7
BOILER
MODEL
BURNER
MIN.
INPUT
(GPH)
BURNER
MAX.
INPUT
(GPH)
BURNER
MODEL
DIFFUSER
OPENING
(IN.)
APPROX. HIGH FIRE
DAMPER SETTING -
TOP / BOTTOM DAMPER
(IN.)
HIGH FIRE
PUMP
PRESSURE
(PSI)
NOZZLE
MAKE
NOZZLE DATA
GPH X ANGLE
- TYPE
MPC4
3.0
3.55
C1-O
3/16
5/16 / Closed
300
Delavan
2.5 X 90 - B
MPC5
3.0
5.5
C1-O
3/8
1 / Closed
300
Delavan
3.5 X 80 - B
MPC6
3.0
7.1
C1-O
1/4
1-3/32 / 1-3/8
270
Delavan
4.5 X 90 - B
MPC7
3.0
8.7
C1-O
1/4
3/4 / 3/4
270
Delavan
6.0 X 90 - B
MPC8
5.5
10.2
C2-OA
1/4
1 / Closed
300
Monarch
6.5 X 80 - PLP
MPC9
5.5
11.8
C2-OA
1/4
13/16 / 11/16
300
Monarch
7.0 X 80 - PLP
MPC10
5.5
13.4
C2-OA
3/16
Both Wide Open
250
Monarch
8.5 X 80 - PLP
MPC11
5.5
15.0
C2-OA
3/8
1-3/8 / 1-1/4
260
Monarch
9.5 X 70 - PLP
MPC12
5.5
16.6
C2-OB
3/8
1-3/4 / 1-3/4
300
Monarch
10.5 X 70 - PLP
MPC13
5.5
18.2
C2-OB
3/8
1-1/2 / 1-1/4
300
Monarch
11.0 X 80 - PLP
MPC14
5.5
19.8
C2-OB
1/2
1-1/4 / 1-1/4
270
Monarch
12.0 X 80 - PLP
MPC15
5.5
21.5
C3-O
1/2
1-7/8 / Closed
280
Hago
14.0 X 80 - BPS
MPC16
7.4
23.0
C3-O
5/16
1-3/4 / 1-3/4
225
Hago
16.0 X 80 - BPS
MPC17
7.4
24.5
C3-O
3/8
2 / 2
280
Hago
15.0 X 80 - BPS
MPC18
7.4
26.0
C3-O
3/8
Both Wide Open
300
Hago
16.0 X 80 - BPS
Table XIVa: Power Flame #2 Oil Burner Specifications
BOILER
MODEL
BURNER
MIN.
INPUT
(MBH)
BURNER
MAX.
INPUT
(MBH)
BURNER
MODEL
DIFFUSER
OPENING
(IN.)
APPROX. HIGH FIRE
DAMPER SETTING -
TOP / BOTTOM DAMPER
(IN.)
APPROX. NAT. GAS
MANIFOLD PRESS.
AT ORIFICE TEE
(“WC)
MINIMUM
NAT. GAS
INLET PRESS.
(“WC) **
MPC4
300
500
JR15A-10
N/A
1/2 *
1.2
4.0
MPC5
300
773
JR30A-12
N/A
3/4 *
1.5
4.2
MPC6
300
995
JR30A-12
N/A
13/16 *
2.5
4.9
MPC7
600
1216
JR30A-12
N/A
1-3/32 *
3.5
5.6
MPC8
650
1438
JR50A-15
N/A
3/4 *
2.0
5.9
MPC9
650
1660
JR50A-15
N/A
Wide Open *
1.5
6.9
MPC10
650
1881
JR50A-15
N/A
3*
1.8
5.8
MPC11
650
2103
JR50A-15
N/A
2-3/8*
2.1
5.0
MPC4
300
500
C1-G-10
3/16
5/16 / Closed
1.8
4.0
MPC5
300
773
C1-G-10
3/8
1 / Closed
3.8
4.4
MPC6
300
995
C1-G-12
1/4
1-3/32 / 1-3/8
2.4
4.8
MPC7
300
1216
C1-G-12
1/4
3/4 / 3/4
3.5
5.5
MPC8
750
1438
C2-G-15
1/4
1 / Closed
1.0
6.0
MPC9
750
1660
C2-G-15
1/4
13/16 / 11/16
1.4
6.8
MPC10
750
1881
C2-G-20A
3/16
Both Wide Open
2.6
5.9
MPC11
750
2103
C2-G-20A
3/8
1-3/8 / 1-1/4
2.0
6.5
MPC12
750
2325
C2-G-20A
3/8
1-3/4 / 1-3/4
2.4
5.7
MPC13
750
2547
C2-G-20B
3/8
1-1/2 / 1-1/4
2.9
6.5
MPC14
750
2769
C2-G-20B
1/2
1-1/4 / 1-1/4
3.0
6.5
MPC15
900
2991
C3-G-20
1/2
1-7/8 / Closed
1.7
5.6
MPC16
900
3213
C3-G-20
5/16
1-3/4 / 1-3/4
2.3
6.9
MPC17
900
3435
C3-G-20
3/8
2 / 2
2.6
6.6
MPC18
900
3657
C3-G-20
3/8
Both Wide Open
2.5
6.8
* ON “JR” BURNERS, THIS DIMENSION IS THE GAP BETWEEN THE TWO DAMPER BLADES.
** MINIMUM INLET PRESSURE FOR STANDARD UL GAS TRAINS ONLY. CONSULT FACTORY FOR ADDITIONAL INFORMATION.
Table XIVb: Power Flame Gas Burner Specifications
Summary of Contents for MPC
Page 19: ...19 Figure 5 Manual or Hydraulic Draw up Section Assembly ...
Page 28: ...28 Table VII Modular Return Water Mixing Tube RWMT RC ...
Page 29: ...29 Figure 13 Return Water Mixing Tube RC Assembly and Installation ...
Page 78: ...78 Figure 56 MPC Common Bare Boiler Components ...
Page 80: ...80 Figure 56 MPC Common Bare Boiler Components continued ...
Page 82: ...82 Figure 57 MPC Front Center Section Frame Rail Assembly ...
Page 84: ...84 Figure 58 MPC Rear Section Frame Rail Assembly ...
Page 86: ...86 Figure 59 MPC Return Water Mixing Tube RC Assembly ...
Page 88: ...88 Figure 60 MPC Heat Exchanger Insulation Wrapper ...
Page 90: ...90 Figure 61 MPC Internal Wiring Harness Components ...
Page 92: ...92 Figure 62 MPC Jacket Panel Assembly ...
Page 94: ...94 Figure 62 MPC Jacket Panel Assembly continued ...
Page 96: ...96 Figure 63 MPC 2 nd and 3 rd Pass Flueway Baffles ...