3
wARNING
:
Do not
operate a
single
line system with the
by-pass plug installed. Operating a
single
line system with the by-pass plug installed
will result in damage to the pump shaft seal.
NOTE
: Pump pressure was factory pre-set but must
be checked at time of burner start-up. A
pressure gauge is attached to the
PRESSURE/
BLEEDER PORT
(7) for pressure readings.
Two
PIPE CONNECTORS
(4) are supplied
with the burner for connection to either a
single or two-line system. Also supplied
are two
ADAPTORS
(3), two female ¼”
NPT to adapt oil lines to burner pipe
connectors. All pump port threads are
British
Parallel Thread
design. Direct connection
of NPT threads to the pump
will damage
the
pump body.
Riello manometers and vacuum gauges
do not
require any adapters, and can be safely
connected to the pump ports. An NPT x
metric adapter
must
be used when connecting
other gauge models.
viii.
Replace Burner Cover
and Tighten Burner
Cover Screws.
c. Place oil burner gasket on burner and align holes.
d.
Remove three (3) 5/16-18 x 3/4 lg. cap screw
from burner swing door used for mounting
burner.
e. Thread (1) 5/16-18 x 3/4 lg. cap screw,
approximately three (3) full turns, into tapping
located at 12:00 o'clock on burner swing door.
f. Insert oil burner into the opening of burner
swing door. Align and engage keyhole slot in
burner flange over head of protruding cap screw
installed in previous Step. Rotate burner to the
right to lock flange behind head of cap screw.
g. Align holes and install two (2) remaining cap
screws. Level burner and fully tighten all three
(3) screws.
Summary of Contents for MST288
Page 11: ...11 Figure 4 Boiler Removal from Skid ...
Page 19: ...19 Figure 9 Float Type LWCO and Pressure Limit Installation ...
Page 25: ...25 Figure 12 Recommended Boiler Piping for Gravity Return Steam Boiler ...
Page 34: ...34 Figure 18 Wiring Diagram Steam Hydrolevel CG450 Probe LWCO ...
Page 35: ...35 Figure 18A Wiring Diagram Riello 40 Series Burner Steam Hydrolevel CG450 Probe LWCO ...
Page 36: ...36 Figure 19 Wiring Diagram Steam McDonnell Miller PS 801 Probe LWCO ...
Page 37: ...37 Figure 19A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller PS 801 Probe LWCO ...
Page 38: ...38 Figure 20 Wiring Diagram Steam McDonnell Miller 67 Float LWCO ...
Page 39: ...39 Figure 20A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller 67 Float LWCO ...
Page 45: ...45 Figure 24 L1 and V1 Head Electrode Positioning and Gun Setting Beckett AFG ...
Page 58: ...58 Bare Boiler Assembly ...
Page 60: ...60 Jacket Assembly ...
Page 62: ...62 MST288 Thru MST629 Steam Boilers Trim and Controls ...
Page 64: ...64 Beckett AFG Burner ...