1
TablE 7.1: suMMarY OF HOriZOnTal VEnTing OPTiOns
VENT OPTION #
1
2
3
CLASSIFICATION USED IN THIS
MANUAL
HORIZONTAL
CONCENTRIC
HORIZONTAL
TWIN PIPE
HORIZONTAL
CONCENTRIC
ILLUSTRATED IN FIGURE
7.2
7.3
7.2
VENT PIPE PENETRATION
THROUGH STRUCTURE
WALL
WALL
WALL
AIR INTAKE PIPE PENETRATION
THROUGH STRUCTURE
WALL
WALL
WALL
VENT PIPE SIZE
60/100 mm
CONCENTRIC
3”
80/125mm
CONCENTRIC
AIR INTAKE PIPE SIZE
3”
MAXIMUM
LENGTH
VENT
FCM070
32ft
55ft
55ft
FCM090
32ft
55ft
55ft
FCM120
18ft
55ft
55ft
INLET
FCM070
32ft
55ft
55ft
FCM090
32ft
55ft
55ft
FCM120
18ft
55ft
55ft
MINIMUM
LENGTH
VENT
FCM070
10in
2ft
2ft
FCM090
10in
2ft
2ft
FCM120
10in
2ft
2ft
INLET
FCM070
10in
2ft
2ft
FCM090
10in
2ft
2ft
FCM120
10in
2ft
2ft
VENT TERMINAL
60/100 mm
CONCENTRIC
P/N 8110701
P/N 101494-01
CONCENTRIC
or P/N 101544-01
SNORKEL
AIR INTAKE TERMINAL
3” 90 ELBOW
VENT MATERIAL
U.S. Boiler
60/100mm VENT
COMPONENTS
SHOWN IN
TABLE 7.4a
(Note #1)
APPROVED
STAINLESS
STEEL VENT
SYSTEM SHOWN
IN TABLE 7.5
U.S. Boiler
80/125mm VENT
COMPONENTS
SHOWN IN
TABLE 7.4b
AIR INTAKE MATERIAL
GALVANIZED OR
PVC
Note #1: In Vent Option #1, the 80/125mm concentric straight section (P/N 101162-01) shown in Table 7.4a may be used
between the boiler and the first 80/125 x 60/100 reducing elbow. If this is done, the overall maximum vent length is still
restricted to that shown for Vent Option #1 in Table 7.1 above.
Horizontal Terminal Clearance Requirements (Continued):
• Vent terminal must be at least 6 feet from an inside corner.
• Under certain conditions, water in the flue gas may condense, and possibly freeze, on objects around the vent terminal
including on the structure itself. If these objects are subject to damage by flue gas condensate, they should be moved or
protected.
• If possible, install the vent and air intake terminals on a wall away from the prevailing wind. Reliable operation of this
boiler cannot be guaranteed if these terminals are subjected to winds in excess of 40 mph.
• Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near swimming
pools. See Section IV for
more information on possible contaminates.
Summary of Contents for FREEDOM
Page 8: ...8 Figure 1 Wall Mounting Hole locations ...
Page 9: ...9 Figure 5 2 Boiler Mounting Hardware ...
Page 11: ...11 Figure 6 1 Boiler Installed In A Confined Space Ventilation Air From Inside ...
Page 42: ...42 FIGURE 7 51 CONDENSATE PIPING ARRANGEMENT ...
Page 55: ...55 Figure 10 1 Wiring Connections Diagram ...
Page 56: ...56 Figure 10 2 Ladder Diagram ...
Page 57: ...57 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 60: ...60 FCM Series Lighting and Operating Instructions ...
Page 66: ...66 FIGURE 12 2 BASIC MENU TREE ...
Page 75: ...75 ...
Page 77: ...77 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...
Page 83: ...83 150 151 152 153 154 155 ...
Page 84: ...84 156 157 158 159 160 161 ...
Page 85: ...85 162 ...