background image

A.

  Intermittent Circulator Operation

1.

 

ROOM THERMOSTAT CLOSES

2.  CIRCULATOR MOTOR ENERGIZED

a.  As the thermostat closes its contacts, a low 

voltage circuit (24V.) is completed to the bimetal 

heater in the circulator relay (24A51).  After 

a time delay of 15 seconds, the main contacts 

(120V.) of the circulator relay close to start the 

circulator.

3.   HEATING ELEMENT #1 ENERGIZED 

a.  Simultaneous with the completing of the circuit 

for the circulator relay, two additional circuits 

are completed.  

b.  The first circuit is for the Heating Element 

Relays which pull in immediately and the 

second is for the bimetal heater in the #1 Heating 

Element Sequencer (24A54).  

c.  These two circuits will be energized only if the 

boiler is not “OFF” on limit.  

d.  After a time delay of 45 seconds (30 seconds 

after the circulator has started) the main and 

auxiliary contacts of the #1 Sequencer close; 

the main contacts (240V.) energizing heating 

element #1 and its pilot light (located at the 

bottom of the side panel), the auxiliary contacts 

(24V.) energizing the bimetal heater in the #2 

Heating Element Sequencer.

4.   HEATING ELEMENT #2 ENERGIZED 

a.  45 seconds after bimetal heater in #2 Heating 

Element Sequencer is energized, its main 

contacts (240V.) and auxiliary contacts close; 

the main contacts energizing heating element #2 

and its pilot light (3

rd

 lowest in the boiler), the 

auxiliary contacts (24V.) energizing the bimetal 

heater in the #3 Heating Element Sequencer.

5.   HEATING ELEMENT #3 ENERGIZED 

a.  45 seconds after bimetal heater in the #3 Heating 

Element Sequencer is energized, its main 

contacts and auxiliary contacts close; the main 

contacts (240V.) energizing heating element #3 

and its pilot light (2

nd

 lowest in the boiler), the 

auxiliary contacts (24V.) energizing the bimetal 

heater in the #4 Heating Element Sequencer.

6.   HEATING ELEMENT #4 ENERGIZED 

a.  45 seconds after bimetal heater in #4 Heating 

Element Sequencer is energized, its main 

contacts and auxiliary contacts close, the main 

contacts (240V.) energizing heating element #4 

and its pilot light (highest in the boiler) – nothing 

is connected to the auxiliary contacts.

SECTION II:  OPERATING AND SERVICE INSTRUCTIONS

7.  ROOM THERMOSTAT OPENS
8.  HEATING ELEMENTS DE-ENERGIZED

  When the thermostat is satisfied and opens its 

contacts, the low voltage circuits to the Heating 

Element Relay and the Heating Element Sequencers 

are broken.  The Heating Element Relays “drop-out” 

immediately and totally de-energize the Heating 

Elements and pilot lights.  After a time delay of 45 

seconds, the main contacts of all the Sequencers 

“break” thus resetting the Heating Element Relays.

9.  CIRCULATOR MOTOR DE-ENERGIZED 
  Simultaneous with the breaking of the low voltage 

circuit to the Heating Element Sequencers is the 

breaking of the low voltage circuit to the Circulator 

Relay by the opening of the thermostat contact.  

After a time delay of 90 seconds after all Heating 

Elements are “off” the bimetal heater opens the 

main contacts in the Circulator Relay thus stopping 

the circulator.  When the boiler is zoned with 

circulator and switching relays as illustrated in 

Figure 6 on Page 8 the circulator switch must be in 

the “constant” position; therefore the circulator will 

not have any delay when the thermostat(s) closes or 

opens its contacts.

B.

  Continuous Circulator Operation

 

If the Circulator Switch (located in the control portion 

of the Boiler Jacket) is placed in the “CONT.” position, 

the Circulator will run continuously and the Heating 

Elements will sequence as in steps 3-6 and 8 above.

C.

  Dual Limit Operation

 

The Dual Limit Control consists of two independently 

adjustable temperature limits.  The left hand adjustment 

is for the safety limit and should be set initially for 

220°F.  The lower right hand adjustment is for the 

operating limit and should be set for 210°F with a 

differential setting (upper right hand adjustment) of 10º.  

These adjustments may be varied to suit the individual 

installation, with minimum of 10° difference between 

the limit settings.  If the setting of the operating Limit 

or the safety limit is reached, the Heating Elements only 

will be de-energized; the Circulator will continue to 

run.  If the Circulator Switch is in the “INT.” position, 

the Circulator runs until the thermostat is satisfied and 

the main contacts on the Circulator Relay open.

WARNING

Before installation of the boiler is considered 

complete, the operation of the boiler controls 

should be checked, particularly the Operating & 

Safety Limit Controls.

Summary of Contents for Care-Free E4

Page 1: ...a r e b m u N l a i r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e l i o b r e b m u N l e d o M r e l i o B r e b m u N l a i r e S r e l i o B e t a D n o i t a l l a t s n I 4 E r o t c a r t n o C g n i t a e H r e b m u N e n o h P s s e r d d A D N A G N I T A R E P O N O I T A L L A T S N I R O F S N O I T C U R T S N I E C I V R E S E E R F E R A C R E L I O B C I R T C E ...

Page 2: ...es Two Ventilation Openings one located at top and one at bottom each opening to have 25 sq in net free area Boiler Model DOE HEATING CAPACITY BTU HR AFUE KW Rating 240V Amps 240V No and Size of Elements Recommended Power Supply to Boiler Appx Wt Full Lb Water Contents Gal Water Flow Rate GPM Based on 20 F Temp Rise and Boiler Capacity At 240V 220V 208V Min Wire Size Max Fuse Size Amps 240V 220V 2...

Page 3: ...epending upon wall construction passing through the holes provided in the wall mounting channels Figure 1 shows bolt center dimensions It is recommended that 1 2 plywood be used as a base for mounting the boiler so that the structure is adequate to carry the weight imposed upon it see Figure 1 for weight of boiler when full of water Boiler should be level for proper operation of BUILT IN AIR SEPAR...

Page 4: ...tor will be furnished G A Prewired Low Voltage Control System is furnished with every CARE FREE boiler 1 All controls are furnished in a compartment at the front of the boiler for easy accessibility In addition to the Transformer used to power the system are the following Circulator Relay Heating Element Sequencers one per Heating Element Dual High Limit Control Circulator Operation Selector Switc...

Page 5: ...IONS 7 ROOM THERMOSTAT OPENS 8 HEATING ELEMENTS DE ENERGIZED When the thermostat is satisfied and opens its contacts the low voltage circuits to the Heating Element Relay and the Heating Element Sequencers are broken The Heating Element Relays drop out immediately and totally de energize the Heating Elements and pilot lights After a time delay of 45 seconds the main contacts of all the Sequencers ...

Page 6: ... Figure 4 Wiring Diagram Model E 4 Boilers ...

Page 7: ...ator light is on it indicates its respective heating element is energized If the light is off it indicates 1 The heating element has not been energized 2 The heating element sequencer is malfunctioning E Built In Air Eliminator An air eliminator has been built into the top of the electric boiler and a 3 4 tapping is provided with nipple and tee for connection of Relief Valve and a float type Air V...

Page 8: ...e cost of removing and reinstalling the alleged defective part or its replacement and all labor and material connected therewith and transportation to and from U S Boiler Company Inc b Components that are part of the heating system but were not furnished by U S Boiler Company Inc as part of the residential boiler c Improper burner adjustment control settings care or maintenance d This warranty can...

Reviews: