Diameter
Minimum * Maximum
APX399 100/150 mm
32 in.
60
6-1/2 in
APX500 100/150 mm
32 in
APX800
N/A
N/A
N/A
N/A
* with optional concentric vent components, see Table 13 for details.
Table 13: Concentric Vent Components (applicable to aPX399 and aPX500 only)
Part number
Component Description
Size
Component
Equivalent Vent
Length, Ft
Comments
101548-01
90° Elbow – Long Radius
100/150 mm
8.0
101549-01
45° Elbow - Long Radius
100/150 mm
3.0
101550-01
1 Cut -To-Length Extension, 500 mm (19-1/2”)
100/150 mm
1.63
** Can be cut
101551-01
Cut -To-Length Extension, 1000 mm (39”)
100/150 mm
3.25
** Can be cut
101553-01
Fixed Extension, 2000 mm (78”)
100/150 mm
6.5
*** Must not be cut
101809-01
Horizontal (Wall) Terminal
100/150 mm
* NA
Supplied with boiler
101557-01
Vertical (Roof) Terminal
100/150 mm
* NA
See Note 1
101558-01
Flat Roof Flashing
100/150 mm
101559-01
Sloped Roof Flashing
100/150 mm
See Note 2
101560-01
Support Elbow with Chimney Chase Bracket
100/150 mm
10.0
See Note 3
101561-01
Hanger Wall Bracket
100/150 mm
notes:
* NA – do not include vent terminal into total vent length calculations.
** These sections have plain male end and beaded female end. See Figure 18 for details.
*** These sections have beaded male end and beaded female end. See Figure 19 for details.
1. Vertical terminal can be used with either of the roof flashings listed beneath it.
2. Sloped roof flashing suitable for roof angles between 25° and 45°.
3. Used at base of vertical run inside unused masonry chimney.
Summary of Contents for Apex APX399
Page 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Page 66: ...66 VIII Electrical continued ...
Page 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Page 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Page 116: ...116 XIII Repair Parts continued ...
Page 118: ...118 XIII Repair Parts continued ...
Page 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...