6
TABLE 1A: DIMENSIONAL DATA (SEE FIGURE 1)
TABLE 1B: RATING DATA
Boiler
Model No.
Dimensions (See
Figure 1)
Water Content (To Normal
Water Line) - Gallons
Heat Transfer
Surface Area
- sq. Ft.
Actual Shipping
Weight (LB.)
"A"
"B"
"C"
With Tankless
Heater
Non-Heater
MST288
22-5/8"
24"
6"
15.3
14.9
20.29
607
MST396
22-5/8"
24"
6"
15.3
14.9
20.29
607
MST513
28-5/8"
30"
6"
19.7
19.3
27.29
744
MST629
34-5/8"
36"
7"
24.1
23.8
34.29
881
NOTE: 1: Maximum Working Pressure: Steam - 15 PSI
Boiler
Model
No.
Burner Capacity
I=B=R NET
Ratings
Minimum Chimney
Requirements
AFUE
%
GPH MBH DOE Heating
Capacity MBH
Steam
MBH
Steam
Sq. Ft.
Round
In. Dia.
Rectangle
In. x In.
Height
Ft.
MST288
0.75
105
92
69
288
6
8 X 8
15
86.0
MST396
1.05
147
127
95
396
6
8 X 8
15
86.0
MST513
1.35
189
164
123
513
7
8 X 8
15
86.0
MST629
1.65
231
201
151
629
7
8 X 8
15
86.0
Summary of Contents for MST288
Page 11: ...11 Figure 4 Boiler Removal from Skid ...
Page 19: ...19 Figure 9 Float Type LWCO and Pressure Limit Installation ...
Page 25: ...25 Figure 12 Recommended Boiler Piping for Gravity Return Steam Boiler ...
Page 34: ...34 Figure 18 Wiring Diagram Steam Hydrolevel CG450 Probe LWCO ...
Page 35: ...35 Figure 18A Wiring Diagram Riello 40 Series Burner Steam Hydrolevel CG450 Probe LWCO ...
Page 36: ...36 Figure 19 Wiring Diagram Steam McDonnell Miller PS 801 Probe LWCO ...
Page 37: ...37 Figure 19A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller PS 801 Probe LWCO ...
Page 38: ...38 Figure 20 Wiring Diagram Steam McDonnell Miller 67 Float LWCO ...
Page 39: ...39 Figure 20A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller 67 Float LWCO ...
Page 45: ...45 Figure 24 L1 and V1 Head Electrode Positioning and Gun Setting Beckett AFG ...
Page 58: ...58 Bare Boiler Assembly ...
Page 60: ...60 Jacket Assembly ...
Page 62: ...62 MST288 Thru MST629 Steam Boilers Trim and Controls ...
Page 64: ...64 Beckett AFG Burner ...