6
Appendix A: Special Requirements For Side-Wall Vented Appliances
In The Commonwealth of Massachusetts
ImPOrTaNT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for
installation of side-wall vented gas appliances as follows:
1. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where
the bottom of the vent terminal and the air intake is installed below four feet above grade the following
requirements must be satisfied:
a. If there is not already one present, on each floor level where there are bedroom(s), a carbon
monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The carbon
monoxide detector shall comply with NFPA 720 (2005 Edition).
b. A carbon monoxide detector shall be located in the room that houses the appliance or equipment
and shall:
i. Be powered by the same electrical circuit as the appliance or equipment such that only one
service switch services both the appliance and the carbon monoxide detector;
ii. Have battery back-up power;
iii. Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
iv. Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized
under 527 CMR.
c. A product-approved vent terminal must be used, and if applicable, a product-approved air intake
must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy
of the installation instructions shall remain with the appliance or equipment at the completion of the
installation.
d. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet
directly above the location of the vent terminal. The plate shall be of sufficient size to be easily read
from a distance of eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where
the bottom of the vent terminal and the air intake is installed above four feet above grade the following
requirements must be satisfied:
a. If there is not already one present, on each floor level where there are bedroom(s), a carbon
monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The carbon
monoxide detector shall comply with NFPA 720 (2005 Edition).
b. A carbon monoxide detector shall :
i. Be located in the room that houses the appliance or equipment
ii. Be either hard-wired or battery powered or both; and
iii. Comply with NFPA 720 (2005 Edition)
c. A product-approved vent terminal must be used, and if applicable, a product-approved air intake
must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy
of the installation instructions shall remain with the appliance or equipment at the completion of the
installation.
Summary of Contents for CHG CHG150
Page 25: ...25 Figure 8 3 Piping Method 1 Heat Indirect Water Heater Figure 8 2 Piping Method 1 Heat Only ...
Page 29: ...29 Figure 8 8 Piping Method 2 Heat Only Figure 8 9 Piping Method 2 Heat Indirect Water Heater ...
Page 36: ...36 Figure 9 1 Wiring Connections Diagram ...
Page 37: ...37 Figure 9 2 Ladder Diagram ...
Page 38: ...38 Figure 9 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 40: ...40 CHG Series Lighting and Operating Instructions ...
Page 46: ...46 Figure 11 2 Basic Menu Tree ...
Page 54: ...54 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 63: ...63 ...
Page 65: ...65 ...
Page 66: ...66 ...
Page 67: ...67 ...
Page 69: ...69 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 70: ...70 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 71: ...71 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 72: ...9EARS IN 3ERVICE 3ERVICE HARGE AS OF 2ETAIL 0RICE O HARGE ...